background image

Installation manual

13

ERSQ+ERRQ011~Y1

Outdoor unit for air to water heat pump

4PW49635-1A

M2F ........................Motor (fan) (lower)

PS ..........................Switching power supply

Q1DI.......................Field earth leakage breaker (300 mA)

R1,R2 .....................Resistor

R1T ........................Thermistor (air)

R2T ........................Thermistor (discharge)

R2T ............... #......Thermistor (M1C discharge)

R3T ........................Thermistor (suction 1)

R4T ................*......Thermistor (heat exchanger)

R4T ............... #......Thermistor (subcooling heat exchanger)

R5T ........................Thermistor (suction 2)

R6T ................*......Thermistor (subcooling heat exchanger)

R6T ............... #......Thermistor (heat exchanger)

R7T ........................Thermistor (liquid pipe 1)

R8T ........................Thermistor (liquid pipe 2)

R9T ............... #......Thermistor (power module)

S1NPH ...................Pressure sensor (high)

S1NPL....................Pressure sensor (low)

S1PH......................Pressure switch (high)

V1R ........................Power module

V2R ................*......Diode module

V2R ............... #......Power module

V3R ........................Diode module

V1T.................*......IGBT (Insulated Gate Bipolar Transistor)

X1M........................Terminal strip (power supply)

X2M........................Terminal strip (control)

Y1E ........................Electronic expansion valve (main)

Y3E ........................Electronic expansion valve (subcool)

Y1S ........................Solenoid valve (4 way valve)

Y2S ........................Solenoid valve (hot gas)

Y3S ........................Solenoid valve (unload circuit)

Z1C~Z8C........*......Noise filter (ferrite core)

Z1C~Z7C....... #......Noise filter (ferrite core)

Z1F~Z4F ........*......Noise filter

Z1F~Z3F ....... #......Noise filter

Parts table legend

Notes

9.3.

System overview of field wiring

(See figure 9)

9.4.

Precautions on wiring of power supply and 
inter-unit wiring

Let the power wire (including ground wire and if applicable, the
bottom plate heater wire) go through the power outlet port on
either the front, side or back of the outdoor unit.

Let the transmission wires go through the cable outlet port, pipe
outlet port or knock out hole on either the front, side or back of
the outdoor unit. 

(See figure 8)

.

Precautions when knocking out knockout holes

To punch a knock hole, hit on it with a hammer.

After knocking out the holes, we recommend you paint the
edges and areas around the edges using the repair paint to
prevent rusting.

When passing electrical wiring through the knock holes, remove
any burrs from the knock holes and wrap the wiring with
protective tape to prevent damage.

If there is any possibility that small animals enter the system
through the knock holes, plug the holes with packing materials
(to be prepared on-site).

*

For V1 models only

#

For Y1 models only

1

This wiring diagram only applies to the outdoor unit.

4

Refer to the wiring diagram sticker (on the back of the
front plate) for instructions on how to use BS1~BS5 and
DS1-1, DS1-2 switches.

5

Do not operate the unit by short-circuiting protection
device S1PH.

7

Refer to the installation manual for connection wiring to
indoor-outdoor transmission F1-F2.

1

Earth leakage breaker

2

Field fuse

3

Remote controller

A

Rear direction

B

Lateral direction

C

Front direction

1

Power terminal block (X1M)

2

Control wiring between units

3

Power cable with ground wire. (Keep proper distance between 
power cable and control wiring).

4

Clamp (field supply)

5

Stop valve mounting plate

6

Power cable

7

Ground cable (yellow/green)

8

Fix the control wiring with the clamp

9

Control terminal block (X2M)

10

Interconnection cable for bottom plate heater (ERRQ only)

1

Knockout hole

2

Burr

3

Packing materials

2

3

1

Summary of Contents for ERSQ011AAV1

Page 1: ...STALLATION MANUAL ERSQ011AAV1 ERSQ014AAV1 ERSQ016AAV1 ERRQ011AAV1 ERRQ014AAV1 ERRQ016AAV1 ERSQ011AAY1 ERSQ014AAY1 ERSQ016AAY1 ERRQ011AAY1 ERRQ014AAY1 ERRQ016AAY1 Outdoor unit for air to water heat pum...

Page 2: ...L2 H H L2 0 L2 1 2 H 1 2 H L2 H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000...

Page 3: ...scrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustan...

Page 4: ...is the original instruction Other languages are translations of the original instructions 1 INTRODUCTION 1 1 General information Thank you for purchasing this unit The outdoor unit is the air to water...

Page 5: ...check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove...

Page 6: ...cation e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible 2 When installing the unit in a place exposed to strong wind pay special attention to the following...

Page 7: ...of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installing one unit per row CAUTION When operating the...

Page 8: ...In case drain work on your unit is allowed and the installation site requires drain work then follow the guidelines below Drain kits for drainage are available as option If drain work from the outdoo...

Page 9: ...See the table below concerning lengths and heights Refer to figure 1 Assume that the longest line in the figure corresponds with the actual longest pipe and the highest unit in the figure corresponds...

Page 10: ...tem and prevents proper operation The nitrogen pressure should be set to 0 02 MPa i e just enough so it can be felt on the skin with a pressure reducing valve Do not use anti oxidants when brazing the...

Page 11: ...liquid side 4 mm gas side 6 mm into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning The valve is now open Closing the stop valve...

Page 12: ...the vacuum pump to both the service port of the gas stop valve and the liquid stop valve to increase efficiency Setup See figure 6 Leak test The leak test must satisfy specification EN 378 2 1 Vacuum...

Page 13: ...cessary amount 8 1 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigera...

Page 14: ...arge the additional refrigerant in its liquid state through the service port on the liquid stop valve taking into account following instructions Turn on the power supply of the outdoor unit and indoor...

Page 15: ...urrent which will have to be discharged with the grounding For Y1 models only Make sure to connect power supply cables in normal phase If connected in reverse phase the remote controller of the indoor...

Page 16: ...e transmission wires go through the cable outlet port pipe outlet port or knock out hole on either the front side or back of the outdoor unit See figure 8 Precautions when knocking out knockout holes...

Page 17: ...lues see electrical data of combination with indoor units for exact values 27 A 27 5 A 13 5 A 14 A Transmission line section 0 75 1 25 mm2 Wire type b b Only in protected pipes use H07RN F when protec...

Page 18: ...maximum allowable pressure as indicated on the nameplate of the unit Provide a logbook In accordance with the relevant national and international regulations it may be neccesary to provide a logbook...

Page 19: ...et this function ON or OFF push the button as shown below 4 Push the button and the setting is defined 5 When the button is pushed again the operation starts according to the setting Vacuuming method...

Page 20: ...nal legislation 14 UNIT SPECIFICATIONS Technical specifications Electrical specifications The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor by...

Page 21: ...V1 Y1 3 9 10 1 2 1 2 3 V1 type 1N 50 Hz 220 240 V Y1 type 3N 50 Hz 380 415 V L1 L3 L2 L1 L3 L2 NOTES 10 3 8 2 1 7 6 9 4 4 6 1 4 3 10 4 7 2 9 8 2 10 X2M X3M X1M X2M X1M Y1 V1 3 X2M X3M X2M A2P A1P A1P...

Page 22: ...4PW49635 1A Copyright Daikin...

Reviews: