background image

6 Preparation

Installer reference guide

23

ERGA04~08DAV3(A) + 08S18+23DA
Daikin Altherma – Low temperature split
4P495249-1 – 2017.12

▪ The required pre-pressure is:

Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar=0.3 bar.

▪ The  corresponding  maximum  water  volume  at  0.3  bar  is  290  l.

(See the graph in the chapter above).

▪ Because  250  l  is  lower  than  290  l,  the  expansion  vessel  is

appropriate for the installation.

6.5

Preparing electrical wiring

6.5.1

About preparing electrical wiring

INFORMATION

Also  read  the  precautions  and  requirements  in  the
"General safety precautions" chapter.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on  the  site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

6.5.2

About preferential kWh rate power supply

Electricity  companies  throughout  the  world  work  hard  to  provide
reliable  electric  service  at  competitive  prices  and  are  often
authorized  to  bill  clients  at  benefit  rates.  E.g.  time-of-use  rates,
seasonal rates, Wärmepumpentarif in Germany and Austria, ...

This  equipment  allows  for  connection  to  such  preferential  kWh  rate
power supply delivery systems.

Consult  with  the  electricity  company  acting  as  provider  at  the  site
where  this  equipment  is  to  be  installed  to  know  whether  it  is
appropriate to connect the equipment in one of the preferential kWh
rate power supply delivery systems available, if any.

When  the  equipment  is  connected  to  such  preferential  kWh  rate
power supply, the electricity company is allowed to:

▪ interrupt power supply to the equipment for certain periods of time;

▪ demand  that  the  equipment  only  consumes  a  limited  amount  of

electricity during certain periods of time.

The  indoor  unit  is  designed  to  receive  an  input  signal  by  which  the
unit switches into forced off mode. At that moment, the outdoor unit
compressor will not operate.

Whether the power supply is interrupted or not, the wiring to the unit
is different.

6.5.3

Overview of electrical connections except
external actuators

Normal power

supply

Preferential kWh rate power supply

Power supply is
NOT interrupted

Power supply is

interrupted

1

580

1 50

0

0

2

a

3

1

4

580

1 50

0

0

2

b

3

During preferential
kWh rate power
supply activation,
power supply is NOT
interrupted. The
outdoor unit is turned
off by the control.

Remark:

 The

electricity company
must always allow the
power consumption
of the indoor unit.

5 3

a

b

1

4

580

1 50

0

0

580

1 50

0

0

2

During preferential
kWh rate power
supply activation,
power supply is
interrupted
immediately or after
some time by the
electricity company.
In this case, the
indoor unit must be
powered by a
separate normal
power supply.

a

Normal power supply

b

Preferential kWh rate power supply

1

Power supply for outdoor unit

2

Power supply and interconnection cable to indoor unit

3

Power supply for backup heater

4

Preferential kWh rate power supply (voltage free contact)

5

Normal kWh rate power supply (to power the indoor unit
PCB in the event of power supply interruption of the
preferential kWh rate power supply)

6.5.4

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Outdoor unit and indoor unit power supply

1

Power supply for
outdoor unit

2+GND

(a)

2

Power supply and
interconnection cable to
indoor unit

3

(f)

3

Power supply for
backup heater

See table below. —

4

Preferential kWh rate
power supply (voltage
free contact)

2

(d)

5

Normal kWh rate power
supply

2

6.3 A

Summary of Contents for ERGA06DAV3

Page 1: ...aikin Altherma Low temperature split English Installer reference guide Daikin Altherma Low temperature split ERGA04DAV3 A ERGA06DAV3 A ERGA08DAV3 A EHVZ04S18DA6V G EHVZ08S18DA6V G EHVZ08S23DA6V G EHVZ...

Page 2: ...he expansion vessel pre pressure 21 6 4 3 To check the water volume and flow rate 21 6 4 4 Changing the pre pressure of the expansion vessel 22 6 4 5 To check the water volume Examples 22 6 5 Preparin...

Page 3: ...74 11 3 Checklist for yearly maintenance of the outdoor unit 74 11 4 Checklist for yearly maintenance of the indoor unit 74 11 4 1 To drain the domestic hot water tank 75 11 5 About cleaning the wate...

Page 4: ...revent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminiu...

Page 5: ...efer to the nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require...

Page 6: ...ble with the inverter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do NOT connect wiring of differ...

Page 7: ...e the system after it is installed Commissioning What to do and know to commission the system after it is configured Hand over to the user What to give and explain to the user Maintenance and service...

