0 EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64603-1A – 08.2010
Operation manual
14
[C] Setup on EKRP1HB digital I/O PCB
Solar priority mode
■
[C-00] Solar priority mode setting: for information concerning
the EKSOLHW solar kit, refer to the installation manual of
that kit.
[d] Local shift value weather dependent
Local shift value weather dependent
The local shift value weather dependent
fi
eld setting is only relevant
in case weather dependent set point (see
fi
eld setting
dependent set point (heating operation only)" on page 12
selected.
■
[d-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
[E] Unit information readout
■
[E-00] Readout of the software version (example: 23)
■
[E-01] Readout of the EEPROM version (example: 23)
■
[E-02] Readout of the unit model identi
fi
cation (example: 11)
■
[E-03] Readout of the liquid refrigerant temperature
■
[E-04] Readout of the inlet water temperature
T
t
Target water temperature
T
A
Outdoor temperature
R
Range
S
Local shift value
[1-00], [1-01],
[1-02], [1-03]
Applicable
fi
eld setting of the weather dependent set
point [1]
[d-03]
Outdoor temperature range
(T
A
)
Local shift value
0
—
—
1
–2°C~2°C
2
2
4
3
–4°C~4°C
2
4
4
T
A
T
t
[1-03]
[1-00]
0
°
C
[1-01]
[1-02]
S
R
NOTICE
[E-03] and [E-04] readouts are not permanently refreshed.
Temperature readouts are updated after looping through
the
fi
eld setting
fi
rst codes again only.