background image

7 Configuration

Installation manual

24

ETVH/23E

Daikin Altherma 3 H HT F

4P644728-1D – 2022.08

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–10/2=

35°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

7.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 23].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 23].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 23].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent curves. Also see 

"7.3 Weather-dependent curve"

 [

4

 25].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 23].

#

Code

Description

[3.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

7.2.7

Configuration wizard: Tank

INFORMATION

To make tank defrost possible, we recommend a minimum
tank temperature of 35°C.

Heat up mode

The  domestic  hot  water  can  be  prepared  in  3  different  ways.  They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.

Summary of Contents for ETVX16E6V7

Page 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Page 2: ...e 21 7 2 3 Configuration wizard System 21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 23 7 2 6 Configuration wizard Additional zone 24 7 2 7 Configuration wizard T...

Page 3: ...the instructions from this manual See 5 Piping installation 47 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Page 4: ...omestic hot water circuit j Sealing tape for low voltage wiring intake 3 1 2 To handle the indoor unit Use the handles at the back and at the bottom to carry the unit b a a b a Handles at the back of...

Page 5: ...he cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the...

Page 6: ...pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into pos...

Page 7: ...piping and accessories 5 1 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the o...

Page 8: ...lve between the pressure relief valve field supply and the DHW tank NOTICE A pressure relief valve field supply with an opening pressure of maximum 10 bar 1 MPa must be installed on the domestic cold...

Page 9: ...system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks m...

Page 10: ...r tank 1 Open every hot water tap in turn to purge air from the system pipe work 2 Open the cold water supply valve 3 Close all water taps after all air is purged 4 Check for water leaks 5 2 6 To insu...

Page 11: ...ent Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional...

Page 12: ...see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the main power supply In case of normal kWh rate power supply Interconnection cable mai...

Page 13: ...ackup heater capacity Power supply Maximum running current Zmax 6V 2 kW 1N 230 V a 9 A 4 kW 1N 230 V a 17 A b c 0 22 6 kW 1N 230 V a 26 A b c 0 22 2 kW 3 230 V d 5 A 4 kW 3 230 V d 10 A 6 kW 3 230 V d...

Page 14: ...all a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied by PCB 2 D Shut off va...

Page 15: ...door unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below A 1 M M2P B A...

Page 16: ...illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y2 7 B A B 7 9 X2M A4P...

Page 17: ...puts cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the cable with cable ti...

Page 18: ...acts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Forced on The use of a Smart Grid pulse meter i...

Page 19: ...2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factory...

Page 20: ...izard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to In...

Page 21: ...rview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applie...

Page 22: ...periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION The auto emergency setting can be set in the menu stru...

Page 23: ...change one check if the other is still as expected INFORMATION During normal operation the capacity of the second step of the backup heater at nominal voltage is equal to 6 03 6 04 INFORMATION If 4 0...

Page 24: ...endent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT se...

Page 25: ...ing reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage co...

Page 26: ...temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperat...

Page 27: ...the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curv...

Page 28: ...644728 1D 2022 08 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact nu...

Page 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 30: ...ring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply pa...

Page 31: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe t...

Page 32: ...fter the first 12 hours of power on manually disable room frost protection by setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking o...

Page 33: ...d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve l Loose nut 1 m Shut off valve recommended n Non ret...

Page 34: ...eat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P ON OFF thermostat PC power circuit A3P Heat pump convector A4P Digit...

Page 35: ...Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat conta...

Page 36: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1D 2022 08 Copyright 2021 Daikin 4P644728 1 D 00000004 Verantwortung f r Energie und Umwelt...

Reviews: