11
|
Configuration
Installer reference guide
154
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
If room buffering is enabled, the extra energy from photovoltaic panels is buffered
in the DHW tank and in the space heating/cooling circuit (i.e. heat up or cool down
the room). With the room comfort setpoints (cooling/heating) you can modify the
maximum/minimum setpoints that will be used when buffering the extra energy in
the space heating/cooling circuit.
#
Code
Description
[1.9.1]
[9-0A]
Heating comfort setpoint
▪
[3-07]~[3-06]°C
[1.9.2]
[9-0B]
Cooling comfort setpoint
▪
[3-09]~[3-08]°C
11.6.3 Main zone
Overview
The following items are listed in the submenu:
2
Main zone
Additional zone
Room
Malfunctioning
Space heating/cooling
[2]
Main zone
Setpoint screen
[2.1]
Schedule
[2.2]
Heating schedule
[2.3]
Cooling schedule
[2.4]
Setpoint mode
[2.5]
Heating WD curve
[2.6]
Cooling WD curve
[2.7]
Emitter type
[2.8]
Setpoint range
[2.9]
Control
[2.A]
Ext thermostat type
[2.B]
Delta T
[2.C]
Modulation
[2.E]
WD curve type
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone
.
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪
In
Fixed
LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
▪
In
Weather dependent
LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.