Installation manual
29
EKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW54465-1A
7
Option setup
00
Optional bottom plate heater installed
0 (OFF)
0/1
—
—
02
Multiple set point pattern
0 (A)
0/1
—
—
03
Multiple set point 1
0 (OFF)
0/1
—
—
04
Multiple set point 2
0 (OFF)
0/1
—
—
8
Option setup
00
Remote controller temperature control
1 (ON)
0/1
—
—
01
Status: automatic restart function
1 (ON)
0/1
—
—
03
Status: low noise level
1
1~3
1
—
04
Status: freeze up prevention
0 0~2
1
—
9
Automatic temperature compensation
00
Leaving water temperature compensation value
0
–5~5
0.5
°C
01
Domestic hot water tank compensation value
0
–5~5
0.5
°C
02
Thermo ON/OFF admission
0
–5~5
0.5
°C
A
Option setup
02
Set point: required temperature difference for
leaving and returning water
10
5~15
1
°C
03
Set point: multiple set point 1 required temperature
value
35
25~80
1
°C
04
Set point: multiple set point 2 required temperature
value
65
25~80
1
°C
b
Domestic hot water set points
00
Set point: reheat minimum temperature
35
35~65
1
°C
01
Set point: reheat maximum temperature
45
35~75
1
°C
02
Status: weather dependent domestic water
heating
1 (ON)
0/1
—
—
03
Set point: storage temperature
70
45~75
1
°C
C
Leaving water temperature limits
00
Set point: leaving water maximum temperature
80
37~80
1
°C
01
Set point: leaving water minimum temperature
25
25~37
1
°C
d
Domestic water heating retention times
00
Set point: minimum time for domestic water
heating
10
5~20
1
—
01
Set point: maximum time for domestic water
heating
30
10~60
5
—
02
Set point: interval minimum stop time of domestic
water heating
15
5~30
5
—
E
Service mode
00
Vacuum mode
0
0/1
—
—
04
Pump only operation
0
0~2
1
—
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date
Value