Daikin ERHQ006BAV3 Installation Manual Download Page 9

ERHQ006~0 ERLQ006~008BAV3

Outdoor unit for air to water heat pump

4PW54246-1A

Installation manual

7

All refrigerant pipe joints should be tightened with a torque
wrench at the specified tightening torque. See 

"Connecting the

refrigerant piping to the outdoor unit" on page 6

 for details.

1

Connect the projection side (on which the worm pin is pressed)
of the charging hose coming from the gauge manifold to the gas
stop valve's service port.

2

Fully open the gauge manifold's low-pressure valve (Lo) and
completely close its high-pressure valve (Hi).
The high-pressure valve subsequently requires no operation.

3

Apply vacuum pumping. Check that the compound pressure
gauge reads –0.1 MPa (–760 mm Hg).

4

Close the gauge manifold's low-pressure valve (Lo) and stop the
vacuum pump.

Leave as is for 4-5 minutes and make sure that the coupling
meter needle does not go back.

5

Remove the covers from the liquid stop valve and gas stop
valve.

6

Turn  the liquid stop valve's rod 90 degrees counterclockwise
with a hexagonal wrench to open the valve.

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit's
flare and the outdoor unit's flare and the valve rods.
After the check is complete, wipe all soapy water off.

7

Disconnect the charging hose from the gas stop valve's service
port, then fully open the liquid and gas stop valves.

Do not attempt to turn the valve rod beyond its stop.

8

Tighten the valve lids and service port caps for the liquid and
gas stop valves with a torque wrench at the specified torques.
See 

"Connecting the refrigerant piping to the outdoor unit" on

page 6

 for details.

Charging refrigerant

This outdoor unit is factory charged.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,

 the factory refrigerant charge of the product,

 the additional refrigerant amount charged in the field and

+

➁ 

the total refrigerant charge

on the fluorinated greenhouse gases label supplied with the product.

The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).

To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.

This outdoor unit is factory charged with refrigerant and depending
on pipe sizes and pipe lengths some systems require additional
charging of refrigerant.

Re-charging

In case re-charging is required, refer to the nameplate of the unit. The
nameplate states the type of refrigerant and necessary amount.

Pipe length

15 m

>15 m

Run time

10 minutes

15 minutes

NOTE

If the meter needle does go back, this may
indicate presence of moisture or leaking from
connecting parts. Repeat steps 

2

 through 

4

 after

checking all connecting parts and slightly
loosening and retightening the nuts.

1

4

10

2

6

5

3

7 8 9

8

1

Pressure meter

2

Gauge manifold

3

Low-pressure valve 
(Lo)

4

High-pressure valve 
(Hi)

5

Charging hoses

6

Vacuum pump

7

Service port

8

Valve lids

9

Gas stop valve

10

Liquid stop valve

NOTE

National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide
the appropriate official national language on the unit.
Therefore, an additional multilingual fluorinated
greenhouse gases label is supplied with the unit.

Sticking instructions are illustrated on the backside of
that label.

3

5

6

2

1

4

1

Factory refrigerant 
charge of the product:
see unit name plate

2

Additional refrigerant 
amount charged in the 
field

3

Total refrigerant charge

4

Contains fluorinated 
greenhouse gases 
covered by the Kyoto 
Protocol

5

Outdoor unit

6

Refrigerant cylinder and 
manifold for charging

Summary of Contents for ERHQ006BAV3

Page 1: ...INSTALLATION MANUAL ERHQ006BAV3 ERHQ007BAV3 ERHQ008BAV3 ERLQ006BAV3 ERLQ007BAV3 ERLQ008BAV3 Outdoor unit for air to water heat pump...

Page 2: ...o las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13...

Page 3: ...r leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire Consult your local deale...

Page 4: ...compressor before removing the refrigerant piping If the compressor is still running and the stop valve is open during pump down air will be sucked in when the refrigerant piping is removed causing a...

Page 5: ...re the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blocked drain p...

Page 6: ...nit mm Walls facing two sides unit mm Walls facing three sides unit mm NOTE Units cannot be installed hanging from ceiling or stacked CAUTION When operating the outdoor unit in a low outdoor ambient t...

Page 7: ...e end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 Remove the flare nut from the stop valve and put the flare nut on the pipe 4 Flar...

Page 8: ...from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Use a hexagonal wrench 4 mm to operate the stop valve rod All field piping must be installed by a lic...

Page 9: ...Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with indelible ink the factory refrigerant charge of the pro...

Page 10: ...Running it before the piping is ready will break the compressor WARNING All components procured on the site and all electric construction shall comply with the applicable local and national regulation...

Page 11: ...between indoor unit and outdoor unit when wire length exceeds 10 m use 2 5 mm wires instead of 1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safet...

Page 12: ...s from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If...

Page 13: ...carry out any service mode operation DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national l...

Page 14: ...4PW54246 1A Copyright Daikin...

Reviews: