Pre-Test Run Checks
ESIE11-02
4–22
Part 4 – Commissioning and Test Run
3
1
4
5
1.11
Electrical Checks
Checklist
The table below contains the electrical checklist.
Step
Check whether...
1
The main fuses, earth leak detector and main isolator are installed.
2
The main power supply voltage deviates less than 10% from the nominal value.
3
The flow switch and pump contact are properly wired.
4
The optional wiring for pump control is installed.
5
The optional wiring for remote start/stop is installed.
Make sure that the controller is correctly programmed.
6
The optional wiring for remote cool/heat is installed.
Make sure that the controller is correctly programmed.