background image

5

IMPORTANT NOTES:

• 

The expansion valve is an electronic type, it is controlled by 

the thermistors that are added in the circuit. Each expansion 

valve can control a range of air handler units’ sizes.

• 

The selected air handler unit must be designed for R410A.

• 

Extraneous substances (including mineral oils or moisture) 

must be prevented from getting mixed into the system.

• 

SST: saturated suction temperature at exit of air handler 

unit. 

3.  Selecting the capacity setting adaptor (see accessories)

• 

The corresponding capacity setting adaptor needs to be 

selected depending on the expansion valve (See Table 3).

• 

Connect the correct selected capacity setting adaptor to 

X24A (A1P). (See Figure 9.)

EKEXV

Kit

Capacity setting

 adaptor label

(indication)

63

J71

80

J90

100

J112

125

J140

140

J160

200

J224

250

J280

400

J22

500

J28

Table 3

Use care during construction and check the following items after 

installation is finished. 

Are thermistors fixed firmly?

Thermistors may come loose.

Is the freeze-up setting done correctly?

The air handler may freeze up.

Is the control box fixed firmly?

The unit may drop, vibrate or make noise.

Do electrical connection comply with specifications?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfuncton or components may burn out.

Is the unit safely grounded?

Dangerous or electrical leakage.

Selecting the Installation Site

This is a class A product. In a domestic environment, this product 

may cause radio interference, in which case the user may be 

required to take adequate measures.
Select an installation site where the following conditions are met 

and that meets your customer’s approval.

• 

The kits (expansion valve and control box) are designed for 

both indoor and outdoor installation.

• 

Do not install the option boxes in or on the outdoor unit.

• 

Do not put the option boxes in direct sunlight. Direct sunlight 

will increase the temperature inside the option boxes and 

may reduce its lifetime and influence its operation.

• 

Choose a flat and strong mounting surface.

• 

Ambient temperature of the control box is between 14°F 

(-10°C) and 104°F (40°C).

• 

Keep the space in front of the boxes free for future mainte-

nance.

• 

Keep air handler unit, power supply wiring and transmission 

wiring at least 3-1/4 ft. (1 m) away from televisions and radi-

os. This is to prevent image interference and noise in those 

electrical appliances. (Noise may be generated depending 

on the conditions under which the electric wave is generated, 

even if 3-1/4 ft. (1 m) is kept.)

• 

Make sure the control box is installed horizontally. Screw nuts 

position must be downwards.

Precautions

Do not install or operate the unit in rooms mentioned below.

-  Where mineral oil, like cutting oil is present.
-  Where the air contains high levels of salt such as air near 

the ocean.

-  Where sulfurous gas is present such as that in areas of hot 

spring.

-  In vehicles or vessels.
-  Where voltage fluctuates frequently such as in factory sites.
-  Where high concentration of vapor or spray are present.
-  Where machines generating electromagnetic waves are 

present.

-  Where acidic or alkaline vapor is present.
-  The option boxes must be installed with entrances 

downward.

Refrigerant Piping

NOTE: The use of a heat shield is strongly recommended when 

brazing to avoid burning the serial plate or the finish of the unit.  

Heat trap or wet rags must be used to protect heat sensitive 

components such as service valves EEV, thermistor and pressure 

sensor.

• 

For refrigerant piping of outdoor unit, refer to the installation 

manual supplied with the outdoor unit.

• 

Follow the outdoor unit specifications for additional charging, 

piping diameter and installation.

• 

The maximum allowed piping length depends on the con-

nected outdoor model.

Piping Installation

Piping Limits

L

A

3

2

1

5

4

Figure 2

Summary of Contents for EKEQFCBAV3-US

Page 1: ...y or death WARNING Only personnel that have been trained to install adjust service or repair hereinafter service the equipment specified in this manual should service the equipment The manufacturer wi...

Page 2: ...information increases the risk of property damage product dam age personal injury or death HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MA...

Page 3: ...e to wire splice 6 Installation operation manual 1 Tie wrap 6 Capacity setting adaptor 10 Stopper closing cup 1 Conduit mounting plate with sealing gasket P N 0121V00023 1 PT Screw K50x10mm P N 0163M0...

Page 4: ...500 6 3 26500 7 8 24200 7 1 30000 8 8 80 27000 7 9 33800 9 9 30500 8 9 38000 11 1 100 34000 10 0 42000 12 3 38500 11 2 47000 13 8 125 42500 12 4 52500 15 4 47500 13 9 59000 17 3 140 53000 15 5 60000 1...

Page 5: ...s in or on the outdoor unit Do not put the option boxes in direct sunlight Direct sunlight will increase the temperature inside the option boxes and may reduce its lifetime and influence its operation...

Page 6: ...E OR EXPLOSION NEVER USE OXYGEN HIGH PRESSURE AIR OR FLAMMABLE GASES FOR LEAK TESTING OF A REFRIGERATION SYSTEM WARNING TO AVOID POSSIBLE EXPLOSION THE LINE FROM THE NITROGEN CYLINDER MUST INCLUDE A P...

Page 7: ...nsulation back in place and close it with the upper insulation cover after pealing off the liner 8 Secure the pipe fixing clamp C in place again 2 x 10 32 M5 9 Make sure that field pipes are fully ins...

Page 8: ...NECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING 1 Control box 2 Hanger bracket 3 Main PCB 4 Transforme...

Page 9: ...ncorporated in the fixed wiring in accordance with relevant local and national legislation 1 Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire co...

Page 10: ...Figure 12 Wiring Diagram A1P Printed circuit board A2P Printed circuit board option KRP4 F1U Fuse 250 V F5A A1P F3U Field fuse HAP Light emitting diode service monitor green K1R Magnetic relay K4R Mag...

Page 11: ...er field supply AWG 18 0 03 Digital output voltage free Maximum 230 V maximum 2A Save this Only necessary for capacity controlled system The maximum length depends on the external device that is conne...

Page 12: ...side the air handler unit or shield it to prevent it from getting touched 1 2 Gas R3T 1 Liquid R2T Figure 13 Installation of the Thermistor Cable 1 Put the thermistor cable in a separate protective tu...

Page 13: ...ore operating the unit you must check the following Refer to the section of Use care during construction and check the following items after installation is finished on page 5 After finishing the cons...

Page 14: ...V 100 43 F 6 C 115 F 46 C Voltages shown are the center points of each step range The capacities mentioned in the table above are not exact The compressor frequency can vary and will have an impact o...

Page 15: ...ded The system will turn on again automatically after 3 minutes The system does not restart immediately after the power supply is turned on Wait 1 minute until the micro processor is prepared for oper...

Page 16: ...ILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING WATER OR DETERGENT MAY DETERIORATE THE INSULATION OF ELECTRONIC COMPONENTS AND RESULTS IN BURN OUT OF THESE COMPONENTS WARNING...

Page 17: ...17 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 18: ...18 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 19: ...19 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 20: ...on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Our continuing commitment to quality products may mean a change...

Reviews: