Daikin ETVX12E9W Installation Manual Download Page 10

6 Electrical installation

Installation manual

10

ETVH/23E

Daikin Altherma 3 H MT F

4P634880-1C – 2022.08

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

Glycol and the maximum allowed water volume

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water volume of the system. For more information, see the installer
reference guide (topic "To check the water volume and flow rate").

Glycol setting

NOTICE

If  glycol  is  present  in  the  system,  setting  [E-0D]  must  be
set to 1. If the glycol setting is NOT set correctly, the liquid
inside the piping can freeze.

Freeze protection by freeze protection valves

About freeze protection valves

When no glycol is added to the water, you can use freeze protection
valves to drain the water from the system before it can freeze.

▪ Install freeze protection valves (field supply) at all lowest points of

the field piping.

▪ Normally closed valves (located indoors near the piping entry/exit

points)  can  prevent  that  all  water  from  indoor  piping  is  drained
when the freeze protection valves open.

NOTICE

When  freeze  protection  valves  are  installed,  set  the
minimum cooling setpoint (default=7°C) at least 2°C higher
than  the  maximum  opening  temperature  of  the  freeze
protection  valve.  If  lower,  freeze  protection  valves  can
open during cooling operation.

For more information, see the installer reference guide.

5.2.5

To fill the domestic hot water tank

1

Open  every  hot  water  tap  in  turn  to  purge  air  from  the  system
pipe work.

2

Open the cold water supply valve.

3

Close all water taps after all air is purged.

4

Check for water leaks.

5.2.6

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

Outdoor water piping insulation

See  the  installation  manual  of  the  outdoor  unit,  or  the  installer
reference guide.

6

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

CAUTION

Do NOT push or place redundant cable length into the unit.

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 50 mm.

6.1

About electrical compliance

Only for the backup heater of the indoor unit

See 

"6.3.2 To connect the backup heater power supply"

 [

4

 13].

6.2

Guidelines when connecting the
electrical wiring

Tightening torques

Indoor unit:

Item

Tightening torque (N•m)

X1M

2.45 ±10%

X2M

0.88 ±10%

X5M

0.88 ±10%

X6M

2.45 ±10%

X10M

0.88 ±10%

M4 (earth)

1.47 ±10%

6.3

Connections to the indoor unit

Item

Description

Power supply (main)

See 

"6.3.1 To connect the main power

supply"

 [

4

 12].

Power supply (backup
heater)

See 

"6.3.2 To connect the backup heater

power supply"

 [

4

 13].

Shut-off valve

See 

"6.3.3 To connect the shut-off

valve"

 [

4

 14].

Electricity meters

See 

"6.3.4 To connect the electricity

meters"

 [

4

 14].

Domestic hot water
pump

See 

"6.3.5 To connect the domestic hot

water pump"

 [

4

 15].

Alarm output

See 

"6.3.6 To connect the alarm

output"

 [

4

 15].

Space cooling/heating
operation control

See 

"6.3.7 To connect the space cooling/

heating ON/OFF output"

 [

4

 16].

Changeover to
external heat source
control

See 

"6.3.8 To connect the changeover to

external heat source"

 [

4

 16].

Power consumption
digital inputs

See 

"6.3.9 To connect the power

consumption digital inputs"

 [

4

 17].

Safety thermostat

See 

"6.3.10 To connect the safety

thermostat (normally closed
contact)"

 [

4

 17].

Summary of Contents for ETVX12E9W

Page 1: ...ltherma 3 H MT F English Installation manual Daikin Altherma 3 H MT F ETVH12S18E 6V ETVH12S23E 6V ETVH12S18E 9W ETVH12S23E 9W ETVX12S18E 6V ETVX12S23E 6V ETVX12S18E 9W ETVX12S23E 9W A B C Z 1 2 3 9 https daikintechnicaldatahub eu ...

Page 2: ...Configuration wizard 21 7 2 1 Configuration wizard Language 21 7 2 2 Configuration wizard Time and date 21 7 2 3 Configuration wizard System 21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 23 7 2 6 Configuration wizard Additional zone 24 7 2 7 Configuration wizard Tank 24 7 3 Weather dependent curve 25 7 3 1 What is a weather dependent curve 25 7 3 2 2 points cu...

Page 3: ...g method of the indoor unit MUST be in accordance with the instructions from this manual See 4 3 Mounting the indoor unit 46 Piping installation see 5 Piping installation 47 WARNING The field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 47 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of g...

Page 4: ...tion manual f Operation manual g WLAN cartridge h Sealing rings for shut off valves space heating water circuit i Sealing rings for field supplied shut off valves domestic hot water circuit j Sealing tape for low voltage wiring intake 3 1 2 To handle the indoor unit Use the handles at the back and at the bottom to carry the unit b a a b a Handles at the back of the unit b Handles at the bottom of ...

Page 5: ...at the top and slide the top panel upwards NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the following cases 4 2 2 To lower the switch box on the indoor unit 45 4 3 2 To connect the drain...

Page 6: ...e pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximum allowed deviation is 1 1 NOTICE Do NOT tilt the unit forwards 0 1 1 4 3 2 To connect the drain hose t...

Page 7: ...imum temperature for piping and accessories 5 1 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is higher than the minimum water volume the internal water volume of the indoor unit NOT included If Then the minimum water volume is Cooling operation 20 l Heating operation 0 l NOTICE When circulation in each space heating cooling lo...

Page 8: ...alve between the pressure relief valve field supply and the DHW tank NOTICE A pressure relief valve field supply with an opening pressure of maximum 10 bar 1 MPa must be installed on the domestic cold water inlet connection in accordance with the applicable legislation NOTICE A drain device and pressure relief device must be installed on the cold water inlet connection of the domestic hot water cy...

Page 9: ... system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system Therefore it is important that the water treatment is correctly executed by a qualified water specialist a glyc...

Page 10: ...er tank 1 Open every hot water tap in turn to purge air from the system pipe work 2 Open the cold water supply valve 3 Close all water taps after all air is purged 4 Check for water leaks 5 2 6 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity Outdoor water pipin...

Page 11: ...ment Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 2 External sensor Room 1 7 Room sensor offset Item Description Human Comfort Interface See Installation and operation manual of the Human Comfort Interface Addendum b...

Page 12: ... see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the main power supply In case of normal kWh rate power supply Interconnection cable main power supply Wires 3 GND 1 5 mm A 1 2 3 a B A B 1 2 3 X2M X1A X11YA X11YB X11Y X1M a a Interconnection cable main power supply In case of preferential kWh rate power supply Interconnection cable ma...

Page 13: ...ckup heater capacity Power supply Maximum running current Zmax 6V 2 kW 1N 230 V a 9 A 4 kW 1N 230 V a 17 A b c 0 22 Ω 6 kW 1N 230 V a 26 A b c 0 22 Ω 2 kW 3 230 V d 5 A 4 kW 3 230 V d 10 A 6 kW 3 230 V d 15 A Backup heater type Backup heater capacity Power supply Maximum running current Zmax 9W 3 kW 3N 400 V 4 A 6 kW 3N 400 V 9 A 9 kW 3N 400 V 13 A a 6V3 b Electrical equipment complying with EN IE...

Page 14: ...tall a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied by PCB 2 D Shut off valve 1 Open the following see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the valve control cable to the appropriate terminals as shown...

Page 15: ...ndoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below A 1 M M2P B A B 1 2 X2M 3 Fix the cable with cable ties to the cable tie mountings 6 3 6 To connect the alarm output Wires 2 1 0 75 mm Maximum load 0 3 A 250 V AC 9 D Alarm output 1 Open the following see 4 2 1 T...

Page 16: ...e illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y2 7 B A B 7 9 X2M A4P Y2 YC X1M a b a Installation of EKRP1HBAA is required b Prewiring between X2M 7 9 and Q1L thermal protector backup heater Do NOT change 3 Fix the cable with cable ties to the cable tie mountings 6 3...

Page 17: ...nputs cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the cable with cable ties to the cable tie mountings 6 3 10 To connect the safety thermostat normally closed contact Wires 2 0 75 mm Maximum length 50 m Safety thermostat contact 16 V DC detection voltage supplied by PCB T...

Page 18: ...tacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Forced on The use of a Smart Grid pulse meter is not mandatory If Smart Grid pulse meter is Then 9 8 8 Limit setting kW is Used 9 A 2 Electricity meter 2 None Not applicable Not used 9 A 2 Electricity meter 2 None Applicable In case of low voltag...

Page 19: ...P 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factory mounted If you also connect a safety thermostat Q4L replace the jumper with the safety thermostat wires f Smart Grid pulse meter 1 Install the components of the Smart Grid relay kit as follows a b c...

Page 20: ...wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to Installer settings Configuration wizard To access Installer settings see 7 1 1 To access the most used commands 420 Afterwards If necessary you can make changes to the configuration in the menu structu...

Page 21: ...erview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applied 7 2 Configuration wizard After first power ON of the system the user interface starts a configuration wizard Use this wizard to set the most important initial settings for the unit to run properly ...

Page 22: ...r periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION The auto emergency setting can be set in the menu structure of the user interface only INFORMATION If a heat pump failure occurs and Emergency is set to Manual the room frost protection function the underfloor heating screed dryout function and the wate...

Page 23: ...u change one check if the other is still as expected INFORMATION During normal operation the capacity of the second step of the backup heater at nominal voltage is equal to 6 03 6 04 INFORMATION If 4 0A 3 and emergency mode is active the power usage of the backup heater is maximal and equal to 2 6 03 6 04 INFORMATION Only for systems with integrated domestic hot water tank If the storage temperatu...

Page 24: ...pendent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT setpoint mode 2 4 is as follows In Fixed LWT setpoint mode the scheduled actions consist of desired leaving water temperatures either preset or custom In Weather dependent LWT setpoint mode the schedul...

Page 25: ...ring reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentially Code Descrip...

Page 26: ... temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature for all ambient temperat...

Page 27: ...n the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset OK Cold You feel Fine tune with slope and offset At regular outd...

Page 28: ...P634880 1C 2022 08 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact number here Code Description 8 3 N A Number that users can call in case of problems ...

Page 29: ...trical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention Benefit kWh power supply Power consumption control Energy metering Sensors Bivalent Alarm output Auto restart Power saving function Disable protections Overview field settings Forced defrost Export ...

Page 30: ...iring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor unit and the room thermostat if applicable The system is properly earthed and the earth terminals are t...

Page 31: ...cked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2 4 To perform an actuator test run Purpose Perform an actuator test run to confirm the operation of the different actuators For example when you select Pump a test run of the pump will star...

Page 32: ... installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system and what to do in case of problems Show the user what to do for the ...

Page 33: ...g on model PCB Note 1 Connection point of the power supply for the BUH should be foreseen outside the unit Note 1 Connection point of the power supply for the backup heater should be foreseen outside the unit Backup heater power supply Backup heater power supply 6T1 3 230 V 6 kW 6T1 3 230 V 6 kW 6V3 1N 230 V 6 kW 6V3 1N 230 V 6 kW 6WN 9WN 3N 400 V 6 9 kW 6WN 9WN 3N 400 V 6 9 kW User installed opti...

Page 34: ...r supply for indoor unit 2 Backup heater power supply 2 Backup heater power supply English Translation Only for Only for 3 User interface 3 User interface Only for remote user interface Only for the dedicated Human Comfort Interface BRC1HHDA used as room thermostat SD card Card slot for WLAN cartridge SWB Switch box WLAN cartridge WLAN cartridge 5 Ext thermistor 5 External thermistor SWB Switch bo...

Page 35: ...ain LWT zone Main leaving water temperature zone Only for external sensor floor ambient Only for external sensor floor or ambient Only for heat pump convector Only for heat pump convector Only for wired On OFF thermostat Only for wired ON OFF thermostat Only for wireless On OFF thermostat Only for wireless ON OFF thermostat ...

Page 36: ...h Only for preferential kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X6M L1 L2 L3 earth or L N earth or L1 L2 L3 N earth 5 or 4 or 3 core Backup heater power supply 6 9 kW 400 V or 230 V earth Electricity meter pulse input 1 Smart Grid contact K2A ...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P634880 1C 2022 08 Copyright 2021 Daikin 4P634880 1 C 00000001 Verantwortung für Energie und Umwelt ...

Reviews: