background image

4 Configuration

 

Installation manual

12

EHBH/X04~16CA

Daikin Altherma - Low Temperature Split

4P313771-1C – 2012.11

X1M

X2M

1

2

3

4

5

A8P

X8

01

M

S6

S

S7

S

S8

S

S9

S

a

a

Installation of EKRP1AHTA is required.

2

Fix the cable with cable ties to the cable tie mountings.

3.6

Finishing the indoor unit installation

3.6.1

To fix the user interface cover to the
indoor unit

1

Make sure that the front panel is removed from the indoor unit.
See "3.1.1 To open the indoor unit" on page 4.

2

Plug the user interface cover into the hinges.

3

Mount the front panel to the indoor unit.

3.6.2

To close the indoor unit

1

Close the switch box cover.

2

Reinstall the front panel.

NOTICE 

When  closing  the  indoor  unit  cover,  make  sure  that  the
tightening torque does NOT exceed 4.1 N•m.

4

Configuration

4.1

Overview: Configuration

If you do NOT configure the system correctly, it might NOT work as
expected. You can configure the system with the user interface.

 

When you turn ON the user interface for the first time (via the indoor
unit),  a  quick  wizard  starts  to  help  you  configure  the  system.  If
necessary,  you  can  also  make  changes  to  the  configuration
afterwards.

NOTICE 

The  explanation  about  the  configuration  in  this  chapter
gives  you  ONLY  basic  explanations.  For  more  detailed
explanation  and  background  information,  see  the  installer
reference guide.

 

The configuration influences the following:

▪ The calculations of the software

▪ What you can see on and do with the user interface

 

Legend for the settings tables:

#

: Breadcrumb in the menu structure

Code

: Code in the overview settings

When  the  installer  settings  are  changed,  the  system  will  request  to
confirm. When confirmation is complete, the screen will shortly turn
OFF and "busy" will be displayed for several seconds.

The  most  commonly  used  installation  settings  are  accessible
through  the  menu  structure.  Their  location  is  mentioned  by  the
breadcrumb indication (#). Additionally, all installer settings can also
be  found  in  "4.3  Menu  structure:  Overview  installer  settings"  on
page 16.

For  access  to  the  setting  codes,  see  "4.1.1  To  access  the  installer
settings" on page 12.

Not all settings are accessible through the menu structure. Some are
only  accessible  through  their  code.  Then  in  the  table  explained
below, the bread crumb is set as N/A (not applicable).

4.1.1

To access the installer settings

1

Set the user permission level to Installer.

2

Go to [A]: 

 > Installer settings.

4.1.2

To access the overview settings

1

Set the user permission level to Installer.

2

Go to [A.8]: 

 > Installer settings > Overview settings.

4.1.3

To set the user permission level to
Installer

1

Go to [6.4]: 

 > Information > User permission level.

2

Press 

 for more than 4 seconds.

Result: 

 is displayed on the home pages.

3

If you do NOT press any button for more than 1 hour or press

 again for more than 4 seconds, the installer permission level

switches back to End user.

4.1.4

To switch between user permission levels
(End user and Advanced end user)

1

Go to [6] or any of its submenus: 

 > Information.

2

Press 

 for more than 4 seconds.

Result: 

The  user  permission  level  switches  to  Adv.  end  user.

Additional information is displayed and "+" is added to the menu
title.

3

If you do NOT press any button for more than 1 hour or press

 again for more than 4 seconds, the user permission level

switches back to End user.

 

Summary of Contents for EHBH04CA

Page 1: ...Installation manual Daikin Altherma Low Temperature Split English Installation manual Daikin Altherma Low Temperature Split EHBH04CA EHBH08CA EHBH16CA EHBX04CA EHBX08CA EHBX16CA ...

Page 2: ...ledujícímnormámnebonormativnímdokumentům uskladusaslijedećimstandardom ima ilidrugimnormativnimdokumentom ima uzuvjetdaseonikoristeuskladusnašim uputama megfelelnekazalábbiszabvány ok nakvagyegyébirányadódokumentum ok nak haazokatelőírásszerinthasználják 17 18 19 20 21 22 23 24 25 spełniająwymoginastępującychnormiinnychdokumentównormalizacyjnych podwarunkiemżeużywanesązgodnieznaszymi instrukcjami ...

Page 3: ...4 2 2 Quick wizard Standard 13 4 2 3 Quick wizard Options 13 4 2 4 Quick wizard Capacities energy metering 14 4 2 5 Space heating cooling control 14 4 2 6 Domestic hot water control 15 4 2 7 Contact helpdesk number 15 4 3 Menu structure Overview installer settings 16 5 Commissioning 17 5 1 Checklist before test run 17 5 2 To perform an air purge 17 5 3 To perform a test run 17 5 4 To perform an ac...

