Installer reference guide
27
08 + ERLQ004~008
Daikin Altherma - Low Temperature Split
4P313774-1 – 2012.05
7 Installation
7.1.2 To open the indoor unit
1
Loosen and remove the 2 screws that fix the front panel.
2
Tilt the front panel towards you and remove the front panel.
7.1.3 To open the switch box cover of the indoor
unit
7.2
Mounting the outdoor unit
7.2.1 To prepare the installation structure
Check the strength and level of the installation ground so that the unit
will not cause any operating vibration or noise.
Fix the unit securely by means of the foundation bolts in accordance
with the foundation drawing.
If the unit is installed directly on the floor, prepare 4 sets of M8 or M10
anchor bolts, nuts and washers (field supply) as follows:
In order to guarantee good operation of the unit in areas with risk of
snowfall, a minimum of 15 cm needs to be assured below the bottom
plate of the unit. It is recommended to construct a pedestal with the
same height as the maximum snowfall height. On this pedestal it is
then recommended to install the EKFT008CA option kit to guarantee
the minimum space of 15 cm below the bottom plate of the unit.
INFORMATION
The maximum height of the upper protruding part of the
bolts is 15 mm.
2x
4x
a
Maximum snowfall height
b
EKFT008CA option kit
283
580
<100
(mm)
<100
>300
283
580
<150
<150
(mm)
>300
150
a
b