Operation manual

 

1

 

EWWP045~06 ECB1~3MUW

 

Packaged water-cooled water chillers

 

4PW30041-1A

 

C

 

ONTENTS

 

Page

 

Introduction ....................................................................................... 1

 

Technical specifications ............................................................................. 1
Electrical specifications ............................................................................. 2

 

Description ........................................................................................ 2

 

Function of the main components.............................................................. 3
Safety devices............................................................................................ 4
Internal wiring - Parts table ........................................................................ 4

 

Before operation................................................................................ 5

 

Checks before initial start-up ..................................................................... 5
Water supply .............................................................................................. 5
General recommendations ........................................................................ 5

 

Operation 16~24Hp........................................................................... 5

 

Digital controller ......................................................................................... 5
Working with the 16~24Hp units ................................................................ 6
Advanced features of the digital controller................................................. 8

 

Operation 32~72Hp......................................................................... 12

 

Digital controller ....................................................................................... 12
Working with the 32~72Hp units .............................................................. 12
Advanced features of the digital controller............................................... 14

 

Troubleshooting ............................................................................... 19

Maintenance.................................................................................... 20

 

Important information regarding the refrigerant used .............................. 20
Maintenance activities ............................................................................. 20
Disposal requirements ............................................................................. 20

 

I

 

NTRODUCTION

 

This operation manual concerns packaged water-cooled water
chillers of the Daikin EWWP-KA series. These units are provided for
indoor installation and used for cooling and/or heating applications.
The units can be combined with Daikin fan coil units or air handling
units for air conditioning purposes. They can also be used for
supplying water for process cooling.

This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance. 

In case of persisting problems contact your local dealer.

 

Technical specifications 

 

(1)

 

EWWP045KAW1M

ECB1MUW

EWWP055KAW1M

ECB2MUW

EWWP065KAW1M

ECB3MUW

 

Packaged water-cooled water chillers

 

Operation manual

 

READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW THIS MANUAL AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
Read the chapter 

"User settings menu" on page 14

 before

changing the parameters. 

 

Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in 

"Checks before initial

start-up" on page 5

.

 

(1) Refer to the engineering data book for the complete list of specifications.

 

General

 

Hp

16

20

24

32

36

40

44

48

52

56

60

64

68

72

 

Nominal cooling 

capacity

 

(a)

(kW)

 

43.0

56.0

65.0

86

99

112

121

130

142

155

168

177

186

195

Nominal input

 

(b)

(kW)

 

12.1

16.0

18.3

24.2

28.1

32.0

34.3

36.6

40.2

44.1

48.0

50.3

52.6

54.9

Dimensions HxWxD

 

(mm)

 

600 x 600 x 1200

1200 x 600 x 1200

1800 x 600 x 1200

Machine weight

 

(kg)

 

300

320

334

600

620

640

654

668

920

940

960

974

988

1002

 

Connections

 

• water inlet

(inch)

 

2x FBSP 1.5"

2x 2x FBSP 1.5"

3x 2x FBSP 1.5"

 

• water outlet

(inch)

 

2x FBSP 1.5"

2x 2x FBSP 1.5"

3x 2x FBSP 1.5"

 

Compressor

 

Type

hermetically sealed scroll

Qty x model

 

2x

JT212DA-YE

2x

JT300DA-YE

2x

JT335DA-YE

4x

JT212DA-YE

2x

JT212DA-YE 

+ 2x 

JT300DA-YE

4x

JT300DA-YE

2x

JT300DA-YE 

+ 2x 

JT335DA-YE

4x

JT335DA-YE

4x

 

JT212DA-YE

 

+ 2x

 

JT300DA-YE

 

2x

 

JT212DA-YE

 

+ 4x

 

JT300DA-YE

 

6x

 

JT300DA-YE

 

4x

 

JT300DA-YE

 

+ 2x

 

JT335DA-YE

 

2x

 

JT300DA-YE

 

+ 4x

 

JT335DA-YE

 

6x

 

JT335DA-YE

 

Speed

 

(rpm)

 

2900

2900

2900

Oil type

FVC 68D

FVC 68D

FVC 68D

Oil charge volume

 

(l)

 

2x 2.7

4x 2.7

6x 2.7

 

Evaporator

 

Type

brased plate heat exchanger

Qty

1

2

3

Nominal water flow

 

(l/min)

 

123

161

186

247

284

321

347

373

407

444

482

507

533

559

Water flow range

 

(l/min)

62 -247

80 - 321

93 - 373 123 - 493 142 - 568 161 - 642 173 -694 186 - 745

 

204 - 814

222 - 889

241 -963

254-1015

267-1066

280-1118

 

Condenser

 

Type

brased plate heat exchanger

Qty

1

2

3

Nominal water flow

 

(l/min)

 

157

205

237

314

362

410

442

474

519

567

614

647

679

711

Water flow range

 

(l/min)

79 - 314 102 - 410 118 - 474 157 - 629 181 -724 205 - 819 221 - 883 237 - 948

 

260-1038

283-1133

307-1229

323-1293

339-1357

355-1422

 

(a) The nominal cooling capacity is based on:

- entering water temperature of 12°C
- chilled water temperature of 7°C
- condenser in/out water temperature of 30/35°C

(b) The nominal input includes total input of the unit: compressor, control circuit and water pumps.

Summary of Contents for EWWP045KAW1M

Page 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Page 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Page 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Page 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Page 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Page 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Page 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Page 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Page 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Page 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Page 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Page 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Page 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Page 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Page 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Page 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Page 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Page 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Page 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Page 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Page 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Page 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Page 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Page 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Page 25: ...NOTES NOTES...