3 Preparation

Installation manual

4

EKCB07CAV3

Daikin Altherma low temperature monobloc control box

4P404075­1 – 2015.03

3

Preparation

3.1

Preparing installation site

3.1.1

Installation site requirements of the
control box

▪ Mind the measurement guidelines:

Maximum distance between control box and
outdoor unit

20 m

Maximum distance between control box and backup
heater kit

10 m

Maximum distance between control box and
domestic hot water tank

10 m

▪ Mind the following spacing installation guidelines:

100

50

50

600

50

50

(mm)

▪ The control box is designed to be wall­mounted in indoor locations

only. Make sure the installation surface is a flat and vertical non­
combustible wall.

▪ The  control  box  is  designed  to  operate  in  ambient  temperatures

ranging from 5~35°C.

3.2

Preparing electrical wiring

3.2.1

Overview of electrical connections for
external and internal actuators

Item

Description

Wires

Maximum

running

current

Power supply

1

Power supply for
control box

2+GND

(a)

Interconnection cable

2

Interconnection cable
between outdoor unit
and control box

2

(b)

User interface

3

User interface

2

100 mA

(c)

Optional equipment

4

Preferential kWh rate
power supply (voltage­
free contact)

2

(d)

5

Backup heater kit
thermistor

2

(e)

6

Backup heater kit
thermal protector

2

(e)

7

Backup heater kit
connection (from
control box)

2 (3V3)

3 (6V3, 6W1,
9W1)

(e)

Item

Description

Wires

Maximum

running

current

8

3­way valve

3

(f)

9

Power supply for
booster heater and
thermal protection
(from control box)

4+GND

(a)

10

Power supply for
booster heater (to
control box)

2+GND

13 A

11

Domestic hot water
tank thermistor

2

(f)

12

Room thermostat

3 or 4

100 mA

(e)

(a)

Cable section 2.5 mm².

(b)

Minimum cable section 0.75 mm²; maximum length: 20 m.

(c)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
use interface connection.

(d)

Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage­free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.

(e)

Minimum cable section 0.75 mm²; maximum length: 10 m.

(f)

The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.

NOTICE

More  technical  specifications  of  the  different  connections
are indicated on the inside of the control box.

4

Installation

4.1

Opening the units

4.1.1

To open the control box

1

1

2

WARNING

The  screws  are  delivered  with  toothed  lock  washers.
ALWAYS use toothed lock washers, also when the screws
need  to  be  replaced.  Failure  to  follow  this  warning  may
result in electric shock.

Summary of Contents for EKCB07CAV3

Page 1: ...Installation manual Daikin Altherma low temperature monobloc control box English Installation manual Daikin Altherma low temperature monobloc control box EKCB07CAV3 ...

Page 2: ...ntům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących norm i innych dokumentów normalizacyjnych pod warunkiem że używane są zgodnie z naszymi instr...

Page 3: ...ral safety precautions Safety instructions that you must read before installing Paper in the box of the outdoor unit Outdoor unit installation manual Installation instructions Paper in the box of the outdoor unit Control box installation manual Installation instructions Paper in the box of the control box Option box installation manual Installation instructions Paper in the box of the option box B...

Page 4: ... power supply voltage free contact 2 d 5 Backup heater kit thermistor 2 e 6 Backup heater kit thermal protector 2 e 7 Backup heater kit connection from control box 2 3V3 3 6V3 6W1 9W1 e Item Description Wires Maximum running current 8 3 way valve 3 f 9 Power supply for booster heater and thermal protection from control box 4 GND a 10 Power supply for booster heater to control box 2 GND 13 A 11 Dom...

Page 5: ... use multicore cable for power supply cables 4 3 1 About electrical compliance Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 4 3 2 To connect the electrical wiring on the control box 1 Insert the wiring from the bot...

Page 6: ...user interface cable to control box terminals X2M 20 21 Route the cable from the right hand side of the terminals fasten it to the cable tie mountings and route it through the hole of the low voltage wiring Onto control box In the room 2 Connect the control box to the outdoor unit Fix the cable with cable ties to the cable tie mountings X5M 20 21 1 2 X2M 3 Insert a screwdriver into the slots under...

Page 7: ...4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 5 Starting up the system For instructions on how to configure and commission the system and hand it over to the user refer to the installation manual of the outdoor unit ...

Page 8: ...4P404075 1 2015 03 Copyright 2015 Daikin ...

Reviews: