background image

9

 | 

Electrical installation

Installer reference guide

120

ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF

Daikin Altherma 3 R ECH₂O

4P678716-1 – 2022.01

In case of…

See…

Wired room thermostat with
multi-zoning base unit

Installation  manual  of  the  wired  room
thermostat (digital or analogue) + multi-zoning
base unit

Addendum book for optional equipment

In this case:

-

You  need  to  connect  the  wired  room
thermostat  (digital  or  analogue)  to  the
multi-zoning base unit

-

You  need  to  connect  the  multi-zoning  base
unit to the outdoor unit

-

For  cooling/heating  operation,  you  also
need to implement a relay (field supply, see
addendum book for optional equipment)

9.3.1 To connect the electrical wiring to the indoor unit

Remark

: All cables which will be connected to the switch box of the ECH

2

O must be

fixed by strain relief.

To have easier access to the switch box itself and the routing of cables the switch
box can be lowered (see 

"7.2.4 To open the indoor unit"

 [

4

 76]).

If  the  switch  box  is  lowered  in  service  position  while  the  electrical  installation  is
done, additional cable length has to be taken into account adequately. The cable
routing in normal position is longer than in service position.

Summary of Contents for ERGA06EAV3H

Page 1: ...V3H ERGA08EAV3H ERGA04EAV3A ERGA06EAV3A ERGA08EAV3A ERGA04EAV37 EHSH04P30EF EHSHB04P30EF EHSH08P30EF EHSHB08P30EF EHSH08P50EF EHSHB08P50EF EHSX04P30EF EHSXB04P30EF EHSX04P50EF EHSXB04P50EF EHSX08P30EF...

Page 2: ...5 3 3 Possible options for the indoor unit 29 6 Application guidelines 33 6 1 Overview Application guidelines 33 6 2 Setting up the space heating cooling system 34 6 2 1 Single room 35 6 2 2 Multiple...

Page 3: ...erant piping 90 8 2 3 Guidelines when connecting the refrigerant piping 90 8 2 4 Pipe bending guidelines 91 8 2 5 To flare the pipe end 91 8 2 6 To braze the pipe end 92 8 2 7 Using the stop valve and...

Page 4: ...46 11 1 1 To access the most used commands 147 11 1 2 To connect the PC cable to the switch box 149 11 2 Configuration wizard 149 11 3 Possible screens 151 11 3 1 Possible screens Overview 151 11 3 2...

Page 5: ...ise cavitation 257 15 3 7 Symptom The pressure relief valve opens 258 15 3 8 Symptom The water pressure relief valve leaks 258 15 3 9 Symptom The space is NOT sufficiently heated at low outdoor temper...

Page 6: ...n manual Outdoor unit Installation instructions Format Paper in the box of the outdoor unit Installation manual Indoor unit Installation instructions Format Paper in the box of the indoor unit Install...

Page 7: ...nal Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required Online tools In addition to the documentation set some o...

Page 8: ...result in death or serious injury WARNING FLAMMABLE MATERIAL CAUTION Indicates a situation that could result in minor or moderate injury NOTICE Indicates a situation that could result in equipment or...

Page 9: ...formation on how to prepare for an installation Piping installation What to do and know to install the piping of the system including information on how to prepare for an installation Electrical insta...

Page 10: ...efrigerant WARNING Improper installation or attachment of equipment or accessories could result in electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optio...

Page 11: ...ation of the unit Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmos...

Page 12: ...nt Do NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been connected make sure there is no gas leak Use nitrogen to perfor...

Page 13: ...stallation manual or installer reference guide of your application for more information NOTICE Make sure water quality complies with EU directive 2020 2184 2 1 5 Electrical DANGER RISK OF ELECTROCUTIO...

Page 14: ...ing of the earth leakage protector CAUTION When connecting the power supply connect the earth cable first before making the current carrying connections When disconnecting the power supply disconnect...

Page 15: ...ponents box is connected securely Make sure all covers are closed before starting up the unit NOTICE ONLY applicable if the power supply is three phase and the compressor has an ON OFF starting method...

Page 16: ...tion site 466 WARNING Follow the service space dimensions in this manual for correct installation of the unit Outdoor unit See 7 1 1 Installation site requirements of the outdoor unit 466 Indoor unit...

Page 17: ...NING SCALDING Mounting the outdoor unit see 7 3 Mounting the outdoor unit 479 WARNING Fixing method of the outdoor unit MUST be in accordance with the instructions from this manual See 7 3 Mounting th...

Page 18: ...efrigerant circuit may be isolated from other sections caused by components with specific functions e g valves The refrigerant circuit therefore features additional service ports for vacuuming pressur...

Page 19: ...all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth th...

Page 20: ...ve a set maximum value This maximum allowable hot water temperature shall be selected according to the applicable legislation CAUTION The disinfection function settings MUST be configured by the insta...

Page 21: ...default setting If you are unable to find the cause of the problem call your dealer WARNING Prevent hazards due to inadvertent resetting of the thermal cut out power to this appliance MUST NOT be supp...

Page 22: ...move the accessories from the indoor unit 25 4 3 3 To handle the indoor unit 25 4 1 Overview About the box This chapter describes what you have to do after the boxes with the outdoor and indoor unit a...

Page 23: ...e left and the handle to the right Pull up both sides of the sling at the same time to prevent disconnection of the sling from the unit 2 1 1 2 While handling the unit Keep both sides of the sling lev...

Page 24: ...house gases label d Energy label e Unit mounting plate f Bolts nuts washers spring washers and wire clamp 4 3 Indoor unit At delivery the unit MUST be checked for damage Any damage MUST be reported im...

Page 25: ...ain pan hose k Drain pan hose clamp l Cable fixation for strain relief m Cable tie n Switch box metal insert o Screw for switch box metal insert p Top cover screws q General safety precautions r WLAN...

Page 26: ...4P678716 1 2022 01 a Screw plug b Assembly wrench c Handle 1 Open the screw plugs on the front and back of the tank 2 Attach the handles horizontally and turn by 360 3 Use the handles to carry the un...

Page 27: ...outdoor unit 29 5 3 2 Possible options for the outdoor unit 29 5 3 3 Possible options for the indoor unit 29 5 1 Overview About the units and options This chapter contains information about Identifyi...

Page 28: ...2 2 Identification label Indoor unit Location Model identification Example E HS H B 04 P 30 EF Code Description E European model HS Floor standing refrigerant split unit with integrated pressureless...

Page 29: ...008D The U beams are installation brackets on which the outdoor unit can be installed It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfal...

Page 30: ...r sensor KRCS01 1 By default the internal sensor of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat will be used as room temperature sensor As an option the remote indoor sensor...

Page 31: ...all the optional wireless LAN module BRP069A71 For installation instructions see the installation manual of the WLAN module and the addendum book for optional equipment Universal centralised controlle...

Page 32: ...kit BIV connector kit EKECBIVCO To make the connection of a bivalent heat source to the bivalent heat exchanger easier you can install a bivalent connector kit For installation instructions see the i...

Page 33: ...r 56 6 4 5 DHW pump for disinfection 56 6 5 Setting up the energy metering 57 6 5 1 Produced heat 57 6 5 2 Consumed energy 57 6 5 3 Normal kWh rate power supply 58 6 5 4 Preferential kWh rate power su...

