Set the noise-intensive stage to "no" under the parameter "active".
Î
The stage will be skipped during actuation of pump P
S
.
5.3.8 Correction values for measuring points
If the measured value of a sensor deviates from the actual value, it can be compensated with a correction value.
•
In the menu path: "Selection 2/2" -> "System" -> "Correction values" select the correction parameter (see Fig 5-9) and
modify values Tab. 5-4 accordingly.
Tab. 5-4
Correction values
5.4
Recommended settings
5.4.1 Standard parameter settings, recommended setting ranges
The following table summarises the factory settings and the possible and recommended setting ranges of the solar system parameters.
Designation
Access level
Measurement/set-
ting/value range
Factory value
Increment
Solar panel temperature correction
Technician
-9 to +9
0 K
1 K
Return temperature correction
-9 to +9
0 K
1 K
Storage tank temperature correction
-9 to +9
0 K
1 K
Feed temperature correction
-9 to +9
0 K
1 K
Flow correction
-2 to +2
0 l/min
1 l/min
Parameter
Designation
Access level Setting range Recommended
setting range
Factory
setting
Increment
BE
FA
Delta T on Cut-in temperature difference
x
x
1...80
(>"Delta T off")
10 to 15 K
15 K
1 K
Delta T off Cut-out temperature difference
x
x
1...20
(<"Delta T on")
2 to 5 K
4 K
1 K
T
S
max
Maximum storage tank temperature
x
x
20 to 85°C
75 to 85°C
80 °C
1 K
Time PsE
Switch-on delay BSK
x
x
0 to 600 s
20 to 40 s
35 s
1 s
Time PsA
Switch-off delay BSK
—
x
0 to 600 s
15 to 30 s
20 s
1 s
Time UB
Reverse condition delay time
—
x
0 to 600 s
5 to 20 s
5 s
1 s
Time Sp
Pump blocking time
—
x
0 to 600 s
—
30 s
10 s
T
K
max
Booster temperature (maximum
solar panel temperature)
i
x
20 to 110°C
—
75 °C
1 K
T
K
zul
Cut-in protection temp. (max.
approved operating solar panel temp.)
i
x
90 to 130°C
—
110 °C
1 K
T
R
min
Minimum temperature storage tank
—
x
0 to 10°C
—
0 °C
1 K
H/A
Automatic reset from manual to
automatic mode
i
x
1 to 900 min
—
30 min
1 min
FLS active Activation FlowSensor
i
x
no / 12
12
without FLS: no
with FLS: 12
no / 12
Cycle
Cycle of data output (serial inter-
face RS 232)
—
x
0 to 300 s
—
0
5 s
Baud rate Step speed of data output
—
x
2400, 4800,
9600, 19200
—
19200
—
Tab. 5-5 Parameter overview
BE
User
FA
Technician
x
adjustable
i
informative
—
not available