Page 4: ...s k Sound plate only for EHBH X16 l Screws for fixing sound plate only for EHBH X16 4 Remove the accessories k l only for EHBH X16 These accessories are located at the bottom of the packaging 3 Installation 3 1 Opening the units 3 1 1 To open the indoor unit 1 Loosen and remove the 2 screws that fix the front panel 2x 2 Tilt the front panel towards you and remove the front panel 3 1 2 To open the ...

Page 5: ...s as shown below 2x 2 1 3 4 4 Lift the unit 1 2 5 Tilt the top of the unit against the wall at the position of the 2 inserted screws 6 Hook the unit against the wall 2 1 2x 3 2x 7 Assemble the unit 1 2 1 2 2 2 3 4x 8 Following step is only applicable for EHBH X16 3 2 2 To install the drain pan kit If a drain pan kit EKHBDPCA2 is required install it before connecting the refrigerant and water pipes...

Page 6: ...f connection with the optional domestic hot water tank see the installation manual of the domestic hot water tank 5 Only applicable for EHBH X16 install the sound plate as shown in the figure below 1 2 4x 3 3 4 2 To fill the water circuit 1 Connect the water supply hose to the drain and fill valve 2 Open the drain and fill valve 3 Make sure that the automatic air purge valve is open at least 2 tur...

Page 7: ...1 To open the indoor unit on page 4 2 Wiring should enter the unit from the bottom 3 Routing of the wiring inside the unit should be as follows For EHBH X04 08 a b c a b c For EHBH X16 a c b a c c c b INFORMATION When installing field supply or option cables foresee sufficient cable length This will make it possible to remove reposition the switch box and gain acces to other components during serv...

Page 8: ...r supply when active 3 5 4 To connect the backup heater power supply CAUTION If the indoor unit has a tank with a built in electrical booster heater EKHW use a dedicated power circuit for the backup heater and booster heater NEVER use a power circuit shared by another appliance This power circuit must be protected with the required safety devices according to the applicable legislation The backup ...

Page 9: ... below should be measured ALWAYS measure the resistance on the contactor clamps K1M K2M and K5M 3 kW 1 230 V 6 kW 1 230 V 6 kW 3 230 V 6 kW 3N 400 V 9 kW 3N 400 V K1M 1 K5M 13 52 9Ω 52 9Ω 52 9Ω K1M 3 105 8Ω 105 8Ω K1M 5 105 8Ω 105 8Ω K1M 3 K1M 5 26 5Ω 26 5Ω 26 5Ω 105 8Ω 105 8Ω K2M 1 K5M 13 26 5Ω 26 5Ω K2M 3 52 9Ω 52 9Ω K2M 5 52 9Ω 52 9Ω K2M 3 K2M 5 52 9Ω 52 9Ω 52 9Ω 52 9Ω 52 9Ω 3 kW 1 230 V 6 kW 1...

Page 10: ... carefully separate the faceplate from the wallplate NOTICE The PCB is mounted in the faceplate of the user interface Be careful NOT to damage it 9 Fix the wallplate of the user interface to wall 10 Connect the wires to the user interface as shown below From the rear b a PCB 1x From the left a PCB b 1x From the top a b PCB b 1x From the top center a PCB b b 1x a Notch this part for the wiring to p...

Page 11: ...To connect the alarm output 1 Connect the alarm output cable to the appropriate terminals as shown in the illustration below X1M X2M 29 X1M YC Y1 Y2 Y3 Y4 A4P X2M a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 3 5 10 To connect the space cooling heating ON OFF output 1 Connect the space cooling heating ON OFF output cable to the appropriate termi...

Page 12: ...overview settings When the installer settings are changed the system will request to confirm When confirmation is complete the screen will shortly turn OFF and busy will be displayed for several seconds The most commonly used installation settings are accessible through the menu structure Their location is mentioned by the breadcrumb indication Additionally all installer settings can also be found...

Page 13: ...ndition 4 2 3 Quick wizard Options Domestic hot water settings Code Description A 2 2 1 E 05 Domestic hot water tank 0 No NOT installed 1 Yes Installed Code Description A 2 2 3 E 07 Tank booster heater 0 Horizontal BSH Installed at side of the tank 1 Backup heater NOT installed 2 N A 3 N A A 2 2 A D 02 Domestic hot water pump 0 No NOT installed 1 Secondary rtrn Installed for instant hot water 2 Di...

Page 14: ...2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pulse kWh 5 Installed 1000 pulse kWh A 2 2 9 D 09 Optional external kWh meter 2 0 No NOT installed 1 Installed 0 1 pulse kWh 2 Installed 1 pulse kWh 3 Installed 10 pulse kWh 4 Installed 100 pulse kWh 5 Installed 1000 pulse kWh 4 2 4 Quick wizard Capacities energy metering Code Description A 2 3 1 6 02 Booster heater capacity kW A 2 3...

Page 15: ...e system 0 Quick Example Small water volume and fan coils 1 Slow Example Large water volume floor heating loops Depending on the system water volume and the heat emitters type the heat up or cool down of a space can take longer This setting can compensate for a slow or a quick heating cooling system by adjusting the unit capacity during the heat up cool down cycle 4 2 6 Domestic hot water control ...

Page 16: ...ooling On temp A 3 3 Setpoint mode Scheduled DHW Domestic hot water DHW A 4 Schedule temperatures Storage comfort SP mode Weather dependent curve Scheduled DHW A 4 2 Setpoint readout type Conversion persons Setpoint readout A 4 3 External sensor Demand PCB Disinfection Operation day Start time Temperature target A 4 4 Duration Backup heater Heat sources A 5 Operation mode Auto emergency operation ...

Page 17: ... pressure relief valve purges water when opened 5 2 To perform an air purge 1 Go to A 7 3 Installer settings Commissioning Air purge 2 Set the type speed and circuit 3 Select Start air purge and press 4 Select OK and press Result The air purge starts It stops automatically when done To stop it manually press select OK and press 5 3 To perform a test run 1 Go to A 7 1 Installer settings Commissioni...

Page 18: ...Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the CD DVD and the printed documentation and ask him her to keep it for future reference Explain the user how to properly operate the system and what he she has to do in case of problems Show the user what jobs he she has to do in relation to maintenance of the unit Explain the user abo...

Page 19: ...ter pulse input 2 electrical meter pulse input 1 preferential kWh rate PS contact external indoor or outdoor ambient thermistor domestic hot water thermistor external sensor floor or ambient ambient sensor On OFF thermostat thermal protector booster heater 6T1 3 230 V 6 kW 9WN 3N 400 V 9 kW 6WN 3N 400 V 6 kW 6V3 1N 230 V 6 kW 3V3 1N 230 V 3 kW Backup heater configuration only for 9W Ext thermistor...

Page 20: ...230 V 6 kW for 3V3 1N 230 V 3 kW only for 9W only for 3V only for KHWS V3 domestic hot water tank 4D077028 page 3 A4P YC A4P Y2 A4P Y2 X2M 29 S6S S7S S8S S9S S3S BSK S1S S2S B1L X2M 14 X2M 9 X2M 14 X2M 9 X2M 13 t R5T t R6T 2 KHR KHUR KCR KFR t R1T t R1T 2 X18A 1 2 X22A 1 X85A 1 2 3 4 5 6 t R1T F1U F2U 3 CN1 1 6 5 4 3 2 CN2 1 X80A 1 2 7 8 4 X4A 1 2 3 X33A 1 3 4 6 5 3 4 5 6 7 8 9 12 11 10 X40A 1 2 3...

Page 21: ...nly for 16 DHW pump 3 wire type SPST NO valve only for domestic hot water option 3 wire type SPDT domestic hot water tank only for enamel tank option only for domestic hot water option 1N 50 Hz 230 V AC Normal kWh rate power supply only for domestic hot water tank option A1P Main PCB A2P User interface PCB A3P Solar pump station PCB A3P On OFF thermostat PC power circuit A3P Heat pump convector A4...

Page 22: ...heater configuration only for 9W User installed options User installed options Bottom plate heater Bottom plate heater Domestic hot water tank Domestic hot water tank Domestic hot water tank with solar connection Domestic hot water tank with solar connection Remote user interface Remote user interface Ext indoor thermistor Extended indoor thermistor Ext outdoor thermistor Extended outdoor thermist...

Page 23: ...core signal Changeover to ext heat source output Ext heat source eg boiler Only for KRP1HB KSOLHWAV1 NO valve X2M 6 7 NC valve X2M 5 7 2 core 2WAY VALVE M2S KHBX units for cooling mode main X2M 1 2 4 add X2M 1a 2a 4 3 core for C H operation 2 core for H only operation main X2M 1 2 3 4 add X2M 1a 2a 3 4 main X2M 1 4 add X2M 1a 4 4 core Only for KRTW wired room thermostat Only for KRTR wireless room...

Page 24: ... pulse kWh 1pulse kWh 10pulse kWh 100 pulse kWh 1000 pulse kWh pulse duration minimum On time 40ms minimum OFF time 100ms measurement type depending on installation single phase AC meter three phase AC meter balanced loads three phase AC meter unbalanced loads electrical meter installation guideline General it is the reponsability of the installer to cover the complete power consumption with elect...

Page 25: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...

Page 26: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...

Page 27: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...

Page 28: ...4P313771 1C 2012 11 Copyright 2012 Daikin ...

Reviews: