6 Electrical installation

Installation manual

11

ETBH/X16E
Daikin Altherma 3 H HT W
4P644727-1B – 2022.03

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors, classified as
Category III according to EN1717.

Required concentration of glycol

The  required  concentration  of  glycol  depends  on  the  lowest
expected  outdoor  temperature,  and  on  whether  you  want  to  protect
the  system  from  bursting  or  from  freezing.  To  prevent  the  system
from freezing, more glycol is required.

Add glycol according to the table below.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

–30°C

35%

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

Glycol and the maximum allowed water volume

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water volume of the system. For more information, see the installer
reference guide (topic "To check the water volume and flow rate").

Glycol setting

NOTICE

If  glycol  is  present  in  the  system,  setting  [E-0D]  must  be
set to 1. If the glycol setting is NOT set correctly, the liquid
inside the piping can freeze.

Freeze protection by freeze protection valves

About freeze protection valves

When no glycol is added to the water, you can use freeze protection
valves to drain the water from the system before it can freeze.

▪ Install freeze protection valves (field supply) at all lowest points of

the field piping.

▪ Normally closed valves (located indoors near the piping entry/exit

points)  can  prevent  that  all  water  from  indoor  piping  is  drained
when the freeze protection valves open.

NOTICE

When  freeze  protection  valves  are  installed,  set  the
minimum cooling setpoint (default=7°C) at least 2°C higher
than  the  maximum  opening  temperature  of  the  freeze
protection  valve.  If  lower,  freeze  protection  valves  can
open during cooling operation.

For more information, see the installer reference guide.

5.2.4

To fill the domestic hot water tank

See the installation manual of the domestic hot water tank.

5.2.5

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

Outdoor water piping insulation

See  the  installation  manual  of  the  outdoor  unit,  or  the  installer
reference guide.

6

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

INFORMATION

When  installing  field  supply  or  option  cables,  foresee
sufficient  cable  length.  This  will  make  it  possible  to  open
the  switch  box  and  gain  access  to  other  components
during service.

CAUTION

Do NOT push or place redundant cable length in the unit.

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 50 mm.

6.1

About electrical compliance

Only for the backup heater of the indoor unit

See 

"6.3.2 To connect the backup heater power supply"

 [

4

 14].

6.2

Guidelines when connecting the
electrical wiring

Tightening torques

Indoor unit:

Item

Tightening torque (N•m)

X1M

2.45 ±10%

X2M

0.88 ±10%

Summary of Contents for ETBH16E 6V Series

Page 1: ...Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16E 6V ETBH16E 9W ETBX16E 6V ETBX16E 9W A B C Z 1 2 3 9 https daikintechnicaldatahub eu...

Page 2: ...e tyto v robky jsou pou v ny v souladu s na imi pokyny u skladu sa sljede om direktivom ma ili odredbom a uz uvjet da se proizvodi koriste sukladno na im uputama megfelelnek az al bbi ir nyelv ek nek...

Page 3: ...regulation s provided that the products are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility...

Page 4: ...er 25 7 2 5 Configuration wizard Main zone 25 7 2 6 Configuration wizard Additional zone 26 7 2 7 Configuration wizard Tank 27 7 3 Weather dependent curve 27 7 3 1 What is a weather dependent curve 27...

Page 5: ...WARNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING D...

Page 6: ...anual e WLAN cartridge f Sealing ring for shut off valve g Shut off valve h Overpressure bypass valve i Wall bracket 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site req...

Page 7: ...the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user interface...

Page 8: ...in hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Connect...

Page 9: ...er interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guarante...

Page 10: ...ct the water circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system be...

Page 11: ...e set to 1 If the glycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to th...

Page 12: ...y 421 Room thermostat wired or wireless See below table Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Ext thermostat type For the additional zone 3 A Ext thermostat ty...

Page 13: ...nstaller reference guide Use the cable delivered with the WLAN module D Wireless gateway Bizone kit See Installation manual of the bizone kit Addendum book for optional equipment Use the cable deliver...

Page 14: ...y of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rat...

Page 15: ...terface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if nec...

Page 16: ...open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings 6 3 4 To connect the electricity meters Wires 2 per me...

Page 17: ...tion below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to the alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required B C A A 7 Y1 C B X2M X2M A4P A4P a 7 9 Y1 YC X1M a Insta...

Page 18: ...open the indoor unit 47 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below B C...

Page 19: ...5M X5M 3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessar...

Page 20: ...Connect the wiring as follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high...

Page 21: ...Grid pulse meter C B X5M X5M 3 4 13 14 3 Connect the high voltage wiring as follows B C A A L N L N X10M 1 X10M 2 X10M 3 X10M 4 2 1 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid conta...

Page 22: ...staller settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column...

Page 23: ...INFORMATION By default daylight savings time is enabled and clock format is set to 24 hours If you want to change these settings you can do this in the menu structure User settings Time date once the...

Page 24: ...reduced DHW off if the house is unattended for longer periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION T...

Page 25: ...h Code Description 9 3 2 5 0D 0 230V 1ph 1 230V 3ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup heat...

Page 26: ...outdoor ambient temperature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient te...

Page 27: ...stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0A Comfort setpoint 30 C 6 0E C Eco setpoi...

Page 28: ...o the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decr...

Page 29: ...er dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional...

Page 30: ...acts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Ext thermostat type Only applicable in external room thermostat control For mor...

Page 31: ...perature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext...

Page 32: ...door unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indo...

Page 33: ...or leaving water and tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic h...

Page 34: ...6 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sur...

Page 35: ...diagram Indoor unit 3D120613B R2T R1T B1PW B2L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut...

Page 36: ...rmostat wired On OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF therm...

Page 37: ...xing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid...

Page 38: ...luded A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR1 wireless room thermostat Only for KRTRB wireless room thermostat Only for KRTW wired room thermostat 5 core for C H oper...

Page 39: ......