Installation manual
9
EMRQ8~16ABY1
Daikin Altherma outdoor unit
4P501819-1 – 2017.08
7.2.
Service space
The space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available. (Refer to the figure below
and choose one of the possibilities).
(distances shown are in mm)
■
In case of an installation site where sides
A+B+C+D
have
obstacles, the wall heights of sides
A+C
have no impact on
service space dimensions. Refer to the figure above for
impact of wall heights of sides
B+D
on service space
dimensions.
■
In case of an installation site where only the sides
A+B
have
obstacles, the wall heights have no influence on any
indicated service space dimensions.
■
The installation space required on these drawings are for full
load heating operation without considering possible ice
accumulation.
If the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation
of ice in between the outdoor units.
8.
I
NSPECTING
,
HANDLING
AND
UNPACKING
THE
UNIT
8.1.
Inspection
At delivery, the unit must be checked and any damage must be
reported immediately to the carrier’s claims agent.
8.2.
Handling
When handling the unit, take into account the following:
1
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
2
Choose on beforehand the path along which the unit is to be
brought in.
3
Bring the unit as close as possible to its final installation position
in its original package to prevent damage during transport.
4
Lift the unit preferably with a crane and 2 belts of at least 8 m
long as shown in the figure above.
Always use protectors to prevent belt damage and pay attention
to the position of the unit's centre of gravity.
A forklift can only be used for transport as long as the unit
remains on its pallet as shown above.
A B C D
Sides along the installation site with obstacles
Suction side
b
a
c
d
a
c
b
d
e
e
a
c
b
f
e
d
a
c
b
d
e
b
h
1
h
2
1500
500
a
≥
10 mm
b
≥
300 mm
c
≥
10 mm
d
≥
500 mm
a
≥
50 mm
b
≥
100 mm
c
≥
50 mm
d
≥
500 mm
a
≥
200 mm
b
≥
300 mm
a
≥
10 mm
b
≥
300 mm
c
≥
10 mm
d
≥
500 mm
e
≥
20 mm
a
≥
50 mm
b
≥
100 mm
c
≥
50 mm
d
≥
500 mm
e
≥
100 mm
a
≥
200 mm
b
≥
300 mm
e
≥
400 mm
a
≥
10 mm
b
≥
300 mm
c
≥
10 mm
d
≥
500 mm
e
≥
20 mm
f
≥
600 mm
a
≥
50 mm
b
≥
100 mm
c
≥
50 mm
d
≥
500 mm
e
≥
100 mm
f
≥
500 mm
a
≥
10 mm
b
≥
300 mm
c
≥
10 mm
d
≥
500 mm
e
≥
20 mm
a
≥
50 mm
b
≥
100 mm
c
≥
50 mm
d
≥
500 mm
e
≥
100 mm
1
Packaging material
2
Belt sling
3
Opening
4
Protector
NOTE
Use a belt sling of
≤
20 mm wide that adequately
bears the weight of the unit.
1
4
2
2
4
4
3
2
3
4
4PEN501819-1.book Page 9 Wednesday, September 13, 2017 12:52 PM