Page 34: ...or thermostat ON OFF signal voltage free contact closed contact thermo ON open contact thermo OFF 6 2 Setting up the space heating cooling system The heat pump system supplies leaving water to heat em...

Page 35: ...ation Setting Value Unit temperature control 2 9 Code C 07 2 Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface Number of water tempera...

Page 36: ...thermostat optional equipment EKRTR1 Configuration Setting Value Unit temperature control 2 9 Code C 07 1 External room thermostat Unit operation is decided by the external thermostat Number of water...

Page 37: ...nvectors For more information see The installation manual of the heat pump convectors The installation manual of the heat pump convector options The addendum book for optional equipment The space heat...

Page 38: ...ing the electrical wiring to the unit see 9 2 Connections to the outdoor unit 4115 9 3 Connections to the indoor unit 4117 The heat pump convectors are directly connected to the indoor unit A shut off...

Page 39: ...eat pump system Comfort The combination of the two heat emitter types provides The excellent heating comfort of the underfloor heating The excellent cooling comfort of the heat pump convectors 6 2 2 M...

Page 40: ...ectly connected to the indoor unit The room temperature of the main room is controlled by the dedicated Human Comfort Interface BRC1HHDA used as room thermostat A thermostatic valve is installed befor...

Page 41: ...liable operation provide a minimum water flow as described in table To check the water volume and flow rate in 8 5 Preparing water piping 498 The user interface integrated in the indoor unit decides t...

Page 42: ...al of the heat pump convectors The installation manual of the heat pump convector options The addendum book for optional equipment The user interface integrated in the indoor unit decides the space op...

Page 43: ...ting A shut off valve to prevent hot water supply when the room has no heating demand A shut off valve to prevent condensation on the floor during cooling operation of the rooms with heat pump convect...

Page 44: ...hest design temperature in cooling Additional zone Zone with the highest design temperature in heating and the lowest design temperature in cooling CAUTION If there is more than one leaving water zone...

Page 45: ...r for main zone B C a a f A E D b c g d e h 3 System with hydraulic separator for both zones For this system a direct pump is required for the additional zone B C a a f A E D b c g d e i h A Additiona...

Page 46: ...request of the room The room temperature is controlled by the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Ensure water circulation is possible in main zone when shut off valves...

Page 47: ...s 4 4 Code 7 02 1 Dual zone Main additional In case of heat pump convectors External room thermostat for the additional zone 3 A Code C 06 1 1 contact When the used external room thermostat or heat pu...

Page 48: ...comfort for each individual installation INFORMATION For systems without indirect auxiliary boiler connected to the storage tank it is mandatory to install an electric backup heater to ensure safe ope...

Page 49: ...determined automatically depending on the outdoor temperature During heating operation of the auxiliary boiler the auxiliary boiler operates to achieve the desired water temperature set via the auxil...

Page 50: ...unit air thermistor install the outdoor unit in the shadow so that it is NOT influenced or turned ON OFF by direct sunlight Frequent changeover may cause corrosion of the auxiliary boiler Contact the...

Page 51: ...auxiliary gas boiler must have a fixed setpoint 55 C or a weather dependent setpoint Tmin 0 30 25 20 15 10 5 0 5 20 30 40 50 60 10 Ta C Tmin C Ta Outdoor temperature Tmin Minimum weather dependent se...

Page 52: ...al on the indoor unit X12M 3 and X12M 4 See 9 3 10 To connect the changeover to external heat source 4133 Configuration Via the user interface configuration wizard Set the use of an indirect bivalent...

Page 53: ...tank temperature above which all other heat sources are stopped when solar energy is provided See Intelligent tank manager 4227 for more information on configuration 6 3 4 Setting up a solar system v...

Page 54: ...you can set the storage tank temperature at a higher temperature example 53 C which is then mixed with cold water example 15 C The resulting domestic hot water temperature depends on this setpoint as...

Page 55: ...e if it is installed and activated However this consumes more energy We recommend to set the desired storage tank temperature below 55 C to avoid using the electrical resistance The higher the outdoor...

Page 56: ...ect the domestic hot water pump 4130 For installation instructions of the optional recirculation connection see the installation manual of the recirculation kit 141554 Configuration For more informati...

Page 57: ...interface you can read out the following energy data Produced heat Consumed energy You can read out the energy data For space heating For space cooling For domestic hot water production You can read o...

Page 58: ...energy Preferred method because of higher accuracy Requires external power meters Setup and configuration When using electrical power meters set the number of pulses kWh for each power meter via the u...

Page 59: ...of one meter is insufficient The electrical meter cannot easily be installed in the electrical cabinet 230 V and 400 V three phase grids are combined very uncommon because of technical limitations of...

Page 60: ...Electrical cabinet L1 L2 L3 N Normal kWh rate power supply c Power meter L1 N d Power meter L1 L2 L3 N e Fuse L1 N f Fuse L1 L2 L3 N g Outdoor unit L1 N h Indoor unit L1 N i Backup heater L1 L2 L3 N...

Page 61: ...imiting the heat pump will reduce performance NOTICE Set a minimum power consumption of 3 6 kW to guarantee Defrost operation Otherwise if defrosting is interrupted several times the heat exchanger wi...

Page 62: ...ower limitation level Example To limit the maximum power of the entire house lighting domestic appliances space heating a b A B C 1 2 3 4 5 A8P A Outdoor unit B Indoor unit C Energy management system...

Page 63: ...is limited and turned OFF first The system limits power consumption in the following order 1 Turns OFF the backup heater 2 Limits the outdoor unit 3 Turns OFF the outdoor unit Example If the configur...

Page 64: ...p an external temperature sensor You can connect one external temperature sensor It measures the indoor or outdoor ambient temperature We recommend to use an external temperature sensor in the followi...

Page 65: ...e outdoor sensor and the addendum book for optional equipment Configuration Select outdoor sensor 9 B When the power saving functionality of the outdoor unit is active see Power saving function 4226 t...

Page 66: ...install the outdoor unit 82 7 3 5 To provide drainage 83 7 4 Mounting the indoor unit 85 7 4 1 About mounting the indoor unit 85 7 4 2 Precautions when mounting the indoor unit 85 7 4 3 To install th...

Page 67: ...tack the units on each other Do NOT hang the unit on a ceiling Strong winds 18 km h blowing against the outdoor unit s air outlet causes short circuit suction of discharge air This may result in deter...

Page 68: ...ge It is NOT recommended to install the unit in the following places because it may shorten the life of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapo...

Page 69: ...ille and dispose of it 3 Reattach the screws to the unit 2 4 1 3 a a Suction grille Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up c c d b e a...

Page 70: ...e following measurements guidelines Maximum refrigerant piping length between indoor unit and outdoor unit 30 m Minimum refrigerant piping length between indoor unit and outdoor unit 3 m Maximum heigh...

Page 71: ...for R32 units Additionally to the spacing guidelines Because the total refrigerant charge in the system is 1 84 kg the room where you install the indoor unit must also comply with the conditions descr...

Page 72: ...ilation openings 1 84 kg i e if the piping length is 27 m Living room kitchen garage attic basement storage room 2 3 Technical room i e room that is NEVER occupied by persons 2 3 4 PATTERN 1 PATTERN 2...

Page 73: ...rant charge mmax kg allowed for room A Contact your dealer Use table 3 in chapter Technical data and dm to calculate the minimum bottom opening area for natural ventilation between room A and room B A...

Page 74: ...mm from the floor of the unoccupied room Must be Anv min minimum bottom opening area as specified in the table below 50 of the required opening area Anv min must be 200 mm from the floor of the unoccu...

Page 75: ...closing the units 7 2 1 About opening the units At certain times you have to open the unit Example When connecting the refrigerant piping When connecting the electrical wiring When maintaining or ser...

Page 76: ...at the tightening torque does NOT exceed 4 1 N m 7 2 4 To open the indoor unit NOTICE The top cover can only be removed if the switch box is lowered Overview a b a User interface panel b Switch box co...

Page 77: ...To lower the switch box of the indoor unit and remove the top cover During the installation you will need access to the inside of the indoor unit To have easier front access lower the switch box of th...

Page 78: ...Daikin Altherma 3 R ECH O 4P678716 1 2022 01 1 4 If switch box is opened Disconnect the ground connection from the top cover of the switch box 5 If necessary remove the top cover This is necessary in...

Page 79: ...the following stages 1 Providing the installation structure 2 Installing the outdoor unit 3 Preventing the unit from falling over 4 Protecting the unit against snow and wind by installing a snow cover...

Page 80: ...ation with the low sound cover EKLN08A1 different installation instructions apply for the U beams See the installation manual of the low sound cover a b c a Low sound cover b Bottom parts of the low s...

Page 81: ...m Option 3 On a pedestal with the EKFT008D option kit The EKFT008D option kit is recommended in areas with heavy snowfall 300 6 0 0 1 5 0 1 5 0 mm 300 100 a b 0 mm a Maximum snowfall height b EKFT008D...

Page 82: ...50 300 250 mm a b c 4 a Maximum snowfall height b EKFT008D option kit c Anti vibration rubber field supply 7 3 4 To install the outdoor unit CAUTION Do NOT remove the protective cardboard before the u...

Page 83: ...tective cardboard b Instruction sheet 7 3 5 To provide drainage Make sure that condensation water can be evacuated properly Install the unit on a base to make sure that there is proper drainage in ord...

Page 84: ...ons see the installation manual of the drain pan In short the drain pan must be installed level with a tolerance of 1 at all sides and as follows b a c a Drain pan b U beams c Drain hole insulation 35...

Page 85: ...he indoor unit 7 4 1 About mounting the indoor unit When You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping Typical workflow Mounting the indoor unit...

Page 86: ...ollecting in the drain pan must be drained You must connect the drain hoses to an appropriate drain according to the applicable legislation 1 Open the screw plug a a c c b 1 3 2 a Screw plug b Assembl...

Page 87: ...in Altherma 3 R ECH O 4P678716 1 2022 01 a a Drain pan hose 7 Connect the pressure relief valve to an appropriate drain in accordance with the applicable legislation Ensure that any steam or water tha...

Page 88: ...harging refrigerant 98 8 4 3 To fix the fluorinated greenhouse gases label 98 8 5 Preparing water piping 98 8 5 1 Water circuit requirements 98 8 5 2 To check the water volume and flow rate 101 8 6 Co...

Page 89: ...at resistance of at least 120 C Insulation thickness Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 15 9 mm 5 8 16 20 mm 13 mm i i t p p If the tempe...

Page 90: ...32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used for R32 installations to withstand the pressure and to prevent foreign materials e g mineral oil...

Page 91: ...m 6 4 15 17 8 7 9 1 R 0 4 0 8 2 45 90 2 A 15 9 62 75 19 3 19 7 8 2 4 Pipe bending guidelines Use a pipe bender for bending All pipe bends should be as gentle as possible bending radius should be 30 40...

Page 92: ...dversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure...

Page 93: ...indicated with the arrow Do NOT damage it After handling the stop valve tighten the stem cap and check for refrigerant leaks Item Tightening torque N m Stem cap liquid side 13 5 16 5 Stem cap gas side...

Page 94: ...piping to the indoor unit 1 Connect the liquid stop valve from the outdoor unit to the refrigerant liquid connection of the indoor unit a b a Refrigerant liquid connection b Refrigerant gas connection...

Page 95: ...eparing refrigerant piping 488 NOTICE Use a 2 stage vacuum pump with a non return valve that can evacuate to a gauge pressure of 100 7 kPa 1 007 bar 5 Torr absolute Make sure the pump oil does not flo...

Page 96: ...rvice port h Valve lids i Gas stop valve j Liquid stop valve 1 Vacuum the system until the pressure on the manifold indicates 0 1 MPa 1 bar 2 Leave as is for 4 5 minutes and check the pressure If the...

Page 97: ...outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it might be necessary to connect electrical wiring...

Page 98: ...el is delivered with the unit see accessories peel off the applicable language and stick it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total...

Page 99: ...or connecting the water circuit Inappropriate tooling will cause damage to the pipes Closed circuit Use the indoor unit ONLY in a closed water system Using the system in an open water system will lead...

Page 100: ...n hose to the drain 486 Air vents Provide air vents at all high points of the system which must also be easily accessible for servicing An automatic air purge is provided in the indoor unit Check that...

Page 101: ...sy filling and draining of the storage tank we recommend to install a shut off valve See option kit Fill and drain kit 165215 Thermostatic mixing valves In accordance with the applicable legislation i...

Page 102: ...e in the installation is guaranteed in all conditions Minimum required flow rate 12 l min NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it...

Page 103: ...6 2 Precautions when connecting the water piping INFORMATION Also read the precautions and requirements in the following chapters 2 General safety precautions 410 8 5 Preparing water piping 498 8 6 3...

Page 104: ...avoid damage apply the necessary countertorque with a suitable tool 2 7 mm 1 3 4 Connect the domestic hot water in and out pipes to the indoor unit Do NOT exceed the maximum tightening torque Thread s...

Page 105: ...lves on the space heating cooling water in and out connections as well as on the domestic cold water in and domestic hot water out connections These shut off valves are field supplied NOTICE To avoid...

Page 106: ...tc connected to the tank is subjected to this high pressure To prevent this a pressure relief valve needs to be installed The overpressure prevention depends on the correct operation of the field inst...

Page 107: ...cording to the instructions see To purge the air out of the unit with the manual air vent valves 4243 3 Open the water tap 4 Open fill and drain valve and monitor the manometer 5 Fill the system with...

Page 108: ...ng until no more air is vented from the taps 4 Check for water leaks The bivalent heat exchanger only for some models 5 Fill the bivalent heat exchanger with water by connecting the bivalent heating c...

Page 109: ...led drainback solar kit option 1 Combine the fill and drain kit option with the drainback solar kit option to fill the storage tank 2 Connect the hose with non return valve to the fill and drain kit F...

Page 110: ...37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be...

Page 111: ...t the shut off valve 128 9 3 6 To connect the electricity meters 129 9 3 7 To connect the domestic hot water pump 130 9 3 8 To connect the alarm output 131 9 3 9 To connect the space cooling heating O...

Page 112: ...OT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause ov...

Page 113: ...ning torque N m M4 X1M 1 2 1 5 M4 earth Indoor unit Item Tightening torque N m M4 X1M 1 2 M4 X12M X15M 0 88 10 Indoor unit BUH option Item Tightening torque N m M4 X6M 3V 6V 2 45 10 M4 X6M 9W 1 2 9 1...

Page 114: ...nt the outdoor unit compressor will NOT operate The wiring to the unit is different depending on whether the power supply is interrupted or NOT 9 1 5 Overview of electrical connections except external...

Page 115: ...equency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cable Minimum cable section of 1 5 mm and applicable for 230 V Recommended field fuse 20 A 25 A 16 A Earth leakage circ...

Page 116: ...ing cover 1 1 2 3 Strip insulation 20 mm from the wires a b a Strip wire end to this point b An excessive strip length may cause electrical shock or leakage 4 Connect the interconnection cable and pow...

Page 117: ...oor unit Item Description Power supply main See 9 3 2 To connect the main power supply 4122 Power supply backup heater See 9 3 3 To connect the backup heater power supply 4124 Backup heater See 9 3 4...

Page 118: ...ee 9 3 15 To connect the solar input 4143 DHW output See 9 3 16 To connect the DHW output 4143 Room thermostat wired or wireless See below table Wires 0 75 mm Maximum running current 100 mA For the ma...

Page 119: ...ernal sensor Room 1 7 Room sensor offset Human Comfort Interface See Installation and operation manual of the Human Comfort Interface Addendum book for optional equipment Wires 2 0 75 1 25 mm Maximum...

Page 120: ...ing base unit to the outdoor unit For cooling heating operation you also need to implement a relay field supply see addendum book for optional equipment 9 3 1 To connect the electrical wiring to the i...

Page 121: ...tion Installer reference guide 121 ERGA04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 All cables which will be connected to the switch box of the ECH2O must be f...

Page 122: ...hile cables are connected to one of the terminals Otherwise the cables could be too short X12M 9 3 2 To connect the main power supply 1 Open the following see 7 2 4 To open the indoor unit 476 1 User...

Page 123: ...le b Power supply indoor unit In case of preferential kWh rate power supply Interconnection cable Wires 3 GND 1 5 mm Power supply indoor unit Wires 1N GND Maximum running current 6 3 A Preferential kW...

Page 124: ...ply contact 3 Fix the cable with cable ties to the cable tie mountings General information see 9 3 1 To connect the electrical wiring to the indoor unit 4120 9 3 3 To connect the backup heater power s...

Page 125: ...13 A a Electrical equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage sy...

Page 126: ...P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 X6M SWB2 3V 3V 1N 230 V 6V 6V 1N 230 V 9W 3N 400 V 1N 50 Hz 230 V AC SWB2 Q1DI N L 1 2 3 4 F1B 20A I I X6M Model power supply Connections to backu...

Page 127: ...V AC SWB2 Q1DI L1 L2 L3 N X6M 1 2 3 4 5 6 F1B 20A I I I F1B Overcurrent fuse field supply Recommended fuse tripping class C Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal...

Page 128: ...INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor heating and heat pump convectors install a shut off valve before the underfloor heating to prevent cond...

Page 129: ...electricity meters Wires 2 per meter 0 75 mm Electricity meters 12 V DC pulse detection voltage supplied by PCB 9 A Energy metering INFORMATION In case of an electricity meter with transistor output...

Page 130: ...3 1 To connect the electrical wiring to the indoor unit 4120 9 3 7 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW...

Page 131: ...neral information see 9 3 1 To connect the electrical wiring to the indoor unit 4120 9 3 8 To connect the alarm output Wires 2 0 75 mm Maximum load 0 3 A 230 V AC Maximum load 1 A 5 V DC 9 D Alarm out...

Page 132: ...1 To connect the electrical wiring to the indoor unit 4120 9 3 9 To connect the space cooling heating ON OFF output INFORMATION Cooling is only applicable in case of reversible models Wires 2 0 75 mm...

Page 133: ...he indoor unit 4120 9 3 10 To connect the changeover to external heat source INFORMATION Bivalent is only possible in case of 1 leaving water temperature zone with room thermostat control OR external...

Page 134: ...ie mountings General information see 9 3 1 To connect the electrical wiring to the indoor unit 4120 9 3 11 To connect the power consumption digital inputs Wires 2 per input signal 0 75 mm Power limita...

Page 135: ...2 01 1 2 3 3 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below A B B A A8P M 1 0 8 X 1 2 3 4 5 1 2 4 5 S 6 S S 7 S S 8 S S 9 S 3 a 4 Fi...

Page 136: ...d of 15 V DC 10 mA 9 8 1 3 Benefit kWh power supply Safety thermostat 1 Open the following see 7 2 4 To open the indoor unit 476 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top co...

Page 137: ...fety thermostat after it is installed Without configuration the unit will ignore the safety thermostat contact 9 3 13 To connect a Smart Grid This topic describes 2 possible ways to connect the indoor...

Page 138: ...6 5 S S 10 4 3 X 5M 1 S S 4 10 9 a 2 1 a Jumper factory mounted If you also connect a safety thermostat Q4L replace the jumper with the safety thermostat wires S4S Smart Grid pulse meter 1 S10S Low vo...

Page 139: ...6 3 4 K1A L N L N STEP 3 a b c d e f STEP 1 STEP 2 A1 A2 25 24 25 23 X1 M 2 K2A A1 A2 2 1 STEP 1 Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 Hig...

Page 140: ...allation Installer reference guide 140 ERGA04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 X M 10 K1A X10M K2A 3 Install the components of the Smart Grid relay ki...

Page 141: ...0 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 K1A K2A X15M X12M X 5M M X 1 12 3 4 5 6 X15M 3 X12M 23 X12M 24 X12M 25 X12M 25 X15M 5 X15M 4 X15M 6 23 24 25 4 Connect the low voltage wiring as fol...

Page 142: ...1 24 25 X M 12 25 X M 12 24 X M 12 25 X M 12 23 1 2 23 L2 L1 N N 6 Fix the cable with cable ties to the cable tie mountings General information see 9 3 1 To connect the electrical wiring to the indoor...

Page 143: ...ndoor unit 476 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the solar input cable as shown in the illustration below A A B B 13 14 X 5M 1 13 14 Solar input 3 Fi...

Page 144: ...User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the DHW signal cable as shown in the illustration below A B X 2M 1 11 12 A B DHW output Max load 0 3 A 230 V AC 12 1...

Page 145: ...unit installation NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 1 Insulate and...

Page 146: ...ent curves 164 11 5 Settings menu 166 11 5 1 Malfunctioning 166 11 5 2 Room 166 11 5 3 Main zone 170 11 5 4 Additional zone 180 11 5 5 Space heating cooling 185 11 5 6 Tank 194 11 5 7 User settings 19...

Page 147: ...ferent methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings v...

Page 148: ...ttings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user pe...

Page 149: ...CCAB4 kit is required 1 Connect the USB connector of the cable to your PC 2 Connect the plug of the cable to X10A on A1P of the switch box of the indoor unit A1P X10A 3 Pay special attention to the po...

Page 150: ...umber of zones 4 4 11 5 5 Space heating cooling 4185 Glycol Filled system overview field setting E 0D 11 5 9 Installer settings 4206 Solar 9 2 4 11 5 9 Installer settings 4206 Backup heater Voltage 9...

Page 151: ...Heating WD curve 3 5 if applicable Cooling WD curve 3 6 if applicable Schedule 3 1 WD curve type 3 C read only Tank Heat up mode 5 6 11 5 6 Tank 4194 Hysteresis 5 9 11 3 Possible screens 11 3 1 Possib...

Page 152: ...ough the list of the main menu Go to the main menu screen Enable disable breadcrumbs Item Description a Domestic hot water a1 Domestic hot water a2 55 Measured tank temperature a b Disinfection Powerf...

Page 153: ...ss No room thermostat installed or set Unit operation is decided based on the leaving water temperature regardless of the actual room temperature and or heating demand of the room i2 Installed heat em...

Page 154: ...list Enter the submenu Enable disable breadcrumbs Submenu Description 0 or Malfunctioning Restriction Only displayed if a malfunction occurs See 15 4 1 To display the help text in case of a malfunctio...

Page 155: ...taller Perform tests and maintenance B User profile Change the active user profile C Operation Turn heating cooling functionality and domestic hot water preparation on or off D Wireless gateway Restri...

Page 156: ...Description Minimum temperature limit a1 Fixed by the unit a2 Restricted by the installer Maximum temperature limit b1 Fixed by the unit b2 Restricted by the installer Current temperature c Measured b...

Page 157: ...able if room thermostat control is active If leaving water temperature control is active you can program the main zone schedule instead 1 Go to the schedule 2 optional Clear the content of the whole w...

Page 158: ...ser defined 1 2 Select Edit Delete Edit Copy 3 Use the left dial to select an entry and edit the entry with the right dial You can program up to 6 actions each day On the bar a high temperature has a...

Page 159: ...User defined 1 2 Select Copy Delete Edit Copy Result Next to the copied day C is displayed 3 Select Tuesday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 4 Select Paste Delete Edit Copy Paste Result M...

Page 160: ...ser defined 1 C To rename the schedule 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Rename Delete Rename Select 3 optional To delete the current schedu...

Page 161: ...rve To be able to compensate for differences in temperature the unit relies on its weather dependent curve This curve defines how much the temperature of the tank or leaving water must be at different...

Page 162: ...m changes and proceed 11 4 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the...

Page 163: ...mperature at X1 is unequally higher than the preferred temperature at X2 When offset is changed the new preferred temperature at X1 is equally higher as the preferred temperature at X2 c Slope d Offse...

Page 164: ...point mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Additional zone Setpoint mode WD heating fixed cool...

Page 165: ...he maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve...

Page 166: ...eration User profile Main zone 11 5 2 Room Overview The following items are listed in the submenu 1 Room Main zone Malfunctioning Operation Additional zone 1 Room Setpoint screen 1 1 Schedule 1 2 Heat...

Page 167: ...al room thermostat and C 2 Space heating cooling Off or if 2 9 Control Leaving water In the above cases Antifrost will heat the space heating water to a reduced setpoint when the outdoor temperature i...

Page 168: ...on mode Heating The unit will supply leaving water to the heat emitters to heat up the room according to normal logic Space heating cooling On and Operation mode Cooling There is no room frost protect...

Page 169: ...nit will supply leaving water to the heat emitters to heat up the room again Code Description 1 4 1 2 06 Activation 0 No Antifrost functionality is OFF 1 Yes Antifrost functionality is on 1 4 2 2 05 R...

Page 170: ...et Human Comfort Interface BRC1HHDA used as room thermostat Offset on the actual room temperature measured by the Human Comfort Interface 5 C 5 C step 0 5 C 1 7 2 09 Room sensor offset external room s...

Page 171: ...nt screen 2 Main zone See 11 3 5 Setpoint screen 4155 Schedule Indicate if the temperature of the leaving water is defined according to a schedule or not Influence of the LWT setpoint mode 2 4 is as f...

Page 172: ...perature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Desc...

Page 173: ...mperature 40 C 5 C 1 01 High outdoor ambient temperature 10 C 25 C 1 02 Desired leaving water temperature when the outdoor temperature equals or drops below the low ambient temperature 9 01 C 9 00 C N...

Page 174: ...d water is required 1 09 Desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature 9 03 C 9 02 C Note This value should be lower than 1 08 as fo...

Page 175: ...ant that in heating the zone with the lowest water temperature is configured as the main zone and the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2...

Page 176: ...esign and selection of the heat emitters The desired leaving water temperature is the result of several settings preset values shift values weather dependent curves modulation As a result too high or...

Page 177: ...om thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 E...

Page 178: ...tween leaving water temperature setpoint and inlet temperature at startup INFORMATION If the main zone or the additional zone has a heating demand and this zone is equipped with radiators then the tar...

Page 179: ...can only be read out on the user interface 2 C 2 8 06 Max modulation 0 C 10 C This is the temperature value by which the desired leaving water temperature is increased or decreased INFORMATION When l...

Page 180: ...or cooling demand INFORMATION The setting F 0B is only valid when there is a thermostat or external room thermostat request setting NOT in case of leaving water temperature setting During cooling If F...

Page 181: ...mperature for the additional zone via setpoint screen 3 Additional zone See 11 3 5 Setpoint screen 4155 Schedule Indicates if the desired leaving water temperature is according to a schedule See 11 5...

Page 182: ...tdoor temperature 0 03 Low outdoor ambient temperature 40 C 5 C 0 02 High outdoor ambient temperature 10 C 25 C 0 01 Desired leaving water temperature when the outdoor temperature equals or drops belo...

Page 183: ...mperatures less cold water is required 0 04 Desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature 9 07 C 9 08 C Note This value should be lo...

Page 184: ...55 C 3 8 3 9 07 Cooling minimum 5 C 18 C 3 8 4 9 08 Cooling maximum 18 C 22 C Control The control type for the additional zone is read only It is determined by the control type of the main zone See 1...

Page 185: ...set see 11 4 3 Slope offset curve 4162 In 2 E WD curve type you can choose which method you want to use In 3 C WD curve type the chosen method is shown read only same value as in 2 E Code Description...

Page 186: ...the unit is in heating mode the icon is shown When the unit is in cooling mode the icon is shown The status indicator shows if the unit is currently in operation When the unit is not in operation the...

Page 187: ...veraged If the outdoor temperature drops the operation mode will switch to heating and vice versa If the outdoor temperature is between the Space heating off temperature and the Space cooling off temp...

Page 188: ...subtracted by the offset value thus 24 4 20 C Guard timer to prevent too frequent changing from heating to cooling and vice versa Code Description Changeover settings related to the indoor temperatur...

Page 189: ...ixing station NOTICE NOT configuring the system in the following way can cause damage to the heat emitters If there are 2 zones it is important that in heating the zone with the lowest water temperatu...

