6
|
Application guidelines
Installer reference guide
54
EPRA14~W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02
Configuration
Via the user interface:
▪
Select, whether all other heat sources are stopped, when solar energy is
provided.
▪
Select tank temperature, above which all other heat sources are stopped, when
solar energy is provided.
225] for more information on configuration.
6.3.5 Setting up an electric backup heater
INFORMATION
For systems without indirect auxiliary boiler connected to the storage tank, it is
mandatory to install an electric backup heater to ensure safe operation for all
conditions.
Configuration
Via the user interface (configuration wizard):
▪
Set the backup heater voltage
▪
Set the capacity steps, if applicable
6.4 Setting up the storage tank
6.4.1 System layout – Integrated storage tank
b
a
A
A
Domestic hot water
a
Cold water IN
b
Hot water OUT
6.4.2 Selecting the volume and desired temperature for the storage tank
People experience water as hot when its temperature is 40°C. Therefore, the DHW
consumption is always expressed as equivalent hot water volume at 40°C.
However, you can set the storage tank temperature at a higher temperature
(example: 53°C), which is then mixed with cold water (example: 15°C). The
resulting domestic hot water temperature depends on this setpoint as well as the
actual storage tank temperature.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent
hot water volume at 40°C) using typical water volumes: