4 Operation

Operation manual

16

ETVH/9W(G) + ETBH/9W

Daikin Altherma 3 H HT F+W

4P586455-1C – 2020.10

4.9

Weather-dependent curve

4.9.1

What is a weather-dependent curve?

Weather-dependent operation

The unit operates 'weather dependent' if the desired leaving water or
tank  temperature  is  determined  automatically  by  the  outdoor
temperature.  It  therefore  is  connected  to  a  temperature  sensor  on
the  North  wall  of  the  building.  If  the  outdoor  temperature  drops  or
rises, the unit compensates instantly. Thus, the unit does not have to
wait  for  feedback  by  the  thermostat  to  increase  or  decrease  the
temperature  of  the  leaving  water  or  tank.  Because  it  reacts  more
quickly,  it  prevents  high  rises  and  drops  of  the  indoor  temperature
and water temperature at tap points.

Advantage

Weather-dependent operation reduces energy consumption.

Weather-dependent curve

To  be  able  to  compensate  for  differences  in  temperature,  the  unit
relies on its weather-dependent curve. This curve defines how much
the  temperature  of  the  tank  or  leaving  water  must  be  at  different
outdoor  temperatures.  Because  the  slope  of  the  curve  depends  on
local circumstances such as climate and the insulation of the house,
the curve can be adjusted by an installer or user.

Types of weather-dependent curve

There are 2 types of weather-dependent curves:

▪ 2-points curve

▪ Slope-offset curve

Which type of curve you use to make adjustments, depends on your
personal  preference.  See 

"4.9.4  Using  weather-dependent

curves" 

[

4

 17].

Availability

The weather-dependent curve is available for:

▪ Main zone - Heating

▪ Main zone - Cooling

▪ Additional zone - Heating

▪ Additional zone - Cooling

▪ Tank (only available to installers)

INFORMATION

To  operate  weather  dependent,  correctly  configure  the
setpoint  of  the  main  zone,  additional  zone  or  tank.  See

"4.9.4 Using weather-dependent curves" 

[

4

 17].

4.9.2

2-points curve

Define the weather-dependent curve with these two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Example

Y1

Y2

X1

X2

a

Item

Description

a

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Domestic hot water tank

Possible actions on this screen

Go through the temperatures.

Change the temperature.

Go to the next temperature.

Confirm changes and proceed.

4.9.3

Slope-offset curve

Slope and offset

Define the weather-dependent curve by its slope and offset:

▪ Change  the 

slope

  to  differently  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures.  For  example,  if  leaving  water  temperature  is  in
general  fine  but  at  low  ambient  temperatures  too  cold,  raise  the
slope  so  that  leaving  water  temperature  is  heated  increasingly
more at decreasingly lower ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to  equally  increase  the  leaving  water  temperature  for  all  ambient
temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

e

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Summary of Contents for ETBX16DF6V

Page 1: ...H HT F W English Operation manual Daikin Altherma 3 H HT F W ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETVX16S18DA9W G ETVX16S23DA9W G ETBH16DF6V...

Page 2: ...e 16 4 9 2 2 points curve 16 4 9 3 Slope offset curve 16 4 9 4 Using weather dependent curves 17 5 Energy saving tips 18 6 Maintenance and service 18 6 1 Overview Maintenance and service 18 7 Troubles...

Page 3: ...cooling On On C 1 2 Set operation to On or Off To turn space heating cooling operation ON or OFF NOTICE Room frost protection Even if you turn OFF space heating cooling operation C 2 Operation Space h...

Page 4: ...is changed the new preferred temperature at X1 is unequally higher than the preferred temperature at X2 X1 X2 c d Y1 Y2 Y3 Y4 a b Offset When offset is changed the new preferred temperature at X1 is e...

Page 5: ...r Off To change the tank temperature setpoint In Reheat only mode you can use the tank temperature setpoint screen to read out and adjust the domestic hot water temperature 1 Go to 5 Tank Tank 5 2 Adj...

Page 6: ...mation Addendum book for optional equipment Additional info about how to install optional equipment Format Paper in the box of the indoor unit Digital files on http www daikineurope com support and ma...

Page 7: ...unit is not in operation Continuous blue Operation The unit is in operation Blinking red Malfunction A malfunction occurred See 7 1 To display the help text in case of a malfunction 419 for more infor...

Page 8: ...Actuators Operation modes About Connection status Running hours B User profile C Operation Room Space heating cooling Tank 1 4 Antifrost Activation Room setpoint 1 5 Setpoint range Heating minimum He...

Page 9: ...y Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy...

Page 10: ...erature 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leavin...

Page 11: ...e icon in the home screen will be greyed out Room temperature control 1 6 bar 55 21 35 45 a 1 6 bar 55 21 35 45 b a Room temperature control ON b Room temperature control OFF Space heating cooling ope...

Page 12: ...cool down a space You have to tell the system which operation mode to use To tell the system which space operation to use you can You can Location Check which space operation mode is currently used H...

Page 13: ...RMATION When the DHW tank mode is reheat the risk for capacity shortage and comfort problem is significant In case of frequent reheat operation space heating cooling function is regularly interrupted...

Page 14: ...een Example This example shows how to set a room temperature schedule in heating mode for the main zone INFORMATION The procedures to program other schedules are similar To program the schedule overvi...

Page 15: ...Wed Fri Thu Tue Sun User defined 1 C 4 Select Paste Delete Edit Copy Paste Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C 5 Repeat this action for all other weekdays Mon Sat Wed Fri Thu Tue Sun U...

Page 16: ...zone Heating Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 4 9 4 Usi...

Page 17: ...e Heating Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather...

Page 18: ...of the day when instant hot water is necessary Example In the morning and evening 6 Maintenance and service 6 1 Overview Maintenance and service The installer has to perform a yearly maintenance You...

Page 19: ...ing DHW powerful operation 414 If the problems recurs daily do one of the following Increase the DHW tank temperature preset value See the user reference guide Adjust the DHW tank temperature schedule...

Page 20: ...ing heat emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P586455 1C 2020 10 Copyright 2019 Daikin 4P586455 1 C 00000005 Verantwortung f r Energie und Umwelt...

Reviews: