INSTALLATION MANUAL                                                                                        FXMQ_PB/FBQ ECONOMIZER 

 

C.

 

Fan Mode 

1.

 

While in fan only operation, cooling thermo-off, and heating thermo-off, the damper will open to the minimum vent 
position. The minimum vent position is site-configurable.     

 
D.

 

Enthalpy Control 

1.

 

The enthalpy economizer control senses both temperature and humidity of the outside air. When the heat content 
of the outside air is below the control set point, the control permits the outside air dampers to operate as described 
in section 5.A.2. above. When the heat content rises above the control set point, the control closes the outdoor air 
dampers to the minimum vent position. This setpoint can be adjusted as needed.     

 

 

 

Figure 2. Single Enthalpy Curve and Boundaries 

 

Table 3. Single Enthalpy and Dual Enthalpy High Limit Curves 

 

 

E.

 

Settings 

1.

 

The mixed air temperature set point must be no lower than 65 

°

FDB for continuous operation. This may be 

configured down to 60 

°

FDB, however thermo off may be carried out due to freeze protection.

 

2.

 

The economizer is recommended for standard comfort cooling applications only. This must not be used for high heat 
density, year round cooling applications.

 

3.

 

The enthalpy curve setting must not be programmed to ES4 or ES5. 

 

 

6.

 

Wiring Diagram 

Provide field supplied 24VAC power supply and 18 gauge, stranded wire as indicated in Figure 3. All wiring and electrical work 
should conform to applicable national, state, and local codes.     

 

Summary of Contents for ECONMQ12P-8-1K

Page 1: ...1 INSTALLATION MANUAL FXMQ_PB FBQ Economizer MODELS ECONMQ12P 8 1K ECONMQ12P 13 1K ECONMQ30P 8 1K ECONMQ30P 13 1K ECONMQ48P 8 1K ECONMQ48P 13 1K ...

Page 2: ...el Number Description Applicable Indoor Units Field Supplied Power ECONMQ12P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ12P 13 1K Fully modulating economizer 1 12 x 20 x 4 MERV 13 filter FXMQ07PBVJU FXMQ09PBVJU 24VAC ECONMQ30P 8 1K Fully modulating economizer 1 12 x 20 x 2 MERV 8 filter FXMQ15PBVJU FXMQ18PBVJU FXMQ24PBVJU FBQ18PVJU FBQ24PVJU FB...

Page 3: ...ER 3 2 Dimensions Kit Model A B1 B2 C D E ECONMQ12P 8 1K 21 625 13 00 9 75 24 25 7 50 17 00 ECONMQ12P 13 1K ECONMQ30P 8 1K 36 4375 13 00 9 75 24 25 7 50 32 00 ECONMQ30P 13 1K ECONMQ48P 8 1K 52 1875 13 00 9 75 24 25 7 50 48 00 ECONMQ48P 13 1K ...

Page 4: ...zer and indoor unit g Place the return air duct and fresh air duct over the economizer return and fresh air dampers Note Economizer section may be rotated 180 for bottom fresh air connection 5 Operation Mode A Cooling Mode 1 While in cooling thermo on with the ambient temperature and humidity above the enthalpy control set point the fresh air damper will open to the minimum vent position and the c...

Page 5: ... the minimum vent position This setpoint can be adjusted as needed Figure 2 Single Enthalpy Curve and Boundaries Table 3 Single Enthalpy and Dual Enthalpy High Limit Curves E Settings 1 The mixed air temperature set point must be no lower than 65 FDB for continuous operation This may be configured down to 60 FDB however thermo off may be carried out due to freeze protection 2 The economizer is rec...

Page 6: ...ay the value of the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value Press the button to accept the displayed value and store it in non volatile RAM CHANGE STORED displays Press the button Enter to return to the current parameter Press the button MenuUp Exit to return to the previous menu No...

Reviews: