Daikin EBHQ011BB6V3 Installation Manual Download Page 45

E(D/B)(H/L)Q011~016BB

Unit for air to water heat pump system

4PW67904-1 – 01.2011

Installation manual

42

Additional external backup heater permission signal [C-02]=2

This function gives the possibility to drive an additional external
backup heater.
The additional external backup heater can be used to assist space
heating (not domestic water heating) during low ambient conditions.

The signal for additional external heater will be activated when the
second step of the internal backup heater is closed and when the
outdoor temperature goes below [C-03] setting with [C-04]
hysteresis.

[C-02]=2 Additional external backup heater operation is
enabled (2)

[C-03] External backup heater ON temperature: defines the
outdoor temperature below which the permission signal for
the external backup heater will be active (closed, KCR on
EKRP1HB).

[C-04] External backup heater hysteresis
External backup heater permission signal X1–X2 (EKRP1HB)

T

A

Outdoor temperature

[d] Benefit kWh rate power supply/Local shift value weather
dependent

Benefit kWh rate power supply

[d-00] Switching off heaters: Defines which heaters are
switched off when the benefit kWh rate signal of the
electricity company is received.
If [d-01]=1 or 2 and the benefit kWh rate signal of the
electricity company is received, following devices will be
switched off.
Only for EKHW*

(1)

:

Only for EKHTS

(2)

:

[d-01] Unit connection to benefit kWh rate power supply:
Defines whether or not the unit is connected to a benefit kWh
rate power supply.
If [d-01]=0, the unit is connected to a normal power supply
(default value).
If [d-01]=1 or 2, the unit is connected to a benefit kWh rate
power supply. In this case the wiring requires specific
installation like explained in 

"Connection to a benefit kWh

rate power supply" on page 26

When parameter [d-01]=1 at the moment that the benefit
kWh rate signal is sent by the electricity company, that
contact will open and the unit will go in forced off mode

(3)

.

When parameter [d-01]=2 at the moment that the benefit
kWh rate signal is sent by the electricity company, that
contact will close and the unit will go in forced off mode

(4)

.

INFORMATION

In case the outdoor unit is not single phase (W1),
the combination of setting [4-03]=0/2 with
bivalent operation at low outdoor temperature
can result in domestic hot water shortage.

The bivalent operation function has no impact on
the domestic water heating mode. The domestic
hot water is still and only heated by the unit.

The permission signal for the auxiliary boiler is
located on the EKRP1HB (digital I/O PCB). When
it is activated, the contact X1, X2 is closed and
open when it is disactivated. See figure for the
schematic location of this contact.

INFORMATION

When [4-07] "Backup heater second step" is disabled, then
the additional external backup heater signal will never be
activated.

CAUTION

It is the responsibility of the installer to make sure no
unwanted situations can occur and that all safeties are
implemented according to applicable legislation.

Daikin shall not be held liable for any damage resulting
from failure to observe this rule.

INFORMATION

Permission signal X1–X2 can only be for the bivalent
operation OR external backup heater permission signal.

Both functions cannot be used at the same time.

YC Y1 Y2 Y3 Y4

X1

X2

X3

X4

OFF ON

X2M

SS1

X1M

closed

open

T

A

[C-03]

[C-04]

(1) Only applicable for tank with built-in electrical booster heater (EKHW*).

[d-00]

Compressor

Back up heater

Booster heater


(default)

Forced off

Forced off

Forced off

1

Forced off

Forced off

Permitted

2

Forced off

Permitted

Forced off

3

Forced off

Permitted

Permitted

(2) Only applicable for tank without electrical booster heater (EKHTS).

[d-00]

Compressor

Backup heater

0 (default)

Forced off

Forced off

2

Forced off

Permitted

INFORMATION

[d-00] settings 1, 2 and 3 are only meaningful
if the benefit kWh rate power supply is of type
1 or the unit is connected to a normal kWh
rate power supply (via 1-2 X11M) and the
backup heater and booster heater are not
connected to the benefit kWh rate power
supply.

For EKHTS, do not select 1 or 3 value.

(3) When the signal is released again, the voltage free contact will close and 

the unit will restart operation. It is therefore important to leave the auto 
restart function enabled. Refer to 

"[3] Auto restart" on page 34

.

(4) When the signal is released again, the voltage free contact will open and 

the unit will restart operation. It is therefore important to leave the auto 
restart function enabled. Refer to 

"[3] Auto restart" on page 34

.

Summary of Contents for EBHQ011BB6V3

Page 1: ... EDHQ016BB6W1 EDLQ011BB6V3 EDLQ014BB6V3 EDLQ016BB6V3 EDLQ011BB6W1 EDLQ014BB6W1 EDLQ016BB6W1 EBHQ011BB6V3 EBHQ014BB6V3 EBHQ016BB6V3 EBHQ011BB6W1 EBHQ014BB6W1 EBHQ016BB6W1 EBLQ011BB6V3 EBLQ014BB6V3 EBLQ016BB6V3 EBLQ011BB6W1 EBLQ014BB6W1 EBLQ016BB6W1 Unit for air to water heat pump system ...

Page 2: ...2 1 W1 V3 DC AC DC AC AC AC A A B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 A A B2 B2 B2 D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 B1 B1 B1 C C 1 2 ...

Page 3: ...er iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen määräyksiä 14 za dodržení ustanovení předpisu 15 prema odredbama 16 követi a z 17 zgodnie z postanowieniami Dyrektyw 18 în urma prevederilor 19 ob upoštevanju določb 20 vastavalt nõuetele 21 следвайки клаузите на 22 laikantis nuostatų pateikiamų 23 ievērojot prasības kas noteiktas 24 održia...

Page 4: ...elines 24 9 5 Precautions on wiring of power supply 24 Specifications of standard wiring components 24 Connection of the backup heater power supply 24 Connection of the thermostat cable 25 Connection of the valve control cables 26 Connection to a benefit kWh rate power supply 26 Installation of the digital controller 28 Wiring specifications 28 10 Start up and configuration 28 10 1 DIP switch sett...

Page 5: ...peration of the unit always contact your local dealer for advice and information Improper installation or attachment of equipment or accessories could result in electric shock short circuit leaks fire or other damage to the equipment Be sure only to use accessories and optional equipment made by Daikin which are specially designed for use with the products as of subject in this manual and have the...

Page 6: ...ctrical booster heater EKHW in 3 different sizes 150 200 and 300 litre tank without electrical booster heater EKHTS in 2 different sizes 200 and 260 litre Refer to the domestic hot water tank installation manual for further details Solar kit for domestic hot water tank option For information concerning the EKSOLHW solar kit refer to the installation manual of that kit WARNING Never directly touch ...

Page 7: ...ce the selection is done and the water system is designed this manual describes the procedures for handling installing and connecting the EDH EBH EDL and EBL units This manual has been prepared to ensure adequate maintenance of the unit and it will provide help if problems occur 3 3 Model identification 3 4 Typical application examples The application examples given below are for illustration purp...

Page 8: ...ls on pump configuration can be found under 10 3 Pump operation configuration on page 29 NOTICE When circulation in each floor heating loop FHL1 3 is controlled by remotely controlled valves M1 3 it is important to provide a by pass valve 8 to avoid the flow switch safety device from being activated The by pass valve should be selected as such that at all time the minimum water flow as mentioned u...

Page 9: ...ough floor heating loops and fan coil units Cooling is provided through the fan coil units only 1 Unit 2 Heat exchanger 3 Backup heater 4 Pump 5 Shut off valve 6 Collector field supply 7 By pass valve field supply 8 Motorised 2 way valve to shut off the floor heating loops during cooling operation field supply 9 Motorised 2 way valve for activation of the room thermostat field supply FCU1 3 Fan co...

Page 10: ... 12 Aquastat valve field supply 13 Shut off valve field supply 14 Non return valve field supply FHL1 3 Floor heating loop field supply UI User interface Field wiring configuration A BTI Boiler thermostat input A Auxiliary contact normal closed H Heating demand room thermostat optional Com Common room thermostat optional E D B Unit auto Automatic Boiler Boiler K1A Auxiliary relay for activation of ...

Page 11: ...o as to achieve the target leaving water temperature as set on the user interface When weather dependent operation is active the water temperature is determined automatically depending on the outdoor temperature During heating operation of the boiler the boiler will operate so as to achieve the target leaving water temperature as set on the boiler controller Never set the target leaving water temp...

Page 12: ...is that the heat pump will can operate at the lowest required leaving water temperature when only floor heating is required Higher leaving water temperatures are only required in case fan coil units are operating This results in a better performance of the heat pump The hydraulic balance is very important unit mixing station FCU1 3 FHL1 FHL2 FHL3 T1 T2 FCU1 FCU2 FCU3 8 7 6 B A 5 4 2 3 1 Set point ...

Page 13: ...it 4 Heat exchanger 5 Expansion vessel 10 l 6 Refrigerant liquid connection 7 Refrigerant gas connection 8 Shut off valves The shut off valves on the water inlet connection and water outlet connection allow isolation of the unit water circuit side from the residential water circuit side This facilitates draining and filter replacement of the unit 9 Water inlet connection 10 Water outlet connection...

Page 14: ...ch box main components door 2 1 Backup heater contactors K1M and K5M 2 Main PCB The main PCB Printed Circuit Board controls the functioning of the unit 3 Booster heater contactor K3M only for installations with domestic hot water tank 4 Booster heater circuit breaker F2B only for installations with domestic hot water tank The circuit breaker protects the booster heater in the domestic hot water ta...

Page 15: ...imals making contact with electrical parts can cause malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean and clear Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation work may result in accidents due to fall of equipment The equipment is not intended for use in a potentially explosive at...

Page 16: ...tion of the wind 3 Prepare a water drainage channel around the foundation to drain waste water from around the unit 4 If the water drainage of the unit is not easy please build up the unit on a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit in o...

Page 17: ...age 16 Precaution A In case of non stacked installation figure 1 INFORMATION Spare thermistor fixing plate is delivered in the accessory bag 2 1 3 4 5 6 8 7 9 10 Suction side obstacle Obstacle is present Discharge side obstacle 1 In these cases close the bottom of the installation frame to prevent the discharged air from being bypassed Left side obstacle Right side obstacle 2 In these cases only 2...

Page 18: ... slings These slings can be fitted into specially for this purpose foreseen sleeves at the base frame Opening closing the unit Be sure to confirm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the tightening torque does not exceed 4 1 N m Accessory check Check if all unit accessories ar...

Page 19: ...ptional and insulate the pipe to prevent condensation Make sure the drain works properly Installation method for prevention of falling over If it is necessary to prevent the unit from falling over install as shown in the figure prepare all 4 wires as indicated in the drawing unscrew the top plate at the 4 locations indicated A and B put the screws through the nooses and screw them back tight A Loc...

Page 20: ...ass metallic piping make sure to insulate both materials from each other to prevent galvanic corrosion Because brass is a soft material use appropriate tooling for connecting the water circuit Inappropriate tooling will cause damage to the pipes Select piping diameter in relation to required water flow and available external static pressure of the pump The minimum required water flow for the unit ...

Page 21: ...ill lead to malfunction of the system Therefore the pre pressure should only be adjusted by an installer Connecting the water circuit Water connections must be made in accordance with the applicable legislation and the outlook diagram delivered with the unit respecting the water in and outlet NOTICE When circulation in each space heating loop is controlled by remotely controlled valves it is impor...

Page 22: ... applicable legislation In case of over pressure when using glycol be sure to connect the safety valve to a drain pan in order to recover the glycol For this purpose a knock out hole is foreseen in the backplate of the unit making it possible to connect a drain pipe to the safety valve Connecting a drain pipe is not required if no glycol is used The discharged water is then drained via the bottom ...

Page 23: ... very likely to happen and damaging the system in the process A A WARNING Electrical installation All field wiring and components must be installed by an installer and must comply with the applicable legislation DANGER ELECTRICAL SHOCK See 2 General safety precautions on page 2 WARNING All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instruc...

Page 24: ...an PS Switching power supply Q1DI Earth leakage circuit breaker R1 R2 Resistor only for V3 models R1 R4 Resistor only for W1 models R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle R6T Thermistor liquid R7T Thermistor fin only for W1 models R10T Thermistor fin only for V3 models RC Signal receiver circuit only for...