Page 8: ...bel d Energy label e Unit mounting plate f Bolts nuts washers spring washers and wire clamp 3 3 Indoor unit 3 3 1 To unpack the indoor unit 1 2 8 3 3 2 To remove the accessories from the indoor unit 4...

Page 9: ...ain pan heater EKDPH008CA The drain pan heater is required to avoid freezing up of the drain pan It is recommended to install this option in colder regions with possible low ambient temperatures or he...

Page 10: ...lation manual of the heat pump convectors and the addendum book for optional equipment LAN adapter for smartphone control Smart Grid applications BRP069A61 You can install this LAN adapter to Control...

Page 11: ...eld supply FHL1 3 Floor heating loops field supply For the main zone the room temperature is controlled by the user interface which is used as room thermostat optional equipment EKRUDAS For the additi...

Page 12: ...100 l 1 150 l 3 10 l 480 l Determining the volume and desired temperature for the DHW tank Formula Example V1 V2 V2 T2 40 40 T1 If V2 180 l T2 54 C T1 15 C Then V1 280 l V1 DHW consumption equivalent...

Page 13: ...ontrol DHW pump operation For more information see 8 Configuration on page 42 5 4 Setting up the energy metering Via the user interface you can read out the following energy data Produced heat Consume...

Page 14: ...ent The electrical meter cannot easily be installed in the electrical cabinet 230 V and 400 V three phase grids are combined very uncommon because of technical limitations of power meters Connection a...

Page 15: ...DI Digital inputs power limitation levels a Power limitation active b Actual power input Setup Demand PCB option EKRP1AHTA needed Maximum four digital inputs are used to activate the corresponding po...

Page 16: ...his chapter describes what you have to do and know before going on site It contains information about Preparing the installation site Preparing the refrigerant piping Preparing the water piping Prepar...

Page 17: ...oling mode 10 43 C Heating mode 25 25 C 6 2 2 Additional installation site requirements of the outdoor unit in cold climates In areas with low ambient temperatures and high humidity or in areas with h...

Page 18: ...off or cause water leakage Sound sensitive areas e g near a bedroom so that the operation noise will cause no trouble In places with high humidity max RH 85 for example a bathroom In places where fros...

Page 19: ...r dealer Use table 3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation...

Page 20: ...when connecting the piping Deformation of the piping can cause malfunctioning of the unit Connecting piping Tools Only use appropriate tooling to handle brass which is a soft material If NOT pipes wil...

Page 21: ...nstallation Immediately after installation the domestic hot water tank must be flushed with fresh water This procedure must be repeated at least once a day the first 5 consecutive days after installat...

Page 22: ...est point of the installation the installation height is 0 m Minimum flow rate Check that the minimum flow rate in the installation is guaranteed in all conditions on each zone separately This minimum...

Page 23: ...tial kWh rate power supply delivery systems Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the...

Page 24: ...up heater type Power supply Required number of conductors 6V 1N 230 V 2 GND 3 230 V 3 GND 9W 3N 400 V 4 GND 7 Installation 7 1 Overview Installation This chapter describes what you have to do and know...

Page 25: ...To lower the switch box on the indoor unit on page 25 7 8 5 To connect the drain hose to the drain on page 35 When you need access to the high voltage switch box 2 T25 7 2 4 To open the switch box cov...

Page 26: ...irements in the following chapters General safety precautions Preparation 7 3 3 To provide the installation structure Check the strength and level of the installation ground so that the unit will not...

Page 27: ...08D option kit c Anti vibration rubber field supply 7 3 4 To install the outdoor unit CAUTION Do NOT remove the protective cardboard before the unit is installed properly 1 Lift the outdoor unit as de...

Page 28: ...n pan You can use the drain pan option EKDP008D to gather the drain water For the complete installation instructions see the installation manual of the drain pan In short the drain pan must be install...

Page 29: ...onnecting the refrigerant piping to the outdoor unit Connecting the refrigerant piping to the indoor unit Insulating the refrigerant piping Keeping in mind the guidelines for Pipe bending Flaring pipe...

Page 30: ...e nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position as shown in the following figure A Flare tool for R32 clutch type Conventional flare tool Clutc...

Page 31: ...handling the stop valve tighten the stem cap and check for refrigerant leaks Item Tightening torque N m Stem cap liquid side 13 5 16 5 Stem cap gas side 22 5 27 5 To handle the service cap ALWAYS use...

