11
|
Configuration
Installer reference guide
215
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
Power saving function
Power saving function
NOTICE
Power saving function.
If you want to use the power saving function, on the
compressor module PCB:
Disconnect X804A from X805A.
Connect X804A to X806A.
X806A
X804A
X805A
X805A
X804A
X806A
3N~
1N~
Defines whether the power supply to the compressor module can be interrupted
(internally by hydro module control) during stand-still conditions (no space
heating/cooling nor domestic hot water demand). The final decision to allow
power interruption of the compressor module during standstill depends on the
ambient temperature, compressor conditions and minimum internal timers.
To enable the power saving function setting, [E‑08] needs to be enabled on the
user interface.
#
Code
Description
[9.F]
[E‑08]
Power saving function
for compressor
module:
▪
0:
No
▪
1:
Yes
Disable protections
INFORMATION
Protective functions – "Installer-on-site mode"
. The software is equipped with
protective functions, such as room antifrost. The unit automatically runs these
functions when necessary.
During installation or service this behaviour is undesired. Therefore, the protective
functions can be disabled:
▪
At first power-on:
The protective functions are disabled by default. After 12
hours they will be automatically enabled.
▪
Afterwards:
An installer can manually disable the protective functions by setting
[9.G]:
Disable protections
=
Yes
. After his work is done, he can enable the
protective functions by setting [9.G]:
Disable protections
=
No
.