Page 25: ... WIRING DIAGRAM ONLY APPLIES TO THE HYDROMODULE SWITCH BOX 2 USE A DEDICATED POWER CIRCUIT FOR THE BACKUP HEATER AND BOOSTER HEATER NEVER USE A POWER CIRCUIT SHARED BY OTHER APPLIANCE 3 FIELD WIRING NO NC NORMAL OPEN NORMAL CLOSED SPST SINGLE POLE SINGLE THROW 4 TERMINAL STRIP CONNECTOR TERMINAL PROTECTIVE EARTH 5 DO NOT OPERATE THE UNIT BY SHORT CIRCUITING ANY PROTECTION DEVICE 6 COLOURS BLK BLAC...

Page 26: ...booster heater EKHW T M M B 1 2 6 4 12 5 7 8 9 C D F I J H G UI E 3 A K 10 11 Item Description AC DC Required number of conductors Maximum running current 1 Power supply cable for unit AC 2 GND a a Refer to nameplate on the unit 2 Power supply cable for backup heater AC 2 GND b b See table under Connection of the backup heater power supply on page 24 3 Power cable for bottom plate heater AC 2 c c ...

Page 27: ...ete connections and fix the wires so that outside forces are not applied to the terminals Specifications of standard wiring components Door 1 compressor compartment and electrical parts X1M 1 Earth leakage circuit breaker 2 Fuse Procedure 1 Using the appropriate cable connect the power circuit to the main circuit breaker as shown on the wiring diagrams inside of door 1 and in figure 2 2 Fix the ca...

Page 28: ... shall be a voltage free contact that ensure 230 V 100 mA Procedure 1 Connect the contact of first set point and second set point to the appropriate terminals as shown in the figure below 2 Fix the cables with cable ties to the cable tie mountings to ensure strain relief 3 Depending on the required pump operation set DIP switch SS2 3 and field setting F 00 See 10 3 Pump operation configuration on ...

Page 29: ... 3 way valve The 3 way valve should be fitted as such that when the 3 way valve is idle not activated the space heating circuit is selected SPST 3 wire type 3 way valve The 3 way valve should be fitted as such that when terminal ports 9 and 10 are electrified the domestic hot water circuit is selected Spring return 2 wire valve SPST 3 wire valve NC 5 X2M 6 7 M NO 5 6 X2M 7 M 9 X2M 8 10 M 9 X2M 8 1...

Page 30: ... 2 1 N L X11M 1 2 1 2 3 4 4 3 2 1 4 3 2 1 2 1 N L X11M 4 3 2 1 2 1 N L X11M BLK WHT BLK WHT 4 3 2 1 17 18 1 2 X40A A1P L N 2 4 1 3 3 L N 2 1 4 3 4 3 L N 2 1 S2S S2S S2S d 01 1 L N 2 1 3 L N 2 1 4 3 4 4 4 3 L N 2 1 S2S S2S S2S d 01 2 X11M X2M L N 5 1 When the signal is released again the voltage free contact will close and the unit will restart operation It is therefore important to leave the auto ...

Page 31: ...0 75 1 25 mm2 Maximum length 500 m NOTICE The wiring for connection is not included NOTICE The digital controller delivered in a kit has to be mounted indoors NOTICE Be careful not to distort the shape of the lower part of the digital controller by over tightening the mounting screws NOTICE When wiring run the wiring away from the power supply wiring in order to avoid receiving electric noise exte...

Page 32: ...he lifetime of the pump INFORMATION When a room thermostat is connected to the unit the heating and cooling schedule timers are never available Other schedule timers are not affected For more information on the schedule timers refer to the operation manual When a room thermostat is connected to the unit and the button or y button is pressed the centralised control indicator e will flash to indicat...

Page 33: ...2B 1 Do not forget to turn on the booster heater circuit breaker F2B in the switch box applies only to units with optional domestic hot water tank 6 Earth wiring Make sure that the earth wires have been connected properly and that the earth terminals are tightened 7 Internal wiring Visually check the switch box on loose connections or damaged electrical components 8 Fixation Check that the unit is...

Page 34: ...t or air outlet are blocked If the error code U2 is displayed on the remote controller check for voltage imbalance If the error code L4 is displayed on the remote controller it is possible that air inlet or air outlet are blocked The reversed phase protection detector of this product only works during the initialisation stage after a power reset The reversed phase protection detector is designed t...

Page 35: ...dication on the user interface is given When level 2 3 is selected the actual permission level either level 2 or level 3 is determined by the field setting 0 00 1 Weather dependent set point The weather dependent set point field settings define the parameters for the weather dependent operation of the unit When weather dependent operation is active the water temperature is determined automatically...

Page 36: ...ch the domestic hot water should be heated 2 01 Status defines whether the disinfection function is turned on 1 or off 0 2 02 Start time time of the day at which the domestic hot water should be heated 2 03 Set point high water temperature to be reached 2 04 Interval time period defining how long the set point temperature should be maintained TDHW Domestic hot water temperature TU User set point t...

Page 37: ... operation is only allowed if heat pump is out of operation range of heat pump domestic water heating mode TA 5 03 or TA 35 C or domestic hot water temperature is 2 C lower then the heat pump OFF temperature THP OFF for domestic hot water mode TDHW THP OFF 2 C Refer to setting 5 03 on page 36 6 00 on page 37 and 6 01 on page 37 Results in the most optimum coverage of domestic hot water heated by t...

Page 38: ...on is enabled and permission signal for auxiliary boiler is ON the booster heater will be restricted even when TA 5 03 See C 02 on page 41 Booster heater is always allowed during powerful and disinfection function except for the period that the backup heater operation is required for safety reasons and 4 02 1 CAUTION For optional domestic hot water tank the field setting 4 03 shall be 0 1 2 3 or 4...

Page 39: ...d and can not be modified 5 01 Equilibrium temperature outdoor temperature below which operation of the backup heater is allowed Space heating priority temperature only for EKHTS Applies only to installations with a domestic hot water tank 2 The domestic water is heated by heat pump and backup heater The space heating priority temperature field settings apply to operation of the 3 way valve and th...

Page 40: ... Example 1 Scheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot water user interface set point TDHW e g 55 C is reached B Scheduled reheat operation activated at 6 06 heat up domestic hot water untill domestic hot water reheat set point 6 07 e g 45 C is reached C Disinf...

Page 41: ...he domestic hot water set point is according to your requirements Start with a low domestic hot water storage set point and only increase if you feel that the domestic hot water supply temperature is not sufficient for your requirements this depends on your water using pattern Make sure the domestic water is not heated unnecessary Start with activating automatic storage during night default settin...

Page 42: ...st set point can be a fixed value or weather dependent The second set point heating 7 03 should be linked to the heat emitters which require the highest set point in heating mode Example fan coil units The second set point cooling 7 04 is always a fixed value It should be linked to the heat emitters which require the lowest set point in cooling mode Example fan coil units The actual second set poi...

Page 43: ...applicable in heating mode INFORMATION When heat pump is active in domestic water heating mode the delay time of booster heater is 8 03 When heat pump is not active in domestic water heating mode the delay time is 20 min The delay timer starts from booster heater ON temperature TBH ON INFORMATION By adapting the booster heater delay time versus the maximum running time an optional balance can be f...

Page 44: ...ating operation parallel connected The purpose of this function is to determine based on the outdoor temperature which heating source can will provide the space heating either the Daikin unit or an auxiliary boiler The field setting bivalent operation applies only to the unit space heating operation and the permission signal for the auxiliary boiler When the bivalent operation function is enabled ...

Page 45: ... unit is not single phase W1 the combination of setting 4 03 0 2 with bivalent operation at low outdoor temperature can result in domestic hot water shortage The bivalent operation function has no impact on the domestic water heating mode The domestic hot water is still and only heated by the unit The permission signal for the auxiliary boiler is located on the EKRP1HB digital I O PCB When it is a...

Page 46: ...r disabled 0 Space cooling permission F 01 Space cooling permission temperature defines the outdoor temperature below which space cooling is turned off Bottom plate heater control Applies only to installation with an E D B LQ unit or in case the option bottom plate heater kit is installed F 02 Bottom plate heater ON temperature defines the outdoor temperature below which the bottom plate heater wi...

Page 47: ...03 5 60 fixed 5 C 03 Set point only in combination with domestic hot water tank with built in electrical booster heater EKHW 4 03 5 70 55 80 5 C 04 Interval only in combination with domestic hot water tank without electrical booster heater EKHTS 4 03 5 60 40 60 5 min 04 Interval only in combination with domestic hot water tank with built in electrical booster heater EKHW 4 03 5 10 5 60 5 min 3 Aut...

Page 48: ...led time storage start time 1 00 0 00 23 00 1 00 hour 05 Scheduled time reheat or continuous reheat 0 OFF 0 1 2 1 06 Scheduled time reheat start time 15 00 0 00 23 00 1 00 hour 07 Domestic hot water reheat set point 45 30 50 1 C 08 Domestic hot water reheat set point hysteresis 10 2 20 1 C 7 DT for booster heater and dual set point control 00 Domestic hot water step length only in combination with...

Page 49: ...applicable Do not change the default value 0 Read only C Setup on EKRP1HB digital I O PCB 00 Solar priority mode setting 0 0 1 1 01 Alarm output logic 0 0 1 1 02 X1 X2 function Bivalent operation status or additional external backup heater 0 0 1 2 1 03 Bivalent ON temperature or additional external backup heater temperature 0 25 25 1 C 04 Bivalent hysteresis or additional external backup heater hy...

Page 50: ...ion number selection 1 1 20 1 06 Heating set point of selected action number F 05 25 0 c 15 55 1 C 07 Time of selected action number F 05 0 c 0 72 12 hour 08 Underfloor heating screed dry out program enabled disabled 0 OFF 0 1 1 09 Latest action number executed 0 0 21 Read only 0 a The storage and reheat function is only applicable in case 4 03 4 or 5 b Only possible to modify the first 3 minutes ...

Page 51: ...st the cooling operation push the h c button so the c icon is displayed To start the test run operation press the y button To test the domestic water heating operation push the v button The test run operation will start without pressing the y button 3 The test run operation will end automatically after 30 minutes or when reaching the set temperature The test run operation can be stopped manually b...

Page 52: ...example 25 C Save the new value by pressing the pr button 3 Set in F 07 Time of selected action number F 05 example 24 hours Save the new value by pressing the pr button 4 Repeat step 1 through 3 to program all the actions Consult the different actions to confirm good setting values as follows Refer to 10 10 Field settings on page 32 to know how to change the field settings 1 Set in F 05 Action nu...

Page 53: ... program enabled 1 disabled 0 is always set to 0 disable when a program has been started once This means that in case a second time an underfloor heating screed dry out program must be started then F 08 needs to be set again DANGER ELECTRIC SHOCK Before carrying out any maintenance or repair activity always switch off the circuit breaker on the supply panel remove the fuses or switch off the circu...

Page 54: ...ff NOTICE For problems related to the optional solar kit for domestic water heating refer to the troubleshooting in the installation manual of that kit POSSIBLE CAUSES CORRECTIVE ACTION The temperature setting is not correct Check the controller set point The water flow is too low Check that all shut off valves of the water circuit are completely open Check if the water filter needs cleaning Make ...

Page 55: ...ated Check that the backup heater operation status field setting 4 00 is turned on see 10 10 Field settings on page 32 Check whether or not the thermal protector of the backup heater has been activated refer to Main components 16 Backup heater thermal protector on page 11 for location of the reset button Check if booster heater and backup heater are configured to operate simultaneously field setti...

Page 56: ...r is giving the correct read out A1 Hydraulic PCB defective Contact your local dealer A5 Too high during heating operation or too low during cooling operation refrigerant temperature measured by R13T Contact your local dealer AA Backup heater thermal protector is open Reset the thermal protector by pressing the reset button refer to 5 2 Main components on page 10 for location of the reset button C...

Page 57: ... contain the latest action number executed F 08 Underfloor heating screed dry out program enabled 1 disabled 0 is always cleared to 0 disable This means that in case a second time a Underfloor heating screed dry out program must be started F 08 needs to be set again U4 Communication failure Contact your local dealer U5 Communication failure Contact your local dealer U7 Communication failure Contac...

Page 58: ......

Page 59: ......

Page 60: ...4PW67904 1 01 2011 Copyright 2011 Daikin ...

Reviews: