D-EOMWC00803-26_01EN - 26/39
4.11.2.2 Compressor Calibrate Sensors
This page allows to adjust the sensors and transducers readings.
Setpoint/Sub-Menu
Default
Range
Description
Suction Temp
Suction Temperature current reading (includes the offset)
Suction Offset
0.0°C
Suction Temperature offset
Discharge Temp
Discharge Temperature current reading (includes the offset)
Discharge Offset
0.0°C
Discharge Temperature offset
Oil Feed Temp
Oil Feed Temperature current reading (includes the offset)
Oil Feed T Offset
0.0°C
Oil Feed Temperature offset
Oil Sump Temp
Oil Sump Temperature current reading (includes the offset)
Oil Sump T Offset
0.0°C
Oil Sump Temperature offset
Suct Press
Suction Pressure current reading (includes the offset)
Suct P Offset
0.0kPa
Suction Pressure offset
Disch Press
Discharge Pressure current reading (includes the offset)
Disc P Offset
0.0kPa
Discharge Pressure offset
Oil Feed Pres
Oil Feed Pressure current reading (includes the offset)
Oil Feed P Offset
0.0kPa
Oil Feed Pressure offset
Oil Sump Pres
Oil Sump e Pressure current reading (includes the offset)
Oil Sump P Offset
0.0kPa
Oil Sump Pressure offset
Calibrations of the Evaporator Pressure and Suction Temperature are mandatory for the applications
with negative water temperature setpoints. These calibrations have to be performed with proper
gauge and thermometer.
An improper calibration of the two instruments may generate limitation of the operations, alarms and
even damages to components.
Scheduled Maintenance
This page may contains the contact number of the Service organization taking care of this unit and the next maintenance
visit schedule.
Setpoint/Sub-Menu
Default
Range
Description
Next Maint=
Jan 2015
Schedule date for next maintenance
Support Reference=
999-999-999
Reference number or email of Service Org
4.12 About this Chiller
This page resumes all the information needed to identify the unit and the current software version installed. These
information may be required in case of alarms or unit failure
Setpoint/Sub-Menu
Default
Range
Description
Model
compressor and code name
Unit S/N=
Unit serial number
OV14-00001
BSP Ver=
Firmware version
App Ver=
Software version