Installation manual

1

EKMV EKMV3C09B7

2-way valve kit/3-way valve kit for fan coil units

4PW65144-1B – 10.2011

The English text is the original instruction. Other languages are
translations of the original instruction.

This option kit needs to be used in combination with an EKRP1C11
kit and a FWF or FWC fan coil unit.

The units are equipped with a water inlet and water outlet for
connection to a water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and
national regulations.

A

CCESSORIES

 

SUPPLIED

 

WITH

 

THE

 

KIT

C

ONNECTION

 

OF

 

THE

 

FAN

 

COIL

 

UNIT

 

TO

 

FIELD

 

PIPING

 

BY

 

USE

 

OF

 

THE

 2-

WAY

/3-

WAY

 

VALVE

Refer to the installation manual of the fan coil unit for details on
installing the fan coil unit.

If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:

Use clean pipes only.

Hold the pipe end downwards when removing burrs.

Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.

Use a good thread sealant for the sealing of the connections.
The sealing must be able to withstand the pressures and
temperatures of the system.

When using non-brass metallic piping, make sure to insulate
both materials from each other to prevent galvanic corrosion.

Because brass is a soft material, use appropriate tooling for
connecting the water circuit. Inappropriate tooling will cause
damage to the pipes.

EKMV2C09B7
EKMV3C09B7

2-way valve kit/3-way valve kit for fan coil units

Installation manual

Read this manual attentively before installation. Do not
throw it away. Keep it in your files for future reference.

Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Be sure only
to use accessories made by Daikin that are specifically
designed for the use with the equipment and have them
installed by a professional.

If unsure of installation procedures or use, always contact
your dealer for advice and information.

Danger: electric shock

Switch off all power supply before removing the control box
cover or before making any connections or touching
electrical parts.

1

Actuator with toothed ring

2

2-way valve (only for EKMV2C09B7)

3

3-way valve (only for EKMV3C09B7)

4

Insulation tape

5

Insulation for valve

6

Installation manual

7

O-ring (1x for EKMV2C09B7) (2x for EKMV3C09B7)

8

Wire (in case 2 valves are connected on same fan coil unit)

In case the supply cord of the actuator is damaged, it is
required to dispose of the actuator and to install a new
actuator.
The supply cord itself can not be replaced solely.

KRP1B101 box and EKRP1C11 PCB are needed for
combination with the FWF units.

KRP1H98 box and EKRP1C11 PCB are needed for
combination with the FWC units.

2x

1

2

3

4

5

6

7

8

Be careful not to deform the unit piping by using excessive
force when connecting the piping. Deformation of the
piping can cause malfunction of the unit.

The unit is only to be used in a closed water system.
Application in an open water circuit can lead to
excessive corrosion of the water piping.

Never use Zn-coated parts in the water circuit.
Excessive corrosion of these parts may occur as
copper piping is used in the unit's internal water
circuit.

The equipment is not intended for use in a potentially
explosive atmosphere.