background image

6 Configuration

Installation manual

21

ETBH/9W
Daikin Altherma 3 H HT W
4P586453-1C – 2020.10

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

6.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.

Emitter type

Heating  up  or  cooling  down  the  main  zone  can  take  longer.  This
depends on:

▪ The water volume of the system

▪ The heater emitter type of the main zone

The  setting 

Emitter  type

  can  compensate  for  a  slow  or  a  quick

heating/cooling system during the heat up/cool down cycle. In room
thermostat  control, 

Emitter 

type

  influences  the  maximum

modulation  of  the  desired  leaving  water  temperature,  and  the
possibility  for  usage  of  the  automatic  cooling/heating  changeover
based on the indoor ambient temperature.

It is important to set 

Emitter type

 correctly and in accordance with

your system layout. The target delta T for the main zone depends on
it.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 70°C

Fixed 10°C

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–10/2=

35°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

6.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"6.2.5  Configuration

wizard: Main zone"

 [

4

 21].

Summary of Contents for ETBH16DF6V

Page 1: ...Installation manual Daikin Altherma 3 H HT W English https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT W ETBH16DF6V ETBH16DF9W ETBX16DF6V ETBX16DF9W...

Page 2: ...y odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Page 3: ...Additional zone 21 6 2 7 Configuration wizard Tank 22 6 3 Weather dependent curve 22 6 3 1 What is a weather dependent curve 22 6 3 2 2 points curve 23 6 3 3 Slope offset curve 23 6 3 4 Using weather...

Page 4: ...g 1 h a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Sealing ring for shut off valve f Shut off valve g Overpressure bypass...

Page 5: ...box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user i...

Page 6: ...en the switch box See 3 2 1 To open the indoor unit 45 Fix the unit to the wall with an 8 mm screw 3 3 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected...

Page 7: ...anger coil The booster heater must be located above the heat exchanger coil NOTICE Performance Performance data for third party tanks CANNOT be provided and performance CANNOT be guaranteed NOTICE Con...

Page 8: ...he glycol s corrosion inhibitor NOTICE Glycol absorbs water from its environment Therefore do NOT add glycol that has been exposed to air Leaving the cap off the glycol container causes the concentrat...

Page 9: ...ccess to other components during service CAUTION Do NOT push or place redundant cable length in the unit NOTICE The distance between the high voltage and low voltage cables should be at least 50 mm 5...

Page 10: ...nt Wires 2 0 75 1 25 mm Maximum length 500 m 2 9 Control 1 6 Room sensor offset Item Description in case of DHW tank 3 way valve See Installation manual of the 3 way valve Addendum book for optional e...

Page 11: ...EKHWP HYC Tank with optional booster heater installed at the top of the tank Power consumption control settings On the user interface make sure to set 9 9 1 1 Power consumption control Continuous 9 9...

Page 12: ...able legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit...

Page 13: ...alve INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor heating and heat pump convectors install a shut off valve before the underfloor heating to prevent...

Page 14: ...o the cable tie mountings 5 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedule 1 Open...

Page 15: ...nnect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF outp...

Page 16: ...r consumption digital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3...

Page 17: ...ork as expected The configuration influences the following The calculations of the software What you can see on and do with the user interface How You can configure the system via the user interface F...

Page 18: ...g the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to...

Page 19: ...lly or by manual interaction When Emergency is set to Automatic and a heat pump failure occurs the backup heater automatically takes over the heat load and the booster heater in the optional tank take...

Page 20: ...you can set the exact heater capacity and this will lead to more accurate energy data Code Description 9 4 1 6 02 Booster heater capacity kW Only applies to domestic hot water tank with an internal bo...

Page 21: ...ase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled...

Page 22: ...ng Tank Heat up mode Reheat only Comfort setpoint Only applicable when domestic hot water preparation is Schedule only or Schedule reheat When programming the schedule you can make use of the comfort...

Page 23: ...mperature Y1 Y2 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water ta...

Page 24: ...n zone WD curve type Viewing which type is selected is also possible via 3 C Additional zone WD curve type 5 E Tank WD curve type Restriction Only available to installers To change the weather depende...

Page 25: ...an only send a thermo ON OFF condition There is no separation between heating or cooling demand 2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OFF conditi...

Page 26: ...meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumpt...

Page 27: ...unted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit...

Page 28: ...tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To mon...

Page 29: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 8 Hand over to the user O...

Page 30: ...ng diagram Indoor unit 3D120613A R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Sh...

Page 31: ...mostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermosta...

Page 32: ...V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electricity meters For safety thermostat For safety...

Page 33: ...tion signal 2 core signal 2 core signal 2 core signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A1...

Page 34: ......

Page 35: ......

Page 36: ...4P586453 1C 2020 10 Copyright 2019 Daikin 4P586453 1 C 00000003 Verantwortung f r Energie und Umwelt...

Reviews: