4 Unit installation
Installation manual
8
EKHWET90~120BAV3
R32 Split series – Domestic hot water tank
4P680074-1 – 2021.11
Tables for PATTERN 1 and 2
Table 1: Minimum floor area
Take the following into account:
• For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 1.7 m², use the column of 1.65 m².
• For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 2.35 kg, use the row of 2.4 kg.
Minimum floor area (m²)
Charge (kg)
Release height without chimney (m)
1,23
1,35
1,50
1,65
1,80
1,95
2,10
2,25
2,40
2,55
2,70
2.2
9,81
8,14
6,60
5,80
5,31
4,90
4,55
4,25
3,99
3,75
3,54
2.3
10,72
8,90
7,21
6,06
5,55
5,13
4,76
4,44
4,17
3,92
3,70
2.4
11,67
9,69
7,85
6,49
5,80
5,35
4,97
4,64
4,35
4,09
3,87
2.5
12,66
10,51
8,52
7,04
6,04
5,57
5,18
4,83
4,53
4,26
4,03
2.6
13,70
11,37
9,21
7,61
6,40
5,80
5,38
5,02
4,71
4,43
4,19
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 5 m², use the column of 4.00 m².
• For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 2.35 kg, use the row of 2.4 kg.
• (*): The release height of the unit without chimney (minimum 1.95 m) is already higher than the minimum required release height. => OK (no
chimney needed).
Minimum release height (m)
Charge (kg)
Floor area (m²)
2,00
4,00
6,00
8,00
10,00
12,00
14,00
2.2
4,88
2,49
1,70
1,47
(*)
(*)
(*)
2.3
5,10
2,60
1,77
1,53
1,38
(*)
(*)
2.4
5,32
2,71
1,84
1,59
1,43
(*)
(*)
2.5
5,53
2,82
1,91
1,65
1,49
1,37
(*)
2.6
5,75
2,93
1,99
1,71
1,54
1,42
(*)
Table 3: Minimum bottom opening area for natural ventilation
Take the following into account:
• Use the correct table. For intermediate refrigerant charges, use the table with the higher value.
Example:
If the refrigerant charge is 2.34 kg,
use the table of 2.4 kg.
• For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 5 m², use the column of 4.00 m².
• For intermediate release height values, use the row with the lower value.
Example:
If the release height is 2.20 m, use the row of 2.05 m.
• A
nv
: Bottom opening area for natural ventilation.
• A
nv-min
: Minimum bottom opening area for natural ventilation.
• (*): Already OK (no ventilation openings needed).
A
nv-min
(dm²) – In case of Refrigerant charge=2.2 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1.23
4,7
3,1
1,5
0,7
(*)
(*)
(*)
1.45
4,0
2,3
0,6
(*)
(*)
(*)
(*)
1.65
3,6
1,7
(*)
(*)
(*)
(*)
(*)
1.85
3,2
1,2
(*)
(*)
(*)
(*)
(*)
2.05
2,8
0,7
(*)
(*)
(*)
(*)
(*)
2.25
2,5
0,3
(*)
(*)
(*)
(*)
(*)
2.45
2,2
(*)
(*)
(*)
(*)
(*)
(*)
2.65
1,9
(*)
(*)
(*)
(*)
(*)
(*)
A
nv-min
(dm²) – In case of Refrigerant charge=2.4 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1.85
5,2
3,6
2,0
1,3
0,6
(*)
(*)
2.05
4,6
2,8
1,1
0,2
(*)
(*)
(*)
2.25
4,1
2,2
0,3
(*)
(*)
(*)
(*)
2.45
3,6
1,7
(*)
(*)
(*)
(*)
(*)
2.65
3,2
1,2
(*)
(*)
(*)
(*)
(*)
1.85
2,9
0,7
(*)
(*)
(*)
(*)
(*)
2.05
2,6
0,3
(*)
(*)
(*)
(*)
(*)
2.25
2,3
(*)
(*)
(*)
(*)
(*)
(*)
A
nv-min
(dm²) – In case of Refrigerant charge=2.6 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1.85
5,8
4,2
2,6
1,9
1,3
0,6
(*)
2.05
5,1
3,3
1,6
0,8
(*)
(*)
(*)
2.25
4,5
2,7
0,8
(*)
(*)
(*)
(*)