5
|
Operation
User reference guide
31
08S18+23EA
Daikin Altherma 3 R F
4P629094-1A – 2021.02
INFORMATION
In case of error code AH and no interruption of the disinfection function occurred
due to domestic hot water tapping, following actions are recommended:
▪
When the
Reheat only
or
Schedule + reheat
mode is selected, it is
recommended to program the start-up of the disinfection function at least
4 hours later than the last expected large hot water tapping. This start-up can be
set by installer settings (disinfection function).
▪
When the
Schedule only
mode is selected, it is recommended to program an
Eco
action 3 hours before the scheduled start-up of the disinfection function to
preheat the tank.
When weather-dependent operation is used for the tank, the tank temperature is
determined automatically by the outdoor temperature. For more information, see
To determine which domestic hot water mode you are using (method 1)
Check the installer settings table filled in by the installer.
To determine which domestic hot water mode you are using (method 2)
1
Go to [5]:
Tank
.
2
Check which items are displayed:
[5.1]
[5.2]
[5.3]
[5.4]
[5.5]
Eco setpoint
Schedule
Reheat setpoint
Comfort setpoint
Powerful operation
If… is displayed
Then the DHW tank mode =…
Only [5.1]
Powerful
operation
Reheat only
All items except [5.4]
Reheat
setpoint
are displayed
Schedule only
All items including [5.4]
Reheat setpoint
are
displayed
Sc reheat
5.7.2 Reheat mode
In reheat mode the DHW tank continuously heats up to the temperature shown on
the home screen (example: 50°C) when the temperature drops below a certain
value.
t
60°C
00:00
07:00
50°C
15°C
40°C
14:00
21:00
1
2
3
4
Tt
T
t
DHW tank temperature
t
Time