4P680077-1A – 2022.11
7.1.3 Installation patterns
Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type
Allowed patterns
Living room, kitchen, garage, attic, basement, storage
room
1, 2
Technical room (i.e. room that is NEVER occupied by
persons)
1, 2, 3
PATTERN 1
PATTERN 2
PATTERN 3
H
release
1a
A
H
release
2a
c2
c1
A
B
c2
c1
A
Ventilation openings
N/A
Between room A and B
Between room A and
outside
Minimum floor area
Room A
Room A + Room B
N/A
Restrictions
32], and
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
release
Actual release height:
From floor to 100 mm below top of the unit.
N/A
Not applicable
Minimum floor area / Release height:
▪
The minimum floor area requirements depend on the release height of the
refrigerant in case of a leakage. The higher the release height, the lower the
minimum floor area requirements.
▪
The default point of release is 100 mm below the top of the unit.
▪
You can also take advantage of the floor area of the adjacent room (= room B) by
providing ventilation openings between the two rooms.
▪
For installations in technical rooms (i.e. room that is NEVER occupied by
persons), additionally to patterns 1 and 2, you can also use
PATTERN
3
. For this
pattern there are no requirements to the minimum floor area if you provide 2
openings (one at the bottom, one at the top) between the room and the outside
to ensure natural ventilation. The room must be protected from frost.