4 Installation

Installation manual

9

EHBH/X04+08DA*V7
Daikin Altherma 3 R W
4P618951-1 – 2020.03

4.4

Connecting water piping

4.4.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.

To  facilitate  service  and  maintenance,  2  shut-off  valves  and  1
overpressure  bypass  valve  are  provided.  Mount  the  shut-off  valves
on the space heating water inlet and space heating water outlet. To
ensure the minimum flow rate (and prevent overpressure), install the
overpressure bypass valve on the space heating water outlet.

1

Install the shut-off valves on the water pipes.

a

b

a

Water inlet

b

Water outlet

2

Screw the indoor unit nuts on the shut-off valves.

3

Connect the field piping on the shut-off valves.

4

In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.

NOTICE

Install air purge valves at all local high points.

NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  overpressure  bypass  valve
(at  the  indoor  unit,  or  at  the  collector).  See 

"3.2.1  To

check the water volume and flow rate" 

[

4

 6].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

overpressure  bypass  valve  setting.  See 

"3.2.1  To

check  the  water  volume  and  flow  rate" 

[

4

  6]  and

"6.2.1 To check the minimum flow rate" 

[

4

 22].

NOTICE

In case an optional domestic hot water tank is installed: A
pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=  1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

4.4.2

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

INFORMATION

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

4.4.3

To fill the domestic hot water tank

See the installation manual of the domestic hot water tank.

4.4.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

4.5.1

About electrical compliance

Only for the backup heater of the indoor unit

See 

"4.5.4 To connect the backup heater power supply" 

[

4

 10].

4.5.2

To connect the electrical wiring to the
indoor unit

1

Open  the  switch  box  so  that  you  can  access  the  back  of  the
switch box. See 

"4.1.1 To open the indoor unit" 

[

4

 7].

2

Route the wiring as follows:

▪ Enter the unit from the bottom.
▪ Route the wiring via the back of the switch box.
▪ Fix  the  cables  with  cable  ties  to  the  cable  tie  mountings  at

the back of the switch box.

b

a

X2M

X1M

X5M

d

b+c

a

c

a, b, c

Field wiring (see table below)

d

Factory-mounted cable for power supply of backup heater

INFORMATION

When  installing  field  supply  or  option  cables,  foresee
sufficient  cable  length.  This  will  make  it  possible  to  open
the  switch  box  and  gain  access  to  other  components
during service.

Summary of Contents for EHBH08DA6V7

Page 1: ...Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EHBH04DA6V7 EHBH08DA6V7 EHBH08DA9W7 EHBX04DA6V7 EHBX08DA6V7 EHBX08DA9W7...

Page 2: ...u s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uput...

Page 3: ...izard Main zone 17 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 18 5 2 8 Configuration wizard Tank 19 5 3 Settings menu 20 5 3 1 Main zone 20 5 3 2...

Page 4: ...es Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured fro...

Page 5: ...ate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings permanently open are provided between room A and B 1...

Page 6: ...ernal actuators Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit...

Page 7: ...witch box cover 4 3 If you have to do work behind the switch box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open...

Page 8: ...2 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable...

Page 9: ...of maximum 10 bar 1 MPa must be installed on the domestic cold water inlet connection in accordance with the applicable legislation 4 4 2 To fill the water circuit To fill the water circuit use a fiel...

Page 10: ...3 6 a Interconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cables with cable ties to the cable tie mountings INFORMATION In case of pre...

Page 11: ...ace point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessa...

Page 12: ...case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity me...

Page 13: ...stat normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install th...

Page 14: ...You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not appl...

Page 15: ...t in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 2 3V 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic ho...

Page 16: ...thermostatic valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance w...

Page 17: ...Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is d...

Page 18: ...ecrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so...

Page 19: ...Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies to systems with an optional domestic hot water tank installed Heat up mode The domestic hot water can be prepared in 3 di...

Page 20: ...ou can set additional settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat co...

Page 21: ...ilibrium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running...

Page 22: ...age on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the ind...

Page 23: ...test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In...

Page 24: ...ult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 7 Hand over to the user On...

Page 25: ...ing water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigeran...

Page 26: ...wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translati...

Page 27: ...witch box 5 Ext thermistor 5 External thermistor SWB Switch box English Translation 6 Field supplied options 6 Field supplied options 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse dete...

Page 28: ...mostat A13P P1 P2 LAN adapter A14P P1 P2 user interface Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H onl...

Page 29: ...H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800 mm 1 84 8 57 7 84 6 64 5 92...

Page 30: ...when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For intermediat...

Page 31: ......

Page 32: ...4P618951 1 2020 03 Copyright 2020 Daikin 4P618951 1 0000000S Verantwortung f r Energie und Umwelt...

Reviews: