ER3~10DA
Air-cooled condensing units
4PW00410-1C

Installation manual

 

1

 

C

 

ONTENTS

 

Page

 

Introduction........................................................................................ 1

Technical specifications............................................................... 1
Electrical specifications ............................................................... 1
Options........................................................................................ 1

Main components .............................................................................. 1

Selection of location .......................................................................... 2

Inspecting and handling the unit........................................................ 2

Unpacking and placing the unit ......................................................... 2

Installation of the head pressure control kit ....................................... 2

Refrigerant piping .............................................................................. 2

Precautions when handling refrigerant piping ............................. 2
Connecting the refrigerant piping ................................................ 2
Leak test and vacuum drying of the refrigerant piping ................ 3
Refrigerant charge ...................................................................... 3
Piping insulation .......................................................................... 4

Field wiring ........................................................................................ 4

Parts table ................................................................................... 4
Power circuit and cable requirements ......................................... 4
CENELEC system for cable designation..................................... 4
Connection of the condensing unit power supply........................ 5
Interconnection cable .................................................................. 5

How to continue ................................................................................. 5

 

I

 

NTRODUCTION

 

The Daikin ER-DA air-cooled condensing units are designed for
outdoor installation and used for cooling applications only. The units
are available in 4 standard sizes with nominal cooling capacities
ranging from 8.3 to 26.6 kW.

The ER-DA condensing units can be combined with the Daikin EFD-F*
and EFV-JB split air-cooled air conditioners or any other type of air
conditioner equipped with a thermostatic expansion valve.

The present installation manual describes the procedures for
unpacking, installing and connecting the ER-DA units. Installation of
the EFD-F* or EFV-JB units is not described in this manual. Always
refer to the installation manual supplied with these units for their
installation.

 

Technical specifications 

 

(1)

 

Electrical specifications 

 

(1)

 

Options 

 

(1)

 

When the ER-DA unit is combined with one of the EFD air-cooled air
conditioners, the following options can be purchased to allow easier
installation:

 

M

 

AIN

 

 

 

COMPONENTS

 

 

 

(refer to 

figure 1

)

 

ER3DA
ER5DA
ER8DA
ER10DA

 

Air-cooled condensing units

 

Installation manual

 

IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR
ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-
CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT.
BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH
ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT
AND HAVE THEM INSTALLED BY A PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS
CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.

 

(1) Refer to the operation manual or engineering data book for the complete 

list of specifications and options.

 

Model

ER3DA

ER5DA

ER8DA

ER10DA

Dimensions HxWxD

 

(mm)

796x922x373

1179x922x373 1254x1390x373 1560x1390x373

 

Weight

 

(kg)

 

85

130

185

210

 

Connections:

 

- refrigerant gas inlet

(inch)

 

5/8 flare

7/8 OD

1 1/8 OD

1 1/8 OD

 

(mm)

 

15 flare

22 OD

28 OD

28 OD

 

- refrigerant liquid outlet

(inch)

 

3/8 flare

1/2 flare

5/8 flare

5/8 flare

 

(mm)

 

10 flare

12 flare

15 flare

15 flare

 

NOTE

 

In case of mm tubes: use flare connections according
to DIN8912.

 

ER3DA

ER5DA

ER8DA

ER10DA

Model

T1

V1

W1

T1

W1

T1

W1

T1

W1

Power circuit

 

- Phase

3~

1~

3N~

3~

3N~

3~

3N~

3~

3N~

- Frequency

(Hz)

 

50

50

50

50

50

50

50

50

50

 

- Voltage

(V)

220

220-240 380-415

220

380-415

220

380-415

220

380-415

- Voltage tolerance

(%)

 

±10 +6/-10 +6/-10 ±10 +6/-10 ±10 +6/-10 ±10 +6/-10

 

Model

ER3DA

ER5DA

ER8DA

ER10DA

 

Head pressure control kit

EKHPRD-E

EKHPRD-E

EKHPRD-E

EKHPRD-E

Floor standing kit

 

EKFSRD

EKFSRD

EKFSRD

EKFSRD

 

Model

ER3DA + 

EFD3F

 

(1)

 

ER5DA + 

EFD5F

 

(1)

 

ER8DA + 

EFD8F

 

(1)

 

 

EFD10F

 

(1)

 

Remote control kit

EKRC01

EKRC01

EKRC01

EKRC01

Switch box

 

ESBFD3FA

ESBFD5FA

ESBFD8FA

ESBFD10FA

 

1

 

Air inlet (condenser side)

 

2

 

Air outlet

 

3

 

Service door

 

4

 

Pipe connection intake

 

5

 

Liquid pipe connection

 

6

 

Gas pipe connection

 

7

 

Identification plate

Summary of Contents for ER3DAW1

Page 1: ...INSTALLATION MANUAL ER3DAW1 ER3DAT1 ER3DAV1 ER5DAW1 ER5DAT1 ER8DAW1 ER8DAT1 ER10DAW1 ER10DAT1 Air cooled condensing units...

Page 2: ...1464 15 ER10DA mm 1390 1021 375 30 1560 294 371 39 1434 1464 15 3 3 DAIKIN F D A B E C A B C D E F ER3DA mm 800 500 1075 300 800 1055 ER5DA mm 800 500 1075 300 800 1055 ER8DA mm 800 500 1170 300 800...

Page 3: ...ons can be purchased to allow easier installation MAIN COMPONENTS refer to figure 1 ER3DA ER5DA ER8DA ER10DA Air cooled condensing units Installation manual IMPROPER INSTALLATION OR ATTACHMENT OF EQUI...

Page 4: ...standing supports Attach the unit to the supports using the bolts spring lock washers and nuts provided with the kit 4 Level the unit in both directions 5 Use four anchor bolts with M8 thread to fix t...

Page 5: ...rom the gauge manifold 20 Remove the blind cap from the gas line stop valve 11 and the liquid line stop valve 12 21 Loosen the gland packing retainers of the gas line stop valve 11 and the liquid line...

Page 6: ...licensed electrician and must comply with relevant European and national regulations The field wiring must be carried out in accordance with the wiring diagrams see figure 6 figure 7 and figure 8 and...

Page 7: ...it and the switch box of the air conditioning unit The cable must be of the type H05VV U5X1 5 and must be connected to terminals 1 3 4 5 and 6 of the condensing unit as shown on the wiring diagrams se...

Page 8: ...NOTES NOTES...

Page 9: ...eration of the air conditioning system is then controlled by the remote control Shut down by switching off the remote control and the circuit breaker of the power circuit WARNINGS Emergency shut down...

Page 10: ...NOTES...

Page 11: ...NOTES...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN00410 1C...