INSTALLATION MANUAL
ERHQ006BAV3ERHQ007BAV3ERHQ008BAV3
ERLQ006BAV3ERLQ007BAV3ERLQ008BAV3
Outdoor unit for air to water heat pump
Page 1: ...INSTALLATION MANUAL ERHQ006BAV3 ERHQ007BAV3 ERHQ008BAV3 ERLQ006BAV3 ERLQ007BAV3 ERLQ008BAV3 Outdoor unit for air to water heat pump...
Page 2: ...o las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13...
Page 3: ...r leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire Consult your local deale...
Page 4: ...compressor before removing the refrigerant piping If the compressor is still running and the stop valve is open during pump down air will be sucked in when the refrigerant piping is removed causing a...
Page 5: ...re the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blocked drain p...
Page 6: ...nit mm Walls facing two sides unit mm Walls facing three sides unit mm NOTE Units cannot be installed hanging from ceiling or stacked CAUTION When operating the outdoor unit in a low outdoor ambient t...
Page 7: ...e end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 Remove the flare nut from the stop valve and put the flare nut on the pipe 4 Flar...
Page 8: ...from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Use a hexagonal wrench 4 mm to operate the stop valve rod All field piping must be installed by a lic...
Page 9: ...Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with indelible ink the factory refrigerant charge of the pro...
Page 10: ...Running it before the piping is ready will break the compressor WARNING All components procured on the site and all electric construction shall comply with the applicable local and national regulation...
Page 11: ...between indoor unit and outdoor unit when wire length exceeds 10 m use 2 5 mm wires instead of 1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safet...
Page 12: ...s from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If...
Page 13: ...carry out any service mode operation DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national l...