9
|
Electrical installation
Installer reference guide
116
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
180°
A8P
A8P
A8P
A8P
5 4 3 2 1
a
X801M
A8P
a
Installation of EKRP1AHTA is required.
3
Fix the cable with cable ties to the cable tie mountings.
9.2.13 To connect the safety thermostat (normally closed contact)
Wires: 2×0.75 mm²
Maximum length: 50 m
Safety thermostat contact: 16 V DC detection (voltage supplied by PCB).
The voltage-free contact shall ensure the minimum applicable load of
15 V DC, 10 mA.
—
1
Access the electrical connections. See
"9.2.1 To connect the electrical wiring
95].
2
Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.
X5M.14
X5M.13
Q4L
13
14
X5M
180°
a
X5M
13
14
a
Remove jumper
3
Fix the cable with cable ties to the cable tie mountings.