Page 32: ...to the service port of the gas stop valve Make sure that the gas stop valve and liquid stop valve are firmly closed before performing the leak test or vacuum drying 7 6 3 To check for leaks NOTICE Do...

Page 33: ...refrigerant typically consists of the following stages 1 Determining how much refrigerant to charge 2 Charging refrigerant 3 Filling in the fluorinated greenhouse gases label and fixing it to the ins...

Page 34: ...safety precautions Preparation 7 8 3 To connect the water piping NOTICE Do NOT use excessive force when connecting the piping Deformation of the piping can cause malfunctioning of the unit To facilit...

Page 35: ...e inside the tank can rise above the tank design pressure Also the field installation piping tapping points etc connected to the tank is subjected to this high pressure To prevent this a pressure reli...

Page 36: ...sure the power supply system complies with the electrical specifications of the heat pump 2 Connecting the electrical wiring to the indoor unit 3 Connecting the main power supply 4 Connecting the remo...

Page 37: ...of 1 5 mm and applicable for 230 V Recommended field fuse 20 A 25 A 16 A Earth leakage circuit breaker Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum...

Page 38: ...type and installed options a Low voltage Preferential power supply contact User interface used as room thermostat option Power consumption digital inputs field supply Outdoor ambient temperature senso...

Page 39: ...gislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model M...

Page 40: ...ontrol cable to the appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normal closed valve and a NO normal open valve X1M X2M X1M X2M NO M2S NC M2S 21 28 21 2...

Page 41: ...to the cable tie mountings 7 9 15 To connect the changeover to external heat source 1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration be...

Page 42: ...the refrigerant piping and interconnection cable as follows f b a e d c a Gas pipe b Gas pipe insulation c Interconnection cable d Liquid pipe e Liquid pipe insulation f Finishing tape 2 Install the...

Page 43: ...change the user permission level on page 43 2 Go to 9 I Installer settings Overview field settings 3 Turn the left dial to select the first part of the setting and confirm by pressing the dial 00 01...

Page 44: ...18 Feb 2018 22 19 55 18 21 45 f i j h g e d a b c Possible actions on this screen Go through the list of the main menu Go to the main menu screen Enable disable breadcrumbs Item Description 21 21 The...

Page 45: ...ation mode on heating only models Tank Restriction Only displayed if a domestic hot water tank is present Set the domestic hot water tank temperature User settings Gives access to user settings such a...

Page 46: ...omestic hot water tank 8 3 8 Schedule screen Example This example shows how to set a room temperature schedule in heating mode for the main zone INFORMATION The procedures to program other schedules a...

Page 47: ...ORMATION Not all schedules can be renamed 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select the Rename option Delete Rename 3 Browse through the character l...

Page 48: ...or temperature drops below 4 C The unit will supply leaving water to the heat emitters to heat up the room again and the leaving water temperature setpoint will be lowered If Then Space heating coolin...

Page 49: ...n warmer water and vice versa During weather dependent operation the user has the possibility to shift the water temperature up or down by a maximum of 10 C Heating WD curve Set weather dependent heat...

Page 50: ...nd if the high emitter system leaving water setpoint is chosen bigger than 60 C in the complete operation range there can be an increased power consumption NOTICE When adjusting the leaving water temp...

Page 51: ...special cases the measured delta T can be different from the set value INFORMATION When only the backup heater is active in heating delta T will be controlled according to the fixed capacity of the ba...

Page 52: ...t the shut off valve to the heating cooling output The shut off valve for the main leaving water temperature zone can close under these circumstances INFORMATION During defrost operation the shut off...

Page 53: ...ater temperature zone with the highest leaving water temperature in heating operation 3 8 1 9 05 Heating minimum 15 C 37 C Code Description 3 8 2 9 06 Heating maximum 2 0D 2 emitter type additional zo...

Page 54: ...ter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter Pump operation mode When the space heating operation is OFF the pump is always OFF Wh...

Page 55: ...nd comfort are NOT guaranteed 5 8 Limitation when no actuators When there is no heating output the pump speed limitation is applicable When there is heating output the pump speed is only determined by...

Page 56: ...g the schedule you can make use of the comfort setpoint as a preset value When you later want to change the storage setpoint you only have to do it in one place The tank will heat up until the storage...

Page 57: ...ast 4 hours later than the last expected large hot water tapping This start up can be set by installer settings disinfection function When the Domestic hot water Type Scheduled only is selected it is...

Page 58: ...when the outdoor temperature equals or rises above the high ambient temperature 35 C 6 0E C Margin In domestic hot water operation the following hysteresis value can be set for the heat pump operatio...

Page 59: ...quiet mode is active To use quiet mode 1 Go to 7 4 1 User settings Quiet Activation 2 Do one of the following If you want to Then Completely deactivate quiet mode Select Off If you want to Then Manual...

Page 60: ...ve kWh 0 9 Gas price 4 08 5 0 9 Gas price 8 58 Calculation of the electricity price Electricity price Actual electricity price Incentive kWh Electricity price 12 49 5 Electricity price 17 49 Price Val...

Page 61: ...nterface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Voltage For a 3V model this is fixed to 230V 1ph For a 6V model...

Page 62: ...ection function the underfloor heating screed dryout function and the water pipe antifreeze function will remain active even if the user does NOT confirm emergency operation Balancing Priorities For s...

Page 63: ...ty thermostat for the additional zone It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone Code Description 9 8 1 D 01 Co...

Page 64: ...ooster heater can operate simultaneously 1 Booster heater The booster heater is prioritized 2 Backup heater The backup heater is prioritized Power consumption control ENABLED 4 08 1 2 0 None Depending...

Page 65: ...with an auxiliary boiler alternating operation connected in parallel The purpose of bivalent operation is to determine which heating source can will provide the space heating either the indoor unit o...

Page 66: ...ON Tcalc can never go below C 03 or above C 03 C 04 a Auxiliary boiler active b Auxiliary boiler inactive CAUTION Make sure to observe all rules mentioned in application guideline 5 when bivalent oper...

Page 67: ...ns set Disable protections to No 36 hours after the first power on the unit will automatically set Disable protections to No ending installer on site mode and enabling the protective functions If afte...

Page 68: ...y price Gas price C Operation Room Space heating cooling Tank B User profile 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price High Medium Low Schedule 7 2 Time date...

Page 69: ...pply Benefit kWh power supply Allow heater Allow pump 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limi...

Page 70: ...ose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B fie...

Page 71: ...and the domestic hot water heating mode Typical workflow Purging the air from the system should consist of 1 Performing a manual air purge 2 Performing an automatic air purge INFORMATION Start by perf...

Page 72: ...est 9 4 5 Underfloor heating screed dryout This function is used for drying out the screed of an underfloor heating system very slowly during the construction of a house It allows the installer to pro...

Page 73: ...ting screed dryout When the program is stopped by an error an operation switch off or a power failure the U3 error will be displayed on the user interface To resolve the error codes see 12 4 Solving p...

Page 74: ...nce of the magnetic filter dirt separator consists of Checking if both parts of the magnetic filter dirt separator are still screwed tight a Emptying the dirt separator as follows 1 Take off the magne...

Page 75: ...fic situations involving the domestic hot water tank please be aware that the domestic hot water tank is a stainless steel cylinder We recommend to use a non chloride based disinfectant approved for u...

Page 76: ...se of severe issues Preferably this action is never to be done during the complete lifetime of the water filter a b a Bottom part to be unscrewed b Water filter housing 3 Remove the strainer and the r...

Page 77: ...ntroller Refer to the operation manual Possible causes Corrective action The water flow is too low Check and make sure that All shut off valves of the water circuit are completely open The water filte...

Page 78: ...the difference in height between the indoor unit and the highest point of the water circuit If the indoor unit is located at the highest point of the installation the installation height is considere...

Page 79: ...edule only is selected it is recommended to program a Eco action 3 hours before the scheduled start up of the disinfection function to preheat the tank The disinfection operation was stopped manually...

Page 80: ...will reset automatically and the unit will resume operation INFORMATION Error AJ 03 is reset automatically from the moment there is a normal tank heat up INFORMATION How an error code can be reset wi...

Page 81: ...hat the unit s compressor does NOT have to operate NOTICE During pump down operation stop the compressor before removing the refrigerant piping If the compressor is still running and the stop valve is...

Page 82: ...1 2017 12 11 Reattach the service PCB cover and switch box cover and turn the power back ON NOTICE Take care that while running forced cooling operation the water temperature remains higher than 5 C...

Page 83: ...uT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 15 9 CuT 3D110394 9 5 CuT 12 7 CuT 15 9 CuT 6 4 CuT S1PH Y1E R1T R3T M1C Y1S 4 0 CuT M1F b a c d e f g h i j k k g g a Field piping liquid 6 4 mm fla...

Page 84: ...IN heating mode condenser d2 Liquid refrigerant OUT heating mode condenser e Plate heat exchanger f Shut off valve for service if equipped g Expansion vessel h Magnetic filter dirt separator i Safety...

Page 85: ...white GRN green YLW yellow 3 Legend AL Connector C Capacitor DB Rectifier bridge DC Connector DP Connector E Connector F1U Fuse T 6 3 A 250 V FU1 FU2 Fuse T 3 15 A 250 V FU3 Fuse T 30 A 250 V H Connec...

Page 86: ...F thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box Engli...

Page 87: ...e user interface used as room thermostat EKRUDAS 5 Ext thermistor 5 External thermistor SWB Switch box English Translation 6 Field supplied options 6 Field supplied options 12 V DC pulse detection vol...

Page 88: ...2 core 3m included signal A13P P1 P2 LAN adapter A14P P1 P2 user interface communication 2 core communication 2 core 2 core 5 core for C H operation 4 core for H only operation 3 core for C H operatio...

Page 89: ...81 1 86 29 44 1 88 30 08 1 90 30 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc...

Page 90: ...s owner of the product and or operates the product Applicable legislation All international European national and local directives laws regulations and or codes that are relevant and applicable for a...

Page 91: ...1 9 Field settings table 8 7 5 7401 Applicable indoor units EHVZ04S18DA6V EHVZ08S18DA6V EHVZ08S18DA9W EHVZ08S23DA6V EHVZ08S23DA9W Notes 1 3V 2 6V 3 9W 4P495259 1A 2017 11...

Page 92: ...ncoil unit 2 Radiator Setpoint range 3 8 1 9 05 R W 15 37 C step 1 C 25 C 3 8 2 9 06 R W 2 0D 2 37 65 step 1 C 55 C 2 0D 2 37 55 step 1 C 55 C Additional zone 3 A C 06 R W 0 1 1 contact 2 2 contacts D...

Page 93: ...2 20 C step 1 C 10 C 5 B R W 0 Fixed 1 Weather dependent WD curve 5 C 0 0B R W 35 6 0E C step 1 C 55 C 5 C 0 0C R W 45 6 0E C step 1 C 60 C 5 C 0 0D R W 10 25 C step 1 C 15 C 5 C 0 0E R W 40 5 C step...

Page 94: ...step 1 C 45 C 9 1 6 0C R W 30 min 50 6 0E C step 1 C 45 C Domestic hot water 9 2 1 E 05 E 06 E 07 R O 3 Integrated 9 2 2 D 02 R W 0 No 1 Secondary rtrn 2 Disinf Shunt 9 2 4 D 07 R W 0 No 1 Yes Back up...

Page 95: ...50 A 9 9 4 5 05 R W 0 50 A step 1 A 50 A 9 9 5 5 06 R W 0 50 A step 1 A 50 A 9 9 6 5 07 R W 0 50 A step 1 A 50 A 9 9 7 5 08 R W 0 50 A step 1 A 50 A 9 9 8 5 09 R W 0 20 kW step 0 5 kW 20 kW 9 9 9 5 09...

Page 96: ...R W 5 5 C step 0 5 C 0 C 9 I 2 0C R W 0 Underfloor heating 1 Fancoil unit 2 Radiator 9 I 2 0D R W 0 Underfloor heating 1 Fancoil unit 2 Radiator What is the desired delta T in heating for the main zo...

Page 97: ...6 0E C step 1 C 60 C 9 I 6 0B R W 30 min 50 6 0E C step 1 C 45 C 9 I 6 0C R W 30 min 50 6 0E C step 1 C 45 C 9 I 6 0D R W 0 Reheat only 1 Reheat sched 2 Scheduled only Is auto restart of the unit allo...

Page 98: ...Room sensor 9 I C 09 R W 0 Normally open 1 Normally closed 9 I C 0A 0 9 I D 00 R W 0 None 1 BSH only 2 BUH only 3 All heaters 9 I D 01 R W 0 No 1 Active open 2 Active closed 3 Safety thermostat Contac...

Page 99: ...ep 1 C 5 C 9 I F 04 R W 0 No 1 Yes 9 I F 05 0 9 I F 09 R W 0 Disabled 1 Enabled 9 I F 0A 0 9 I F 0B R W 0 No 1 Yes 9 I F 0C 1 9 I F 0D R W 0 Continuous 1 Sample 2 Request What is the pump operation mo...

Page 100: ...4P495249 1 2017 12 Copyright 2017 Daikin...

Reviews: