background image

D-EIMWC01008-16EU - 11/20 

refrigerating 
system 

The  following  precautions  should  be  taken  before 
working on the refrigerant circuit: 

— obtain permit for hot work (if required); 
—  ensure  that  no  flammable  materials  are 
stored  in  the  work  area  and  that  no  ignition 
sources  are  present  anywhere  in  the  work 
area; 
—  ensure  that  suitable  fire  extinguishing 
equipment is available; 
—  ensure  that  the  work  area  is 

properly 

ventilated

  before  working  on  the  refrigerant 

circuit or before welding, brazing or soldering 
work; 
—  ensure  that  the  leak  detection  equipment 
being  used  is  non-sparking,  adequately 
sealed or intrinsically safe; 
—  ensure  that  all  maintenance  staff  have 
been instructed. 
The  following  procedure  should  be  followed 
before working on the refrigerant circuit: 

1. 

remove refrigerant (specify the residual 

pressure); 

2. 

purge circuit with 

inert gas

 (e.g. 

nitrogen); 

3. 

evacuate to a pressure of 0,3 (abs.) bar 

(or 0,03 MPa); 

4. 

purge again with 

inert gas

 (e.g. 

nitrogen); 

5. 

open the circuit. 

 

The  area  should  be  checked  with  an  appropriate 
refrigerant detector prior to and during any hot work 
to  make  the  technician  aware  of  a  potentially 
flammable atmosphere. 
If  compressors  or  compressor  oils  are  to  be 
removed,  it  should  be  ensured  that  it  has  been 
evacuated  to  an  acceptable  level  to  ensure  that 
there  is  no  flammable  refrigerant  remaining  within 
the lubricant. 

Only  refrigerant  recovery  equipment  designed 
for  use  with  flammable  refrigerants  should  be 
employed. 

If  the  national  rules  or  regulations  permit  the 
refrigerant to be drained, this should be done safely, 
using  a  hose,  for  example,  through  which  the 
refrigerant 

is 

discharged 

into 

the 

outside 

atmosphere  in  a  safe  area.  It  should  be  ensured 
that 

an 

inflammable 

explosive 

refrigerant 

concentration  cannot  occur  in  the  vicinity  of  an 
ignition  source  or  penetrate  into  a  building  under 
any circumstance. 
In the case  of refrigerating systems with an indirect 
system,  the  heat-transfer  fluid  should  be  checked 
for the possible presence of refrigerant. 
After  any  repair  work,  the  safety  devices,  for 
example  refrigerant  detectors  and  mechanical 
ventilation  systems,  should  be  checked  and  the 
results recorded. 
It  should  be  ensured  that  any  missing  or  illegible 
label  on  components  of  the  refrigerant  circuit  is 
replaced. 
Sources  of  ignition  should  not  be  used  when 
searching for a refrigerant leak. 

 

 
 

This chiller, whether with R134a,R513A or R1234ze, 
must  be  maintained  by  qualified  technicians. 
Before  beginning  any  work  on  the  system  the 

personnel  shall  assure  that  all  security  precautions 
have been taken.

 

 

Always  protect  the  operating  personnel  with 
personal  protective  equipment  appropriate  for  the 

tasks  to  be  performed.  Common  individual  devices  are: 
Helmet,  goggles,  gloves,  caps,  safety  shoes.  Additional 
individual  and  group  protective  equipment  should  be 
adopted after an adequate analysis of the specific risks in 
the  area  of  relevance,  according  to  the  activities  to  be 
performed. 

 
 
 
 

10.  EWLD J, EWLH AND EWLS 

VERSIONS  

 
CONNECTING THE REFRIGERANT CIRCUIT  

 
This product is factory charged with N

2

 

 

The units are equipped with a refrigerant inlet 
(discharge side) and a refrigerant outlet (liquid side) for 
the connection to a remote condenser. This circuit must 
be provided by a licensed technician and must comply 
with all relevant European and national regulations. 
 

10.1.  Precautions when handling 

piping 

 

 If air or dirt gets in the water circuit, problems may   

 

         occur. Therefore,  always  take  into  account  the   
          following  when connecting the water circuit:                     

1.

 

Use clean pipes only. 

2. 

Hold the pipe end downwards when removing  

        

burrs. 

3. 

Cover the pipe end when inserting it through a 

     wall so that no dust and dirt enter.  
 

The  discharge  and  liquid  line  must  be  welded  directly  to  the 
remote  condenser  piping.  For  use  of  the  correct  pipe  diameter 
see table of Technical specifications. 
 

 

 Make sure the pipes are filled with N

2

 during welding in  

         order to protect the pipes against soot. 
         There should be no blockage (stopvalve, solenoid  
         valve) between the remote condenser and the  
         provided liquid injection of the compressor. 
 

10.2.  Leak test and vacuum drying 

 

The units were checked for leaks by the manufacturer. 
After connection of the piping, a leak test must be performed 
and the air in the refrigerant piping must be evacuated to a 
value of 4 mbars absolute by means of a vacuum pumps. 
 
 

 Do not purge the air with refrigerants. Use a vacuum  

        pump to vacuum the installation. 
 

10.3.  Charging the unit 

1.   Perform an integral pre-start inspection like explained in  
      

BEFORE STARTING

”. 

 

 Carefully  perform  all  required  procedures  like 
explained 

        in chapters from which is referred to in chapter  
        

“BEFORE STARTING”

, but do not start the unit. 

 
It  is  also  necessary  to  read  the  operation  manual  delivered 
with the unit. This will contribute to understand the operation 
of the unit and its electronic controller. 
 

Pre-charge of refrigerant without operation of the unit 

 
2.    Use the 

1/4” SAE Flare stop valve on the filter drier to 

       pre-charge  the unit with the complete calculated pre- 
       charge. 
       

Do not operate the compressor for pre-charging, 

Summary of Contents for EWWD J Series

Page 1: ... water cooled screw chillers EWLD110J SS EWLD265J SS EWLH 80J SS EWLH190J SS EWLS 110J SS EWLS270J SS Refrigerant R 134a R1234ze R513A English 2 Deutsch 13 Français 25 Nederlands 36 Español 48 Italiano 60 Ελληνικά 72 Português 84 Русский 96 Swedish 107 Norsk 118 Finnish Suomi 129 Polski 140 Čech 152 Hrvat 163 Magyar 174 Român 185 Slovenski 196 Български 207 Slovenský 219 Installation Operation and...

Page 2: ...d to replace such personnel EWWD120J SS 280J SS EWWH090J SS 200J SS EWWS120J SS 270J SS EWLD 110J SS 265J SS EWLH 80J SS 190J SS EWLS 110J SS 270J SS Label Identification 1 Unit nameplate data 5 Manufacturer s logo 2 Lifting instructions 6 Emergency stop 3 Hazardous Voltage warning 7 Non flammable gas symbol 4 Electrical hazard symbol 8 Gas type ...

Page 3: ...R1234ZE 9 8 5 ADDITIONAL GUIDELINES FOR SAFE USE OF R1234ZE E FOR EQUIPMENT LOCATED IN THE OPEN AIR 9 8 6 ADDITIONAL GUIDELINES FOR SAFE USE OF R1234ZE E FOR EQUIPMENT LOCATED IN A MACHINERY ROOM 9 9 MAINTENANCE 10 9 1 ROUTINE MAINTENANCE FOR R1234ZE 10 10 EWLD J EWLH AND EWLS VERSIONS 11 10 1 PRECAUTIONS WHEN HANDLING PIPING 11 10 2 LEAK TEST AND VACUUM DRYING 11 10 3 CHARGING THE UNIT 11 11 PREP...

Page 4: ...OPER INSTALLATION OR ATTACHEMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUIPMENT BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATI...

Page 5: ... 1600 1607 Operation weight Kg 1663 1675 Connections Chilled water inlet outlet 2 inch 3 Condenser water inlet outlet 2 inch 4 2 Victaulic coupling Model EWLD J 110 130 145 165 195 Dimensions HxWxL mm 1020x913x2726 Weight Unit weight Kg 1086 1101 1169 1164 1236 Operation weight Kg 1090 1114 1183 1183 1263 Connections Chilled water inlet outlet 2 inch 3 Liquid line inlet connection 3 inch 1 3 8 Gas...

Page 6: ...tion with Glycol Fixed minimum capacity at 100 2 Operation with Glycol below 4 C Evap LWT 3 Some units could work partialized in this area EWWH J EWLH J 1 Operation with Glycol Fixed minimum capacity at 100 2 Operation with Glycol below 4 C Evap LWT 3 Operation with fixed minimum capacity at 100 EWWS J EWLS J 1 Operation with Glycol below 4 C Evap LWT 2 Some units could work partialized in this ar...

Page 7: ...ling in the unit to a minimum It drilling is impreventable remove the iron filling thoroughly in order to prevent surface rust 6 UNPACKING AND PLACING THE UNIT 1 Remove the wooden beams from the unit 2 Install vibration mountings in case of an installation where noise and vibration might an impediment 3 Set the unit on a solid and level foundation The unit should be installed on a solid base It is...

Page 8: ...21 66 19 33 10 2 01 9 4 01 29 7 27 48 12 53 67 19 78 9 2 09 10 4 15 30 7 48 49 12 85 68 20 23 8 2 17 11 4 29 31 7 70 50 13 18 69 20 69 7 2 26 12 4 43 32 7 92 51 13 51 70 21 16 6 2 34 13 4 58 33 8 15 52 13 85 71 21 64 5 2 43 14 4 73 34 8 39 53 14 20 72 22 13 4 2 53 15 4 88 35 8 63 54 14 55 73 22 62 3 2 62 16 5 04 36 8 87 55 14 91 74 23 12 2 2 72 17 5 20 37 9 12 56 15 28 75 23 63 1 2 82 18 5 37 38 9...

Page 9: ...mity with the directives along with the documentation Before machine installation and commissioning the people involved in this activity must have acquired the information necessary to carry out these tasks applying all the information collected in this book Do not allow unauthorized and or unskilled personnel to access the unit The chiller has to be installed in open air or machinery room locatio...

Page 10: ...be done with due consideration of local airflow patterns accounting for location sources of ventilation and louvers Consideration shall also be given to the possibility of mechanical damage or contamination At least one detector shall be installed in each machinery room or the occupied space being considered and or at the lowest underground room for refrigerants heavier than air and at the highest...

Page 11: ... technicians Before beginning any work on the system the personnel shall assure that all security precautions have been taken Always protect the operating personnel with personal protective equipment appropriate for the tasks to be performed Common individual devices are Helmet goggles gloves caps safety shoes Additional individual and group protective equipment should be adopted after an adequate...

Page 12: ...h the product NOTE Take care for contamination of the remote condenser In order to avoid blocking of the system It is impossible for the manufacturer to control the contamination of the foreign condenser of the installer The unit has a strict contamination level 11 PREPARING CHECKING AND CONNECTING THE WATER CIRCUIT The units are equipped with a water inlet and water outlet for connection to a chi...

Page 13: ...ransmitting vibration and noise 6 For units in double circuit configuration with common leaving water control ELWT be sure to foresee an insertion hole for the additional water temperature sensor Sensor and sensor holder are optional parts The insertion hole shall be 1 4 GAS female thread and should be located in the mixed waterflow of the chillers Make sure that the sensortip is in the waterflow ...

Page 14: ...e relef valve on the condenser and pipe to each pressure relief valve on the evaporator Cross section and length of the discharge line must comply with local codes 15 FIELD WIRING All field wiring and components must be installed by a licensed electrician and must compy with relevant European and national regulations The field wiring must be carried out in accordance with the wiring diagram suppli...

Page 15: ... sent to specific refuse collection centres Oil must be collected and sent to specific refuse collection centres 16 BEFORE STARTING The unit should not be started not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off va...

Page 16: ...mp VFD D L Demand Limit DI Digital Inputs DO Digital Outputs DPS Double Set Point EF Esternal Fault EFS Evaporator Flow Switch EFS 1 Evaporator Flow Switch 1 EFS 2 Evaporator Flow Switch 2 GA General Alarm KPC Condensator Water Pump KPE 1 Evaporator Water Pump 1 KPE 2 Evaporator Water Pump 2 PS Power Supply Q10 Main Switch S O Setpoint Override TW1 Tower 1 Fan Step TW2 Tower 2 Fan Step TW3 Tower 3...

Page 17: ...D EIMWC01006 11EU 17 20 17 FACTORY AND FIELD CHARGED UNITS INSTRUCTIONS Errore Non si possono creare oggetti dalla modifica di codici di campo 18 FIELD CHARGED UNITS INSTRUCTIONS ...

Page 18: ...frigerant charge Factory Field h Greenhouse gas emission of the total refrigerant charge expressed as tonnes of CO2 equivalent m Refrigerant type n GWP Global Warming Potential p Unit serial number 2 The filled out label must be adhered inside the electrical panel Periodical inspections for refrigerant leaks may be required depending on European or local legislation Please contact your local deale...

Page 19: ... of its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publication All content is copyrighted by...

Page 20: ...D EIMWC01006 11EU 20 20 ...

Reviews: