background image

14 Technical data

Installer reference guide

95

ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA
Daikin Altherma – Low temperature split
4P495248-1 – 2017.12

14.5

Table 1 – Maximum refrigerant
charge allowed in a room: indoor
unit

A

room

 (m

2

)

Maximum refrigerant charge in a room

(m

max

) (kg)

H=600 mm

1

0.138

2

0.276

3

0.414

4

0.553

5

0.691

6

0.829

7

0.907

8

0.970

9

1.028

10

1.084

11

1.137

12

1.187

13

1.236

14

1.283

15

1.328

16

1.371

17

1.413

18

1.454

19

1.494

20

1.533

21

1.571

22

1.608

23

1.644

24

1.679

25

1.714

26

1.748

27

1.781

28

1.814

29

1.846

30

1.877

31

1.909

INFORMATION

▪ For  floorstanding  models,  the  value  of  "Installation

height  (H)"  is  considered  600  mm  to  comply  to
IEC 60335-2-40:2013 A1 2016 Clause GG2.

▪ For  intermediate  A

room

  values  (i.e.  when  A

room

  is

between two values from the table), consider the value
that corresponds to the lower A

room

 value from the table.

If A

room

=12.5 m

2

, consider the value that corresponds to

"A

room

=12 m

2

".

14.6

Table 2 – Minimum floor area:
indoor unit

m

c

 (kg)

Minimum floor area (m²)

H=600 mm

1.84

28.81

1.86

29.44

1.88

30.08

1.90

30.72

INFORMATION

▪ For  floorstanding  models,  the  value  of  "Installation

height  (H)"  is  considered  600  mm  to  comply  to
IEC 60335-2-40:2013 A1 2016 Clause GG2.

▪ For  intermediate  m

c

  values  (i.e.  when  m

c

  is  between

two  values  from  the  table),  consider  the  value  that
corresponds  to  the  higher  m

c

  value  from  the  table.  If

m

c

=1.87  kg,  consider  the  value  that  corresponds  to

"m

c

=1.88 kg".

▪ Systems  with  total  refrigerant  charge  lower  than

1.84 kg are not subjected to any room requirements.

▪ Charges above 1.9 kg are not allowed in the unit.

14.7

Table 3 – Minimum venting
opening area for natural
ventilation: indoor unit

m

c

m

max

dm=m

c

–m

max

 (kg) Minimum venting opening area

(cm

2

)

H=600 mm

1.9

0.1

1.80

729

1.9

0.3

1.60

648

1.9

0.5

1.40

567

1.9

0.7

1.20

486

1.9

0.9

1.00

418

1.9

1.1

0.80

370

1.9

1.3

0.60

301

1.9

1.5

0.40

216

1.9

1.7

0.20

115

INFORMATION

▪ For  floorstanding  models,  the  value  of  "Installation

height  (H)"  is  considered  600  mm  to  comply  to
IEC 60335-2-40:2013 A1 2016 Clause GG2.

▪ For  intermediate  dm  values  (i.e.  when  dm  is  between

two  dm  values  from  the  table),  consider  the  value  that
corresponds  to  the  higher  dm  value  from  the  table.  If
dm=1.55  kg,  consider  the  value  that  corresponds  to
"dm=1.6 kg".

Final English - Tanslations in progress

Summary of Contents for ERGA04DAV3A

Page 1: ...temperature split ERGA04DAV3 A ERGA06DAV3 A ERGA08DAV3 A EHVH04S18DA6V G EHVH04S23DA6V G EHVH08S18DA6V G EHVH08S23DA6V G EHVH08S18DA9W G EHVH08S23DA9W G EHVX04S18DA3V G EHVX04S18DA6V G EHVX04S23DA3V G...

Page 2: ...Refrigerant piping insulation 25 6 4 Preparing water piping 25 6 4 1 Water circuit requirements 25 6 4 2 Formula to calculate the expansion vessel pre pressure 26 6 4 3 To check the water volume and f...

Page 3: ...10 Hand over to the user 80 11 Maintenance and service 80 11 1 Overview Maintenance and service 80 11 2 Maintenance safety precautions 80 11 3 Checklist for yearly maintenance of the outdoor unit 80...

Page 4: ...al temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small...

Page 5: ...arged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory c...

Page 6: ...ter resistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do NOT connect wiring of different thicknesses to...

Page 7: ...it is installed Commissioning What to do and know to commission the system after it is configured Hand over to the user What to give and explain to the user Maintenance and service How to maintain an...

Page 8: ...e Unit mounting plate f Bolts nuts washers spring washers and wire clamp 3 3 Indoor unit 3 3 1 To unpack the indoor unit 1 2 8 3 3 2 To remove the accessories from the indoor unit 2 4 1 4 1 1 1 1 1 a...

Page 9: ...EKDPH008CA The drain pan heater is required to avoid freezing up of the drain pan It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfall F...

Page 10: ...p convectors FWXV For installation instructions refer to the installation manual of the heat pump convectors and the addendum book for optional equipment LAN adapter for smartphone control Smart Grid...

Page 11: ...efficiency Lowest possible leaving water temperature higher efficiency Easy You can easily set the desired room temperature via the user interface For your daily needs you can use preset values and s...

Page 12: ...o prevent condensation on the floor during cooling operation The desired room temperature is set via the remote controller of the heat pump convectors The space heating cooling demand signal is sent t...

Page 13: ...at the operation mode on each room thermostat must be set to match the indoor unit The room thermostats are connected to the shut off valves but do NOT have to be connected to the indoor unit The indo...

Page 14: ...the heat emitters selected for each room are designed for different leaving water temperatures you can use different leaving water temperature zones maximum 2 In this document Main zone Zone with the...

Page 15: ...he desired leaving water temperature based on the actual room temperature modulation The combination of the two heat emitter systems provides the excellent heating comfort of the under floor heating a...

Page 16: ...system on page 10 The auxiliary contact can be An outdoor temperature thermostat An electricity tariff contact A manually operated contact Setup Connect the following field wiring L N H Com A K2A K1A...

Page 17: ...k during the day If energy prices are lower during the night Daikin recommends to heat up the DHW tank during the night When the heat pump produces domestic hot water it cannot heat up a space In case...

Page 18: ...ally based on The actual power input of the outdoor unit The set capacity of the backup heater The voltage Setup and configuration To get accurate energy data measure the capacity resistance measureme...

Page 19: ...tdoor unit L1 N h Indoor unit L1 N i Backup heater L1 L2 L3 N 5 6 Setting up the power consumption control The power consumption control Allows you to limit the power consumption of the entire system...

Page 20: ...unit operation c Backup heater step 1 turned ON 5 7 Setting up an external temperature sensor You can connect one external temperature sensor It can measure the indoor or outdoor ambient temperature...

Page 21: ...celeration in heating operation disruption of operation due to decrease of low pressure or increase of high pressure a broken fan if a strong wind blows continuously on the fan it may start rotating v...

Page 22: ...pter The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 3...

Page 23: ...and have a room size as specified below NOTICE Do NOT re use joints which have been used already Joints made in installation between parts of refrigerant system shall be accessible for maintenance pu...

Page 24: ...3 in chapter Technical data and dm to calculate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings permanen...

Page 25: ...e piping Deformation of the piping can cause malfunctioning of the unit Connecting piping Tools Only use appropriate tooling to handle brass which is a soft material If NOT pipes will get damaged Conn...

Page 26: ...Immediately after installation the domestic hot water tank must be flushed with fresh water This procedure must be repeated at least once a day the first 5 consecutive days after installation Domestic...

Page 27: ...s required during defrost backup heater operation For this purpose use the overpressure bypass valve delivered with the unit NOTICE When circulation in each or certain space heating loops is controlle...

Page 28: ...nt is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available if any When the equipment is connected to s...

Page 29: ...pically consists of the following stages 1 Mounting the outdoor unit 2 Mounting the indoor unit 3 Connecting the refrigerant piping 4 Checking the refrigerant piping 5 Charging refrigerant 6 Connectin...

Page 30: ...o open the switch box cover of the indoor unit 4 T25 4 T25 7 2 5 To lower the switch box on the indoor unit During the installation you will need access to the inside of the indoor unit To have easier...

Page 31: ...that the unit will not cause any operating vibration or noise Fix the unit securely by means of foundation bolts in accordance with the foundation drawing This topic shows different installation struc...

Page 32: ...t 7 3 5 To provide drainage Make sure that condensation water can be evacuated properly Install the unit on a base to make sure that there is proper drainage in order to avoid ice accumulation Prepare...

Page 33: ...er sheet between the cables and the outdoor unit to prevent the cable from scratching the paint field supply 4 Attach the cable s ends Tighten those ends 7 4 Mounting the indoor unit 7 4 1 About mount...

Page 34: ...e g air Only use R32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used for R32 installations to withstand the pressure and to prevent foreign materi...

Page 35: ...the inside of the piping This film adversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can...

Page 36: ...t piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 7 5 9 To connect the refrigerant piping to the indoor unit 1 Connect the liq...

Page 37: ...ssurize to 3000 kPa 30 bar in order to detect small leaks 2 Check for leaks by applying the bubble test solution to all connections 3 Discharge all nitrogen gas 7 6 4 To perform vacuum drying Connect...

Page 38: ...igerant 10 m R total length m of liquid piping 10 m 0 020 R Additional charge kg rounded in units of 0 1 kg INFORMATION Piping length is the one way length of liquid piping 7 7 4 To determine the comp...

Page 39: ...o install the overpressure bypass valve in the space heating water circuit Mind the minimum flow rate when adjusting the overpressure bypass valve setting See 6 4 3 To check the water volume and flow...

Page 40: ...field supply filling kit Make sure you comply with the applicable legislation INFORMATION Make sure both air purge valves one on the magnetic filter and one on the backup heater are open 7 8 7 To fil...

Page 41: ...requirements in the following chapters General safety precautions Preparation DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables 7 9 4 Guidelines when connecting...

Page 42: ...cessory to the screw of the refrigerant piping cover and fix the cables to it with a cable tie 1 1 6 Connect an earth leakage circuit breaker and fuse to the power supply line 7 9 7 To connect the ele...

Page 43: ...ut low voltage cables With low voltage cables 7 9 8 To connect the main power supply 1 Connect the main power supply In case of normal kWh rate power supply X1M X2M X5M X11YB X1A X11Y X11YA 1 2 3 1 2...

Page 44: ...lic low voltage systems with input current 16 A and 75 A per phase b This equipment complies with EN IEC 61000 3 11 European International Technical Standard setting the limits for voltage changes vol...

Page 45: ...lectrical meters INFORMATION In case of an electrical meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M...

Page 46: ...ed 2 Fix the cable with cable ties to the cable tie mountings 7 9 17 To connect the safety thermostat normal closed contact 1 Connect the safety thermostat normal closed cable to the appropriate termi...

Page 47: ...e configuration in the menu structure or the overview settings INFORMATION When the configuration wizard is finished the user interface will show an overview screen and request to confirm When confirm...

Page 48: ...menu structure if required You can find a short overview of the settings in the configuration here All the settings can also be adjusted in the settings menu use the breadcrumbs For the setting Refer...

Page 49: ...ature Item Description Additional zone h3 h1 h2 h1 Heat emitter type Underfloor heating Fancoil unit Radiator h2 Leaving water temperature setpoint h3 Room thermostat type External control Hidden Leav...

Page 50: ...by the unit b2 Restricted by the installer Current temperature c Measured by the unit Desired temperature d Turn the right dial to increase decrease Submenu e Turn or press the left dial to go to the...

Page 51: ...aturday and copy it to Sunday 6 Give the schedule a name To go to the schedule 1 Go to 1 1 Room Schedule 2 Set scheduling to Yes 3 Go to 1 2 Room Heating schedule To clear the contents of the schedule...

Page 52: ...perature is controlled with a schedule or not Code Description 1 1 N A Schedule 0 No Room temperature is controlled by the user 1 Yes Room temperature is controlled with a schedule and can be modified...

Page 53: ...ifrost temperature 2 05 the unit will supply leaving water to the heat emitters to heat up the room again Code Description 1 4 1 2 06 Activation 0 No Antifrost functionality is OFF 1 Yes Antifrost fun...

Page 54: ...eating fixed cooling 2 Weather dependent When weather dependent operation is active low outdoor temperatures will result in warmer water and vice versa During weather dependent operation the user has...

Page 55: ...nes CAUTION If there are 2 zones it is important that the zone with the lowest water temperature is configured as the main zone and the zone with the highest water temperature is configured as the add...

Page 56: ...used external room thermostat can send a separate heating cooling thermo ON OFF condition The room thermostat is connected to 2 digital inputs X2M 35 and X2M 34 Select this value in case of a connect...

Page 57: ...nly be read out on the user interface 2 C 2 8 06 Max modulation 0 C 10 C This is the temperature value by which the desired leaving water temperature is increased or decreased INFORMATION When leaving...

Page 58: ...nal zone can be independently set from the setpoint mode of the main zone see Main zone on page 54 Code Description 3 4 N A Setpoint mode 0 Fixed 1 WD heating fixed cooling 2 Weather dependent Heating...

Page 59: ...ter temperature in cooling operation 3 8 1 9 05 Heating minimum 15 C 37 C Code Description 3 8 2 9 06 Heating maximum 2 0D 2 emitter type additional zone radiator 37 C 65 C Else 37 C 55 C 3 8 3 9 07 C...

Page 60: ...rmined by the Space heating off temperature and the Space cooling off temperature If the outdoor temperature drops the operation mode will switch to cooling and vice versa The outdoor temperature is t...

Page 61: ...emitters CAUTION If there are 2 zones and the emitter types are wrongly configured water of high temperature can be sent towards a low temperature emitter underfloor heating To avoid this Install an...

Page 62: ...is heating output the pump speed is only determined by delta T in relation to the required capacity With this limitation range delta T is possible and the comfort is guaranteed The maximum values dep...

Page 63: ...e risk of space heating cooling and capacity shortage comfort problems is significant In case of frequent domestic hot water operation frequent and long space heating cooling interruptions will happen...

Page 64: ...t maximum value This maximum allowable hot water temperature shall be selected according to the applicable legislation CAUTION Be sure that the disinfection function start time 5 7 3 with defined dura...

Page 65: ...cording to the weather dependent curve During weather dependent operation the end user cannot adjust the desired tank temperature on the user interface Also see 8 3 7 Detailed screen with weather depe...

Page 66: ...de To check if holiday mode is activated and or running If is activated on the home screen holiday mode is active To configure the holiday 1 Activate the holiday mode Go to 7 3 1 User settings Holiday...

Page 67: ...prices Although the running cost can increase the total operation cost taking into account the reimbursement will be optimized NOTICE Make sure to modify the setting of the energy prices at the end o...

Page 68: ...Tank c Domestic hot water pump d Heater element e Non return valve f Shower g Cold water DHW pump schedule Here you can program a schedule for the DHW pump only for field supplied domestic hot water p...

Page 69: ...automatically or non automatically take over the heat load When auto emergency is set to Automatic and a heat pump failure occurs the backup heater will automatically take over the heat load and the d...

Page 70: ...ing time also depends on setting 8 04 When Control Room thermostat This preset value is only taken into account if there is a request for space heating or cooling If there is NO request for space heat...

Page 71: ...1 or indoor unit is connected to a normal kWh rate power supply via X2M 5 6 and the backup heater is NOT connected to the preferential kWh rate power supply 9 8 3 D 05 Allow pump 0 No Pump is forced o...

Page 72: ...kWh Installed 9 A 2 D 09 Electricity meter 2 0 None NOT installed 1 1 10kWh Installed 2 1 kWh Installed 3 10 kWh Installed 4 100 kWh Installed 5 1000 kWh Installed Sensors External sensor Code Descrip...

Page 73: ...in the menu structure Also set the following values NOTICE Do NOT use overview settings Code Description 9 C 3 C 03 Bivalent ON temperature Defines the outdoor temperature below which the permission s...

Page 74: ...g the indoor unit to a normal kWh rate power supply Code Description 9 E C 09 Auto restart 0 Manual 1 Automatic Disable protections INFORMATION The software is equipped with an installer on site mode...

Page 75: ...e Time date Holiday Quiet Electricity price Gas price C Operation Room Space heating cooling Tank B User profile 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule 7 5 Electricity price Hi...

Page 76: ...ower supply Allow heater Allow pump 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit...

Page 77: ...O loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B...

Page 78: ...ff Room Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the user permission level on page 47 2 Go to A 3 Commissioning Air purge 3 In the menu set T...

Page 79: ...ggered to start emergency operation the user interface will ask confirmation before starting The underfloor heating screed dryout function is active even if the user does NOT confirm emergency operati...

Page 80: ...o A 4 3 Commissioning UFH screed dryout Status 2 You can read out the value here Stopped at the step where the underfloor screed dryout was stopped 3 Modify and restart the execution of the program 10...

Page 81: ...move the water filter on page 82 11 5 2 To clean the water filter in case of trouble on page 82 11 5 3 To install the water filter on page 83 Water pressure relief valve Open the valve and check if it...

Page 82: ...water filter on page 82 11 5 2 To clean the water filter in case of trouble on page 82 11 5 3 To install the water filter on page 83 11 5 1 To remove the water filter Prerequisite Turn OFF the unit vi...

Page 83: ...pen the valve if equipped of the water circuit towards the expansion vessel CAUTION Make sure to open the valve if equipped towards the expansion vessel otherwise the overpressure will be generated 5...

Page 84: ...Symptom The compressor does NOT start space heating or domestic water heating Possible causes Corrective action The unit must start up out of its operation range the water temperature is too low If th...

Page 85: ...vated If it has check the following and then press the reset button in the switch box The water pressure Whether there is air in the system The air purge operation Possible causes Corrective action Th...

Page 86: ...is displayed on the screen 2 Press in the error screen Result A long description of the error is displayed on the screen 12 4 2 Error codes Overview Error codes of the outdoor unit Error code Detaile...

Page 87: ...ION In case of error code AH and no interruption of the disinfection function occurred due to domestic hot water tapping following actions are recommended When the Domestic hot water Type Reheat or Re...

Page 88: ...After 5 to 10 minutes after only 1 or 2 minutes in case of very low ambient temperatures 10 C close the liquid stop valve with a hexagonal wrench 5 Check on the manifold if the vacuum is reached 6 Aft...

Page 89: ...6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 15 9 CuT 3D110394 9 5 CuT 12 7 CuT 15 9 CuT 6 4 CuT S1PH Y1E R1T R3T M1C Y1S 4 0 CuT M1F b a c d e f g h i j k k g g a Field piping liquid 6 4 mm flare connection b Fi...

Page 90: ...OUT heating mode condenser d1 Liquid refrigerant IN cooling mode evaporator d2 Gas refrigerant OUT cooling mode evaporator e Plate heat exchanger f Shut off valve for service if equipped g Expansion...

Page 91: ...W yellow 3 Legend AL Connector C Capacitor DB Rectifier bridge DC Connector DP Connector E Connector F1U Fuse T 6 3 A 250 V FU1 FU2 Fuse T 3 15 A 250 V FU3 Fuse T 30 A 250 V H Connector IPM Intelligen...

Page 92: ...ss Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P On OFF th...

Page 93: ...voltage supplied by PCB 12 V DC pulse detection voltage supplied by PCB 230 V AC supplied by PCB 230 V AC supplied by PCB Continuous Continuous current English Translation DHW pump output Domestic ho...

Page 94: ...e signal 2 core signal signal 2 core 2 core 2 core signal 2 core 2 core External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only...

Page 95: ...30 08 1 90 30 72 INFORMATION For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when m...

Page 96: ...operates the product Applicable legislation All international European national and local directives laws regulations and or codes that are relevant and applicable for a certain product or domain Serv...

Page 97: ...HBH08DA6V EHBH08DA9W EHVX04S18DA3V EHVX04S18DA6V EHVX04S23DA3V EHVX04S23DA6V EHVX08S18DA6V EHVX08S18DA9W EHVX08S23DA6V EHVX08S23DA9W EHVH04S18DA6V EHVH04S23DA6V EHVH08S18DA6V EHVH08S18DA9W EHVH08S23DA...

Page 98: ...C step 1 C 15 C 3 5 0 03 R W 40 5 C step 1 C 10 C Cooling WD curve 3 6 0 04 R W 9 07 9 08 C step 1 C 8 C 3 6 0 05 R W 9 07 9 08 C step 1 C 12 C 3 6 0 06 R W 25 43 C step 1 C 35 C 3 6 0 07 R W 10 25 C...

Page 99: ...ed 1 Enabled Tank 5 2 6 0A R W 30 6 0E C step 1 C 60 C 5 3 6 0B R W 30 min 50 6 0E C step 1 C 45 C 5 4 6 0C R W 30 min 50 6 0E C step 1 C 45 C 5 6 6 0D R W 0 Reheat only 1 Reheat sched 2 Scheduled onl...

Page 100: ...tep 1 C 35 C 9 1 1 08 R W 9 03 9 02 C step 1 C 22 C 9 1 1 09 R W 9 03 9 02 C step 1 C 18 C Additional zone 9 1 2 0D R W 0 Underfloor heating 1 Fancoil unit 2 Radiator 9 1 R W 0 Fixed 1 WD heating fixe...

Page 101: ...anual 1 Automatic Balancing 9 6 1 5 02 R W 0 Disabled 1 Enabled 9 6 2 5 03 R W 15 35 C step 1 C 0 C 9 6 3 5 04 R W 0 20 C step 1 C 10 C 9 6 4 8 02 R W 0 10 hour step 0 5 hour 0 5 hour E 07 1 3 hour E...

Page 102: ...0 25 C step 1 C 15 C 9 I 0 03 R W 40 5 C step 1 C 10 C 9 I 0 04 R W 9 07 9 08 C step 1 C 8 C 9 I 0 05 R W 9 07 9 08 C step 1 C 12 C 9 I 0 06 R W 25 43 C step 1 C 35 C 9 I 0 07 R W 10 25 C step 1 C 20...

Page 103: ...ention What is the desired delta T in heating for the additional zone What is the desired delta T in heating for the main zone What is the desired delta T in cooling for the main zone What is the desi...

Page 104: ...95 min step 5 min 95 min 9 I 8 05 R W 0 No 1 Yes 9 I 8 06 R W 0 10 C step 1 C 5 C What is the capacity of the backup heater step 2 Space heating priority temperature Set point correction for domestic...

Page 105: ...kWh 2 1 pulse kWh 3 10 pulse kWh 4 100 pulse kWh 5 1000 pulse kWh 9 I D 09 R W 0 No 1 0 1 pulse kWh 2 1 pulse kWh 3 10 pulse kWh 4 100 pulse kWh 5 1000 pulse kWh What is the desired comfort main LWT...

Page 106: ...C R W 0 No 1 Yes 9 I F 0D R W 0 Continuous 1 Sample 2 Request Which type of unit is installed Which type of compressor is installed What is the indoor unit software type What is the number of backup h...

Page 107: ...Final English Tanslations in progress...

Page 108: ...4P495248 1 2017 12 Copyright 2017 Daikin Final English Tanslations in progress...

Reviews: