8
|
Troubleshooting
User reference guide
59
ETVH/X16S(U)18+9W + ETBH/9W
Daikin Altherma 3 H HT F+W
4P644740-1 – 2021.02
8.5 Symptom: Heat pump failure
When the heat pump fails to operate, the backup heater and/or booster heater
can serve as an emergency heater. It then takes over the heat load either
automatically or by manual interaction.
▪
When
Emergency
is set to
Automatic
and a heat pump failure occurs:
-
For ETVH/X: The backup heater automatically takes over the domestic hot
water production and space heating.
-
For ETBH/X: The backup heater automatically takes over the heat load, and the
booster heater in the optional tank takes over the domestic hot water
production.
▪
When
Emergency
is set to
Manual
and a heat pump failure occurs, the
domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main
menu screen and confirm whether the backup heater and/or booster heater can
take over the heat load or not.
▪
Alternatively, when
Emergency
is set to:
-
auto SH reduced/DHW on
, space heating is reduced but domestic hot
water is still available.
-
auto SH reduced/DHW off
, space heating is reduced and domestic hot
water is NOT available.
-
auto SH normal/DHW off
, space heating operates as normally but
domestic hot water is NOT available.
Similarly as in
Manual
mode, the unit can take the full load with the backup
heater and/or booster heater if the user activates this via the
Malfunctioning
main menu screen.
When the heat pump fails, or
will appear on the user interface.
Possible cause
Corrective action
Heat pump is damaged.
See
"8.1 To display the help text in case
57].
INFORMATION
When the backup heater or booster heater takes over the heat load, electricity
consumption will be considerably higher.
8.6 Symptom: The system is making gurgling noises after commissioning
Possible cause
Corrective action
There is air in the system.
Purge air from the system.
(a)
Incorrect hydraulic balance.
To be performed by the installer:
1
Perform hydraulic balancing to
assure that the flow is correctly
distributed between the emitters.
2
If hydraulic balancing is not
sufficient,
change
the
pump
limitation settings ([9-0D] and [9-0E]
if applicable).