2/9
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Room
└─ Antifrost
1.4.1
[2-06]
R/W
0: Disabled
1: Enabled
1.4.2
[2-05]
R/W
4~16°C, step: 1°C
16°C
└─ Setpoint range
1.5.1
[3-07]
R/W
12~18°C, step: 0,5°C
12°C
1.5.2
[3-06]
R/W
18~30°C, step: 0,5°C
30°C
Room
1.6
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
1.7
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
Main zone
2.4
0: Fixed
2: Weather dependent
└─ Heating WD curve
2.5
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
2.5
[1-01]
R/W
10~25°C, step: 1°C
15°C
2.5
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
2.5
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
Main zone
2.7
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
2.8.1
[9-01]
R/W
15~37°C, step: 1°C
25°C
2.8.2
[9-00]
R/W
[2-0C]=2:
37~65, step: 1°C
55°C
[2-0C]≠2:
37~55, step: 1°C
55°C
Main zone
2.9
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
2.A
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
└─ Delta T
2.B.1
[1-0B]
R/W
3~10°C, step: 1°C
5°C
└─ Modulation
2.C.1
[8-05]
R/W
0: No
1: Yes
2.C.2
[8-06]
R/W
0~10°C, step: 1°C
5°C
└─ Shut off valve
2.D.1
[F-0B]
R/W
0: No
1: Yes
Additional zone
3.4
0: Fixed
2: Weather dependent
└─ Heating WD curve
3.5
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
3.5
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
50°C
3.5
[0-02]
R/W
10~25°C, step: 1°C
15°C
3.5
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~65, step: 1°C
55°C
[2-0D]≠2:
37~55, step: 1°C
55°C
Additional zone
3.A
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1
[1-0C]
R/W
3~10°C, step: 1°C
5°C
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
22°C
Space heating / cooling
4.4
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/O
1: Heating only
Setpoint mode
Installer setting at variance with
default value
Emitter type
Heating minimum
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Activation
Room sensor offset
Room sensor offset
Room setpoint
Heating minimum
Space heating OFF temp
Number of zones
Thermostat type
Delta T heating
During thermo
Thermostat type
Emitter type
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
Delta T heating
Field settings table
High ambient temp. for LWT main zone heating WD curve.
Modulation
Max modulation
Heating minimum
Heating maximum
Setpoint mode
Low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Control
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Heating maximum
Heating maximum
Low ambient temp. for LWT main zone heating WD curve.
Unit type
Pump operation mode
4P499575-1A - 2017.11