7
|
Unit installation
Installer reference guide
34
E120B
R32 Split series – Domestic hot water tank
4P680077-1A – 2022.11
Table 2: Minimum release height
Take the following into account:
•
For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 5 m², use the
column of 4.00 m².
•
For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is
2.35 kg, use the row of 2.4 kg.
Minimum release height (m)
Charge (kg)
Floor area (m²)
2,00
4,00
6,00
8,00
10,00
12,00
14,00
2.2
4,88
2,49
1,70
1,47
(*)
(*)
(*)
2.3
5,10
2,60
1,77
1,53
1,38
(*)
(*)
2.4
5,32
2,71
1,84
1,59
1,43
(*)
(*)
2.5
5,53
2,82
1,91
1,65
1,49
1,37
(*)
2.6
5,75
2,93
1,99
1,71
1,54
1,42
(*)
Table 3: Minimum bottom opening area for natural ventilation
Take the following into account:
•
Use the correct table. For intermediate refrigerant charges, use the table with the higher value.
Example:
If the
refrigerant charge is 2.34 kg, use the table of 2.4 kg.
•
For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 5 m², use the
column of 4.00 m².
•
For intermediate release height values, use the row with the lower value.
Example:
If the release height is
2.20 m, use the row of 2.05 m.
•
A
nv
: Bottom opening area for natural ventilation.
•
A
nv-min
: Minimum bottom opening area for natural ventilation.
•
(*): Already OK (no ventilation openings needed).
A
nv-min
(dm²) – In case of Refrigerant charge=2.2 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1.23
4,7
3,1
1,5
0,7
(*)
(*)
(*)
1.45
4,0
2,3
0,6
(*)
(*)
(*)
(*)
1.65
3,6
1,7
(*)
(*)
(*)
(*)
(*)
1.85
3,2
1,2
(*)
(*)
(*)
(*)
(*)
2.05
2,8
0,7
(*)
(*)
(*)
(*)
(*)
2.25
2,5
0,3
(*)
(*)
(*)
(*)
(*)
2.45
2,2
(*)
(*)
(*)
(*)
(*)
(*)
2.65
1,9
(*)
(*)
(*)
(*)
(*)
(*)
A
nv-min
(dm²) – In case of Refrigerant charge=2.4 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1.23
5,2
3,6
2,0
1,3
0,6
(*)
(*)
1.45
4,6
2,8
1,1
0,2
(*)
(*)
(*)
1.65
4,1
2,2
0,3
(*)
(*)
(*)
(*)
1.85
3,6
1,7
(*)
(*)
(*)
(*)
(*)
2.05
3,2
1,2
(*)
(*)
(*)
(*)
(*)
2.25
2,9
0,7
(*)
(*)
(*)
(*)
(*)
2.45
2,6
0,3
(*)
(*)
(*)
(*)
(*)
2.65
2,3
(*)
(*)
(*)
(*)
(*)
(*)
A
nv-min
(dm²) – In case of Refrigerant charge=2.6 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
2,00
4,00
6,00
8,00
10,00
12,00
14,00
1.23
5,8
4,2
2,6
1,9
1,3
0,6
(*)
1.45
5,1
3,3
1,6
0,8
(*)
(*)
(*)
1.65
4,5
2,7
0,8
(*)
(*)
(*)
(*)
1.85
4,1
2,1
0,2
(*)
(*)
(*)
(*)
2.05
3,7
1,6
(*)
(*)
(*)
(*)
(*)
2.25
3,3
1,2
(*)
(*)
(*)
(*)
(*)