Page 190: ...ion Remark Continuous pump operation requires more energy than sample or request pump operation a b c d b c a Space heating cooling control b Off c On d Pump operation 4 5 F 0D 1 Sample The pump is ON...

Page 191: ...ing only Pump limitation The pump speed limitation defines the maximum pump speed In normal conditions the default setting should NOT be modified The pump speed limitation will be overruled when the f...

Page 192: ...pump speed limitation is applicable When there is heating output the pump speed is only determined by delta T in relation to the required capacity With this limitation range delta T is possible and t...

Page 193: ...p operation 0 Disabled if outdoor temperature is higher than 4 02 or lower than F 01 depending on heating cooling operation mode 1 Possible at all outdoor temperatures Increase around 0 C Use this set...

Page 194: ...e heating cooling Additional zone Information 5 Tank Setpoint screen 5 1 Powerful operation 5 5 Schedule 5 6 Heat up mode 5 7 Disinfection 5 8 Maximum 5 9 Hysteresis 5 B Setpoint mode 5 C WD curve 5 D...

Page 195: ...ting cooling interruptions will happen Schedule You can set the tank temperature schedule using the schedule screen For more information about this screen see 11 3 7 Schedule screen Example 4157 Heat...

Page 196: ...in field setting 2 03 after a disinfection operation When the high domestic hot water temperature can be a potential risk for human injuries a mixing valve field supply shall be installed at the dome...

Page 197: ...mit the temperatures at the hot water taps INFORMATION During disinfection of the water inside the domestic hot water heat exchanger coil by periodically heating the storage tank to a specific tempera...

Page 198: ...the high ambient temperature 35 C 6 0E C Margin In domestic hot water operation the following hysteresis value can be set for the heat pump operation Code Description 5 D 6 01 The temperature differen...

Page 199: ...set on the user interface t Time INFORMATION The maximum heat pump temperature depends on the ambient temperature For more information see the operation range WD curve When weather dependent operation...

Page 200: ...settings Time date once the unit is initialised Holiday About holiday mode During your holiday you can use the holiday mode to deviate from your normal schedules without having to change them While ho...

Page 201: ...level until the next scheduled action Use and program a quiet mode schedule INFORMATION If the outdoor temperature is below zero we recommend to NOT use the most quiet level To check if quiet mode is...

Page 202: ...alent 4222 Code Description 7 5 1 N A Electricity price High 7 5 2 N A Electricity price Medium 7 5 3 N A Electricity price Low 7 6 N A Gas price INFORMATION Electricity price can only be set when biv...

Page 203: ...hough the running cost can increase the total operation cost taking into account the reimbursement will be optimized NOTICE Make sure to modify the setting of the energy prices at the end of the incen...

Page 204: ...Reset 8 B Piping diagram Energy data Read out information about energy flows to check and optimize your energy consumption You can read out electricity input and produced heat divided into space heati...

Page 205: ...us real time sensor and actuator information within the piping layout This allows a check of the system at one glance R3T 3 R4T 3 3 3 P 3 V 3 R1T 3 R2T 3 R7T 3 R5T 3 R6T 3 a1 a3 a4 b1 2 a 3 b b5 b4 c1...

Page 206: ...ed electricity and consumed gas energy flow diagram 8 2 Malfunction history Malfunction history 8 3 Dealer information Contact helpdesk number 8 4 Sensors Room tank or domestic hot water outside and l...

Page 207: ...defrost 9 I Overview field settings 9 N Export MMI settings 9 O Intelligent tank management 9 P Bizone kit Configuration wizard After first power ON of the system the user interface will guide you us...

Page 208: ...schedule to determine when to turn on and off the pump When turned on the pump runs and makes sure hot water is instantly available at the tap To save energy only turn on the pump during periods of th...

Page 209: ...acity of the second step in emergency Code Description 9 3 3 4 0A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked...

Page 210: ...ater configuration Maximum capacity Code Description 9 3 9 4 07 Maximum capacity that should be delivered by the backup heater Range 1 kW 3 kW Step 1 kW Equilibrium Code Description 9 3 6 5 00 Equilib...

Page 211: ...nual interaction When Emergency is set to Automatic and a heat pump failure occurs the backup heater or boiler automatically takes over the domestic hot water production and space heating When Emergen...

Page 212: ...es NOT confirm emergency operation INFORMATION If the boiler is connected as auxiliary heat source to the tank via bivalent coil or via drain back connection the boiler and NOT the backup heater opera...

Page 213: ...heated with the backup heater If an auxiliary boiler is connected to the tank At ambient temperatures below 5 03 only the boiler is used for domestic hot water heating 9 6 2 5 03 Priority temperature...

Page 214: ...stops even when the target domestic hot water temperature is NOT reached The actual maximum running time also depends on setting 8 04 When Control Room thermostat This preset value is only taken into...

Page 215: ...ed on In case the space heating cooling request is OFF and the tank temperature setpoint is reached the unit can choose to buffer energy from the photovoltaic panels in the room only in case of room t...

Page 216: ...T set to Smart grid Allow pump 0 No Pump is forced off 1 Yes No limitation 9 8 4 D 01 Connection to a Benefit kWh power supply or a Smart grid 0 No The outdoor unit is connected to a normal power supp...

Page 217: ...mart Grid operation modes 9 8 6 N A Restriction Only applicable if 9 8 4 Smart grid To set if electrical heaters are allowed Allow electrical heaters No Yes 9 8 7 N A Restriction Only applicable in ca...

Page 218: ...tting Limit setting kW This prevents overconsumption and thus requiring the use of power from the grid Power consumption control Power consumption control See 6 Application guidelines 4 33 for detaile...

Page 219: ...LED 4 08 0 0 None Backup heater and booster heater can operate simultaneously 1 Booster heater The booster heater is prioritised 2 Backup heater The backup heater is prioritised Power consumption cont...

Page 220: ...rent from the permanent power limitation which is always changeable BBR16 activation Code Description 9 9 F 7 07 BBR16 activation 0 disabled 1 enabled BBR16 power limit Code Description 9 9 G N A BBR1...

Page 221: ...of the indoor unit measuring the indoor temperature The temperature sensor in the dedicated Human Comfort Interface is NOT used anymore Remark This value has only meaning in room thermostat control Ex...

Page 222: ...liary boiler is installed directly in the space heating circuit 2 Indirect DHW Set this value in case that the auxiliary boiler is connected to the storage tank and the heat generated by the auxiliary...

Page 223: ...ng and the boiler is activated to support in case of capacity shortage The switch over between the heat pump system parallel bivalent operation if applicable and the auxiliary boiler is based on the f...

Page 224: ...3 and LWT 55 C NOTICE Make sure to set the value of 5 01 at least 1 C higher than the value of C 03 For DHW heating switch over The heat pump system calculates a value Tlim based on outdoor temperatur...

Page 225: ...Very high 1 High 2 Medium 3 Low 4 Very low Alarm output Alarm output Code Description 9 D C 09 Alarm output Indicates the logic of the alarm output during malfunctioning 0 Abnormal The alarm output w...

Page 226: ...ll depends on the ambient temperature compressor conditions and minimum internal timers To enable the power saving function setting E 08 needs to be enabled on the user interface Code Description 9 F...

Page 227: ...ng 4148 Export MMI settings About exporting the configuration settings Export the configuration settings of the unit to a USB memory stick via the MMI the user interface of the indoor unit When troubl...

Page 228: ...ort while boiler may or may not operate This applies only when tank energy is allowed to be used for space heating C 02 3 and the auxiliary boiler is deemed more efficient by the efficiency calculatio...

Page 229: ...HPSH Space heating by heat pump operation Ttank Storage tank temperature TankSH Space heating by tank heating support Tset In this example Tank setpoint may differ depending on space heating setpoint...

Page 230: ...demand Enabling the function for a too small boiler may lead to undesirable and potentially damaging on off switching behavior of the heat pump Continuous heating The continuous heating function allo...

Page 231: ...lar energy is provided and storage tank temperature is above limit temperature heat pump and boiler are switched off 1 No Heat pump and boiler can operate also while solar energy is provided Bizone ki...

Page 232: ...aulic separator with direct pump d c b a a Indoor unit b Mixing station c Hydraulic separator d Direct pump Additional zone pump fixed PWM The speed of the additional zone pump can be fixed with this...

Page 233: ...0 300 sec default 125 11 5 10 Commissioning Overview The following items are listed in the submenu A Commissioning User profile Installer settings Information Operation A Commissioning A 1 Operation t...

Page 234: ...of the two needed connects the system to the internet The user you can then control the system via the Daikin Residential Controller app This needs the following components in case of WLAN cartridge b...

Page 235: ...scription D 1 N A Enable AP mode No Yes Reboot Reboot the WLAN cartridge module Code Description D 2 N A Reboot the gateway Back OK WPS Connect the WLAN cartridge module to the router Code Description...

Page 236: ...1 Configuration Installer reference guide 236 ERGA04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 Code Description D 6 N A Cloud connection Not connected Connecte...

Page 237: ...Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule Level 7 5 Electricity price High Medium Low Schedule 5 Tank Powerful operation...

Page 238: ...ly Smart grid operation mode Allow electrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2...

Page 239: ...tions such as room antifrost The unit automatically runs these functions when necessary During installation or service this behaviour is undesired Therefore the protective functions can be disabled At...

Page 240: ...the result NOTICE ALWAYS complete the refrigerant piping of the unit before operating If NOT the compressor will break 12 3 Checklist before commissioning 1 After the installation of the unit check th...

Page 241: ...relief valve purges water when opened Clean water MUST come out The minimum water volume is guaranteed in all conditions See To check the water volume and flow rate in 8 5 Preparing water piping 498 T...

Page 242: ...t you can start the air purge procedure NOTICE For safety reasons the air purge function does not work for very high storage tank temperatures Manual or automatic There are 2 modes for purging air Man...

Page 243: ...on automatically stops after 30 minutes INFORMATION For best results air purge each loop separately To purge the air out of the unit with the manual air vent valves c a b a b c Manual air vent valve 1...

Page 244: ...aller See To change the user permission level 4147 2 Go to A 3 Commissioning Air purge 3 In the menu set Type Automatic 4 Select Start air purge 5 Select OK to confirm Result The air purge starts It s...

Page 245: ...re information 12 4 4 Actuator test run Purpose Perform an actuator test run to confirm the operation of the different actuators For example when you select Pump a test run of the pump will start To p...

Page 246: ...f the building NOTICE The installer is responsible for contacting the screed manufacturer for the maximum allowed water temperature to avoid cracking the screed programming the underfloor heating scre...

Page 247: ...he left dial to save the schedule To perform an underfloor heating screed dryout INFORMATION If Emergency is set to Manual 9 5 0 and the unit is triggered to start emergency operation the user interfa...

Page 248: ...matically when done 5 To stop the underfloor heating screed dryout manually 1 Open the menu and go to Stop UFH screed dryout 2 Select OK to confirm To read out the status of an underfloor heating scre...

Page 249: ...is stopped Read out UFH screed dryout status When the program is stopped due to an error an operation switch off or a power failure you can read out the underfloor heating screed dryout status 1 Go to...

Page 250: ...taller setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can...

Page 251: ...performing maintenance at least once a year However applicable legislation might require shorter maintenance intervals In this chapter 14 1 Overview Maintenance and service 251 14 2 Maintenance safety...

Page 252: ...re Space heating cooling circuit Keep water pressure above 1 bar If it is lower add water Magnetic filter dirt separator NOTICE The optional magnetic filter dirt separator requires yearly maintenance...

Page 253: ...o be replaced by the manufacturer its service agent or similarly qualified persons Storage tank water level Carry out a visual check of the water level inside the storage tank 1 Open the following see...

Page 254: ...e relief valve leaks 258 15 3 9 Symptom The space is NOT sufficiently heated at low outdoor temperatures 259 15 3 10 Symptom Tank disinfection function is NOT completed correctly AH error 260 15 4 Sol...

Page 255: ...that All shut off valves of the water circuit are completely open The water filter is clean Clean if necessary There is no air in the system Purge air if necessary You can purge air manually see To p...

Page 256: ...or can start If the backup heater doesn t start either check and make sure that The power supply to the backup heater is correctly wired The backup heater thermal protector is NOT activated The backup...

Page 257: ...from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is s...

Page 258: ...expansion vessel is closed Open the valve The water circuit head is too high The water circuit head is the difference in height between the indoor unit and the highest point of the water circuit If t...

Page 259: ...cted directly to the tank and space heating support is activated make sure that the boiler is operating correctly the boiler capacity is sufficient The backup heater equilibrium temperature has not be...

Page 260: ...d off during disinfection Do NOT stop tank operation during disinfection 15 4 Solving problems based on error codes If the unit runs into a problem the user interface displays an error code It is impo...

Page 261: ...ality indoor unit 81 07 Mixed leaving water temperature after the tank thermistor abnormality DLWA2 89 01 Heat exchanger freeze up protection activated during defrost error 89 02 Heat exchanger freeze...

Page 262: ...Compressor startup defect E7 00 OU Malfunction of outdoor unit fan motor E8 00 OU Power input overvoltage E9 00 Malfunction of electronic expansion valve EA 00 OU Cool heat switchover problem EC 00 Ab...

Page 263: ...re rise problem L4 00 OU Malfunction of inverter radiating fin temperature rise L5 00 OU Inverter instantaneous overcurrent DC L8 00 Malfunction triggered by a thermal protection in the inverter PCB L...

Page 264: ...to domestic hot water tapping following actions are recommended It is recommended to program the start up of the disinfection function at least 4 hours later than the last expected large hot water tap...

Page 265: ...n the storage tank with a connected pressureless solar system 267 16 1 To drain the storage tank DANGER RISK OF BURNING SCALDING The water in the storage tank and all the connected piping can be very...

Page 266: ...ltherma 3 R ECH O 4P678716 1 2022 01 a b 2 1 a Connection cover b Screw plug 3 Insert the screw plug into the fill and drain kit and secure with the clip contained in the option kit b 1 2 a b a b a Fi...

Page 267: ...ew plug with drain connection a b 1 2 3 c d a Screw plug b Sealing plug c Screw plug with drain connection optional fill and drain kit d Screw plug with drain connection spillover connector 16 1 2 To...

Page 268: ...04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 1 a a b c 3 4 2 5 a Clip b Sealing plug c Fill and drain kit 5 Open the valve of the fill and drain kit 6 Switch t...

Page 269: ...natural ventilation indoor unit 280 17 8 ESP curve Indoor unit 282 17 9 Name plate Indoor unit 282 17 1 Piping diagram Outdoor unit R2T 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 12 7 CuT 12 7 C...

Page 270: ...quid refrigerant IN cooling mode evaporator c3 Gas refrigerant OUT cooling mode evaporator c4 Liquid refrigerant OUT heating mode condenser d1 Water IN from bivalent heat source screw connection 1 d2...

Page 271: ...lation Notes Notes Connection X1M Main terminal Earth wiring Field supply Option Switch box PCB Wiring depending on model Protective earth Field wire NOTES 1 When operating do not short circuit protec...

Page 272: ...ing power supply Q1L Thermal protector Q1DI Earth leakage circuit breaker Q Insulated gate bipolar transistor IGBT R1T Thermistor air R2T Thermistor heat exchanger R3T Thermistor discharge RTH2 Resist...

Page 273: ...Not mounted in switch box Wiring depending on model PCB Backup heater power supply Backup heater power supply 3V 1N 230 V 3 kW 3V 1N 230 V 3 kW 6V 1N 230 V 6 kW 6V 1N 230 V 6 kW 6WN 9WN 3N 400 V 6 9...

Page 274: ...A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A8P Demand PCB A11P MMI user interface of the indoor unit Main PCB A14P PCB of the dedicated Human Comfort Interface BRC1HHD...

Page 275: ...supply Translation of text on wiring diagram English Translation 1 Main power connection 1 Main power connection Outdoor unit Outdoor unit SWB1 Switch box 2 User interface 2 User interface Only for re...

Page 276: ...Gas meter Gas meter Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Note outputs can be taken from terminal positions X12M 17 L 18 N and X12M 17...

Page 277: ...s and heat pump convector 5 External On OFF thermostats and heat pump convector Additional LWT zone Additional leaving water temperature zone Main LWT zone Main leaving water temperature zone Only for...

Page 278: ...4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART External room thermostat Heat pump convector main and or additional zone main X12M...

Page 279: ...charge allowed in a room indoor unit Aroom m2 Maximum refrigerant charge in a room mmax kg H 600 mm 1 0 138 2 0 276 3 0 414 4 0 553 5 0 691 6 0 829 7 0 907 8 0 970 9 1 028 10 1 084 11 1 137 12 1 187...

Page 280: ...RMATION For HPSU models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between two values from th...

Page 281: ...For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate dm values i e when dm is between two dm values fr...

Page 282: ...Notes Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction See also the minimum and maximum allowed water flow range in the technical specifications Make su...

Page 283: ...ECH O 4P678716 1 2022 01 q Refrigerant circuit r Max operating pressure refrigerant circuit s Total refrigerant charge for information see installation instructions for the outdoor heat pump unit t At...

Page 284: ...in product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenanc...

Page 285: ...EF EHSX04P30EF EHSXB04P30EF EHSX04P50EF EHSXB04P50EF EHSH08P30EF EHSHB08P30EF EHSX08P30EF EHSXB08P30EF EHSH08P50EF EHSHB08P50EF EHSX08P50EF EHSXB08P50EF Notes 1 300 Tank 2 500 Tank 3 X 4 H 5 B 6 EKECB...

Page 286: ...ving water 1 External room thermostat 2 Room thermostat 2 A C 05 R W 1 1 contact 2 2 contacts Delta T 2 B 1 1 0B R W 2 0C 2 R O 2 0C 2 3 10 C step 1 C 2 0C 2 Radiator 5 C 2 0C 2 Radiator 10 C 2 B 2 1...

Page 287: ...C Space heating cooling 4 4 7 02 R W 0 Single zone 1 Dual zone 4 5 F 0D R W 0 Continuous 1 Sample 2 Request 4 6 E 02 R W 1 R O 2 0 Reversible 1 1 Heating only 2 4 7 9 0D R W 0 8 step 1 0 No limitation...

Page 288: ...00 990 kWh 1 kWh 7 5 3 R W 0 00 990 kWh 1 kWh User settings 7 6 R W 0 00 990 kWh 0 00 290 MBtu 1 0 kWh Installer settings Configuration wizard System 9 1 3 2 E 03 R O 4 5 6 R W 7 0 no heater 7 2 3V 4...

Page 289: ...R W 25 43 C step 1 C 35 C 9 1 A 0 07 R W 10 25 C step 1 C 20 C Tank 9 1 B 1 6 0D R W 0 Reheat only 3 scheduled reheat 9 1 B 2 6 0A R W 30 6 0E C step 1 C 60 C 9 1 B 3 6 0B R W 30 min 50 6 0E C step 1...

Page 290: ...C 9 6 4 8 02 R W 0 10 hour step 0 5 hour 0 5 hour 9 6 5 8 00 R W 0 20 min step 1 min 1 min 9 6 6 8 01 R W 5 95 min step 5 min 30 min 9 6 7 8 04 R W 0 95 min step 5 min 95 min Installer settings 9 7 4...

Page 291: ...ormal 1 Normal 9 E 3 00 R W 0 manual 1 automatic 9 F E 08 R W 0 No 1 Yes 9 G R W 0 No 1 Yes Overview field settings 9 I 0 00 R W 9 05 min 45 9 06 C step 1 C 25 C 9 I 0 01 R W 9 05 9 06 C step 1 C 2 0C...

Page 292: ...one cooling WD curve Leaving water value for high ambient temp for DHW WD curve Leaving water value for low ambient temp for DHW WD curve High ambient temp for DHW WD curve Low ambient temp for DHW WD...

Page 293: ...kW 0kW 4 3kW 7 4kW 5 6kW 6 9 I 6 07 0 9 I 6 08 R W 2 20 C step 1 C 10 C 9 I 6 09 0 9 I 6 0A R W 30 6 0E C step 1 C 60 C What is the maximum desired room temperature in heating What is the mimimum desi...

Page 294: ...visible when the language of the user interface is set to Swedish Minimum running time for domestic hot water operation How much is the minimum pump PWM value Additional zone fixed pump PWM in case a...

Page 295: ...0 pulse kWh PV meter 7 1000 pulse kWh PV meter 9 I D 0A 0 9 I D 0B 2 9 I D 0C 0 9 I D 0D 0 9 I D 0E 0 9 I E 00 R O 0 5 0 LT split 9 I E 01 R O 0 9 I E 02 R W 1 R O 2 0 Reversible 1 1 Heating only 2 9...

Page 296: ...0 Continuous 1 Sample 2 Request 9 I F 0E R W 10 35 kW step 1kW 20 kW Bi zone kit settings 9 P 1 E 0B R W 0 not installed 1 2 Bizone kit installed 9 P 2 E 0C R W 0 Without hydraulic separator no direc...

Page 297: ......

Page 298: ......

Page 299: ......

Page 300: ...4P678716 1 2022 01 Copyright 2021 Daikin 4P678716 1 0000000X Verantwortung f r Energie und Umwelt...

Reviews: