5
|
Operation
User reference guide
41
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620246-1A – 2021.02
5.8.4 Using weather-dependent curves
Configure weather-dependent curves as following:
To define the setpoint mode
To use the weather-dependent curve, you need to define the correct setpoint
mode:
Go to setpoint mode …
Set the setpoint mode to …
Main zone – Heating
[2.4]
Main zone
>
Setpoint mode
WD heating, fixed cooling
OR
Weather dependent
Main zone – Cooling
[2.4]
Main zone
>
Setpoint mode
Weather dependent
Additional zone – Heating
[3.4]
Additional zone
>
Setpoint
mode
WD heating, fixed cooling
OR
Weather dependent
Additional zone – Cooling
[3.4]
Additional zone
>
Setpoint
mode
Weather dependent
To change the type of weather-dependent curve
To change the type for all zones (main + additional), go to [2.E]
Main zone
>
WD
curve type
.
Viewing which type is selected is also possible via [3.C]
Additional zone
>
WD
curve type
To change the weather-dependent curve
Zone
Go to …
Main zone – Heating
[2.5]
Main zone
>
Heating WD
curve
Main zone – Cooling
[2.6]
Main zone
>
Cooling WD
curve
Additional zone – Heating
[3.5]
Additional zone
>
Heating
WD curve
Additional zone – Cooling
[3.6]
Additional zone
>
Cooling
WD curve
INFORMATION
Maximum and minimum setpoints
You cannot configure the curve with temperatures that are higher or lower than the
set maximum and minimum setpoints for that zone. When the maximum or
minimum setpoint is reached, the curve flattens out.
To fine-tune the weather-dependent curve: slope-offset curve
The following table describes how to fine-tune the weather-dependent curve of a
zone: