2 Specific installer safety instructions

Installation manual

3

ETVH/23E
Daikin Altherma 3 H HT F
4P644728-1D – 2022.08

Technical engineering data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

Online tools

In addition to the documentation set, some online tools are available
for installers:

Daikin Technical Data Hub

▪ Central hub for technical specifications of the unit, useful tools,

digital resources, and more.

▪ Publicly accessible via 

https://daikintechnicaldatahub.eu

.

Heating Solutions Navigator

▪ Digital  toolbox  that  offers  a  variety  of  tools  to  facilitate  the

installation and configuration of heating systems.

▪ To  access  Heating  Solutions  Navigator,  registration  to  the

Stand  By  Me  platform  is  required.  For  more  information,  see

https://professional.standbyme.daikin.eu

.

Daikin e-Care

▪ Mobile app for installers and service technicians that allows you

to register, configure and troubleshoot heating systems.

▪ The  mobile  app  can  be  downloaded  for  iOS  and  Android

devices  using  the  QR  codes  below.  Registration  to  the  Stand
By Me platform is required to access the app.

App Store

Google Play

2

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

Installation site (see 

"4.1 Preparing the installation site"

 [

4

 4])

WARNING

Follow  the  service  space  dimensions  in  this  manual  for
correct  installation  of  the  unit.  See 

"4.1.1  Installation  site

requirements of the indoor unit"

 [

4

 4].

Opening and closing the unit (see 

"4.2 Opening and closing the

unit"

 [

4

 5])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

Mounting the indoor unit (see 

"4.3 Mounting the indoor

unit"

 [

4

 6])

WARNING

Fixing  method  of  the  indoor  unit  MUST  be  in  accordance
with  the  instructions  from  this  manual.  See 

"4.3  Mounting

the indoor unit"

 [

4

 6].

Piping installation (see 

"5 Piping installation"

 [

4

 7])

WARNING

The  field  piping  method  MUST  be  in  accordance  with  the
instructions 

from 

this 

manual. 

See 

"5 

Piping

installation"

 [

4

 7].

In case of freeze protection by glycol:

WARNING

Ethylene glycol is toxic.

WARNING

Due  to  the  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

Electrical installation (see 

"6 Electrical installation"

 [

4

 10])

DANGER: RISK OF ELECTROCUTION

WARNING

Electrical  wiring  connection  method  MUST  be  in
accordance with the instructions from:

▪ This manual. See 

"6 Electrical installation"

 [

4

 10].

▪ The  wiring  diagram,  which  is  delivered  with  the  unit,

located  on  the  inside  of  the  indoor  unit  switch  box
cover.  For  a  translation  of  its  legend,  see 

"10.2  Wiring

diagram: Indoor unit"

 [

4

 33].

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

CAUTION

Do NOT push or place redundant cable length into the unit.

WARNING

The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.

CAUTION

To  guarantee  the  unit  is  completely  earthed,  ALWAYS
connect  the  backup  heater  power  supply  and  the  earth
cable.

Summary of Contents for ETVX16E6V7

Page 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Page 2: ...e 21 7 2 3 Configuration wizard System 21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 23 7 2 6 Configuration wizard Additional zone 24 7 2 7 Configuration wizard T...

Page 3: ...the instructions from this manual See 5 Piping installation 47 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Page 4: ...omestic hot water circuit j Sealing tape for low voltage wiring intake 3 1 2 To handle the indoor unit Use the handles at the back and at the bottom to carry the unit b a a b a Handles at the back of...

Page 5: ...he cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the...

Page 6: ...pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into pos...

Page 7: ...piping and accessories 5 1 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the o...

Page 8: ...lve between the pressure relief valve field supply and the DHW tank NOTICE A pressure relief valve field supply with an opening pressure of maximum 10 bar 1 MPa must be installed on the domestic cold...

Page 9: ...system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks m...

Page 10: ...r tank 1 Open every hot water tap in turn to purge air from the system pipe work 2 Open the cold water supply valve 3 Close all water taps after all air is purged 4 Check for water leaks 5 2 6 To insu...

Page 11: ...ent Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional...

Page 12: ...see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the main power supply In case of normal kWh rate power supply Interconnection cable mai...

Page 13: ...ackup heater capacity Power supply Maximum running current Zmax 6V 2 kW 1N 230 V a 9 A 4 kW 1N 230 V a 17 A b c 0 22 6 kW 1N 230 V a 26 A b c 0 22 2 kW 3 230 V d 5 A 4 kW 3 230 V d 10 A 6 kW 3 230 V d...

Page 14: ...all a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied by PCB 2 D Shut off va...

Page 15: ...door unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below A 1 M M2P B A...

Page 16: ...illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y2 7 B A B 7 9 X2M A4P...

Page 17: ...puts cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the cable with cable ti...

Page 18: ...acts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Forced on The use of a Smart Grid pulse meter i...

Page 19: ...2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factory...

Page 20: ...izard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to In...

Page 21: ...rview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applie...

Page 22: ...periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION The auto emergency setting can be set in the menu stru...

Page 23: ...change one check if the other is still as expected INFORMATION During normal operation the capacity of the second step of the backup heater at nominal voltage is equal to 6 03 6 04 INFORMATION If 4 0...

Page 24: ...endent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT se...

Page 25: ...ing reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage co...

Page 26: ...temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperat...

Page 27: ...the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curv...

Page 28: ...644728 1D 2022 08 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact nu...

Page 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 30: ...ring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply pa...

Page 31: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe t...

Page 32: ...fter the first 12 hours of power on manually disable room frost protection by setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking o...

Page 33: ...d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve l Loose nut 1 m Shut off valve recommended n Non ret...

Page 34: ...eat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P ON OFF thermostat PC power circuit A3P Heat pump convector A4P Digit...

Page 35: ...Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat conta...

Page 36: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1D 2022 08 Copyright 2021 Daikin 4P644728 1 D 00000004 Verantwortung f r Energie und Umwelt...

Reviews: