7 Configuration

Installation manual

15

EKHWET90~120BAV3
R32 Split series – Domestic hot water tank
4P680074-1 – 2021.11

set  the  exact  heater  capacity  and  this  will  lead  to  more  accurate
energy  data.  The  capacity  of  the  booster  heater  installed  in  the
domestic hot water tank is 1,2 kW.

#

Code

Description

[9.4.1]

[6-02]

Booster heater capacity

 [kW]. The

capacity of the booster heater at nominal
voltage.

Range: 0~10 kW

7.2.4

Configuration wizard: Tank

Heat up mode

The  domestic  hot  water  can  be  prepared  in  3  different  ways.  They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.

#

Code

Description

[5.6]

[6-0D]

Heat up mode

:

▪ 0: 

Reheat 

only

:  Only  reheat

operation is allowed.

▪ 1: 

Sc reheat

: The domestic

hot water tank is heated according to a
schedule  and  between  the  scheduled
heat  up  cycles,  reheat  operation  is
allowed.

▪ 2: 

Schedule  only

:  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

See the operation manual for more details.

Settings for Reheat only mode

During Reheat only mode, the tank setpoint can be set on the user
interface.  The  maximum  allowed  temperature  is  determined  by  the
following setting:

#

Code

Description

[5.8]

[6-0E]

Maximum

:

The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.

The maximum temperature is NOT
applicable during disinfection function.

To set the heat pump ON hysteresis:

#

Code

Description

[5.9]

[6-00]

Heat pump ON hysteresis

▪ 2°C~20°C

INFORMATION

To ensure most optimum operation of the outdoor unit, we
recommend to set the hysteresis to 6°C or higher.

INFORMATION

If Reheat setpoint is outside operation range of the outdoor
unit,  then  the  hysteresis  will  refer  to  the  the  highest
temperature achievable by heat pump operation.

Settings for Schedule only mode and Sc reheat mode

Comfort setpoint

Only  applicable  when  domestic  hot  water  preparation  is 

Schedule

only

 or 

Sc reheat

. When programming the schedule, you

can make use of the comfort setpoint as a preset value. When you
later  want  to  change  the  storage  setpoint,  you  only  have  to  do  it  in
one place.

The  tank  will  heat  up  until  the 

storage  comfort  temperature

  has

been  reached.  It  is  the  higher  desired  temperature  when  a  storage
comfort action is scheduled.

Additionally, a storage stop can be programmed. This feature puts a
stop  to  tank  heating  even  if  the  setpoint  has  NOT  been  reached.
Only  program  a  storage  stop  when  tank  heating  is  absolutely
undesirable.

#

Code

Description

[5.2]

[6-0A]

Comfort setpoint

:

▪ 30°C~[6‑0E]°C

Eco setpoint

The 

storage  economic  temperature

  denotes  the  lower  desired

tank  temperature.  It  is  the  desired  temperature  when  a  storage
economic action is scheduled (preferably during day).

#

Code

Description

[5.3]

[6-0B]

Eco setpoint

:

▪ 30°C~min(50,[6‑0E])°C

Reheat setpoint

Desired reheat tank temperature

, used:

▪ in 

Schedule 

reheat

  mode,  during  reheat  mode:  the

guaranteed  minimum  tank  temperature  is  set  by  the 

Reheat

setpoint

  minus  the  reheat  hysteresis.  If  the  tank  temperature

drops below this value, the tank is heated up.

#

Code

Description

[5.4]

[6-0C]

Reheat setpoint

:

▪ 30°C~min(50,[6‑0E])°C

Hysteresis (reheat hysteresis)

Applicable  when  domestic  hot  water  preparation  is  scheduled
+reheat.  When  the  tank  temperature  drops  below  the  reheat
temperature minus the reheat hysteresis temperature, the tank heats
up to the reheat temperature.

#

Code

Description

[5.A]

[6-08]

Reheat hysteresis

▪ 2°C~20°C

INFORMATION

To ensure most optimum operation of the outdoor unit, we
recommend to set the hysteresis to 6°C or higher.

INFORMATION

If Reheat setpoint is outside operation range of the outdoor
unit,  then  the  hysteresis  will  refer  to  the  the  highest
temperature achievable by heat pump operation.

7.3

Weather-dependent curve

7.3.1

What is a weather-dependent curve?

Weather-dependent operation

The  unit  operates  'weather  dependent'  if  the  desired  tank
temperature is determined automatically by the outdoor temperature.
If  the  outdoor  temperature  drops  or  rises,  the  unit  compensates
instantly.  Thus,  the  unit  does  not  have  to  wait  for  feedback  by  the
user  to  increase  or  decrease  the  target  temperature  of  the  tank.
Because  it  reacts  more  quickly,  it  prevents  high  rises  and  drops  of
the water temperature at tap points.

Advantage

Weather-dependent operation reduces energy consumption.

Summary of Contents for EKHWET90BAV3

Page 1: ...Installation manual R32 Split series Domestic hot water tank English Installation manual R32 Split series Domestic hot water tank EKHWET90BAV3 EKHWET120BAV3 https daikintechnicaldatahub eu...

Page 2: ...trukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky pou...

Page 3: ...or test run 18 9 Hand over to the user 19 10 Technical data 20 10 1 Piping diagram Indoor unit 20 10 2 Wiring diagram Indoor unit 21 1 About this document Target audience Authorised installers Documen...

Page 4: ...ng the indoor unit see 4 3 Mounting the indoor unit 410 WARNING Fixing method of the indoor unit MUST be in accordance with the instructions from this manual See 4 3 Mounting the indoor unit 410 Pipin...

Page 5: ...g ambient temperatures Domestic hot water production 5 35 C Mind the following spacing installation guidelines 300 300 300 300 400 mm 300 300 Additionally to the spacing guidelines Because the total r...

Page 6: ...ease height From floor to 100 mm below top of the unit N A Not applicable Minimum floor area Release height The minimum floor area requirements depend on the release height of the refrigerant in case...

Page 7: ...d Must be 50 of Anv min minimum bottom opening area Must be 1 5 m from the floor A B Anv Anv min Min 50 of Anv min Calculate the total floor area Atotal AroomA AroomB See table 4 Look up the minimum b...

Page 8: ...or area m 2 00 4 00 6 00 8 00 10 00 12 00 14 00 2 2 4 88 2 49 1 70 1 47 2 3 5 10 2 60 1 77 1 53 1 38 2 4 5 32 2 71 1 84 1 59 1 43 2 5 5 53 2 82 1 91 1 65 1 49 1 37 2 6 5 75 2 93 1 99 1 71 1 54 1 42 Ta...

Page 9: ...a as specified in the table below 50 of the required opening area Anv min must be 200 mm from the floor of the unoccupied room The bottom of the opening must be 100 mm from the floor of the unoccupied...

Page 10: ...ce when connecting the field piping and make sure the piping is aligned properly Deformation of the piping can cause malfunctioning of the unit For information related with piping length diameter conn...

Page 11: ...the indoor unit a b a DHW hot water OUT screw connection b DHW cold water IN screw connection NOTICE A pressure relief valve field supply with an opening pressure of maximum 7 bar 0 7 MPa must be inst...

Page 12: ...heater power supply Booster heater cable Wires 2 GND 1 5 mm 9 4 Booster heater WARNING The booster heater MUST have a dedicated power supply and MUST be protected by the safety devices required by th...

Page 13: ...tings see 7 1 1 To access the most used commands 413 Afterwards If necessary you can make changes to the configuration in the menu structure or the overview settings INFORMATION When the configuration...

Page 14: ...rotective functions The unit is equipped with the following protective function Tank disinfection 2 01 The unit automatically runs the protective function when necessary During installation or service...

Page 15: ...ue When you later want to change the storage setpoint you only have to do it in one place The tank will heat up until the storage comfort temperature has been reached It is the higher desired temperat...

Page 16: ...fine the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the target temperature of the tank for different ambient temperatures For example if tank...

Page 17: ...Cold Hot You feel Fine tune with slope and offset At regular outdoor temperatures At cold outdoor temperatures Slope Offset Hot OK Hot Cold Hot Hot See 7 3 3 Slope offset curve 416 To fine tune the w...

Page 18: ...ly installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO lo...

Page 19: ...inished and the unit operates properly please make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user...

Page 20: ...aikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 10 1 Piping diagram Indoor unit R5T a1 c a2 R3T b1 b2 3D13820...

Page 21: ...h box Multi DHW Tank switch box Multi domestic hot water tank switch box Indoor Indoor Outdoor Outdoor SWB Switch box 2 Legend 2 Legend A1P Main PCB F2B Overcurrent fuse booster heater FU1 A1P fuse 5...

Page 22: ...wiring Power supply OUTDOOR UNIT X1M 1 2 3 earth 4 core X2M 1 2 3 earth INDOOR UNIT 1 1 booster heater power supply 1 2 kW 230 V earth STANDARD PART X1M L N earth Only for normal power supply installa...

Page 23: ......

Page 24: ...4P680074 1 2021 11 Copyright 2021 Daikin 4P680074 1 0000000N Verantwortung f r Energie und Umwelt...

Reviews: