CAT 258 • REBEL APPLIED ROOFTOP 22 www.DaikinApplied.com
Heating Data
Heating Data
Table 3: Gas Heat
MBH Input
200
400
600
800
1125
MBH Output
162
324
486
648
911
Staged
2
2
4
N/A
N/A
Modulating Turndown
5:1 or 100:1
5:1, 10:1, or 100:1
5:1, 10:1, or 100:1
10:1, 20:1 or 100:1
10:1, 20:1 or 100:1
Minimum Gas Inlet Pressure
7.0 in. W.C
Maximum Gas Inlet Pressure
0.5 psig
Gas Pipe Connection Size (N.P.T)
0.75
0.75
1.00
1.25
1.25
Table 4: Propane Heat
MBH Input
200
400
600
800
1125
MBH Output
162
324
486
648
911
Staged
2
2
2 or 4
N/A
N/A
Modulating Turndown
3:1
3:1 or 6:1
6:1
6:1 or 12:1
6:1 or 12:1
Minimum Gas Inlet Pressure
7.0 in. W.C
Maximum Gas Inlet Pressure
0.5 psig
Gas Pipe Connection Size (N.P.T)
0.75
0.75
1.00
1.25
1.25
Table 5: Electric Heat
Control
208V
230V
460V
575V
kW
MBH
kW
MBH
kW
MBH
kW
MBH
4 stages, SCR
30
102.0
20¹
62.4
20¹
62.7
25¹
170.6
45
153.0
40
124.7
40
125.0
45
60
204.0
55
187.1
55
188.0
75
255.0
75
249.4
75
250.2
70
255.9
90
306.0
90
311.8
90
313.4
105
357.0
110
374.3
110
375.1
115
341.2
120
408.0
130
436.5
130
438.7
135
426.5
150
498.9
150
500.1
165
564.0
160
511.8
180
625.2
180
597.1
220
750.2
230
682.4
NOTE:
All electric heaters are available with either 4 stages of control or fully modulating SCR control
1. 2 stage only
2. All heaters have a max temp rise of 60°F
Table 6: Energy Recovery Defrost Electric Pre-heater Sizes
Control
208V
230V
460V
575V
kW
MBH
kW
MBH
kW
MBH
kW
MBH
SCR
10
34.1
10
34.1
10
34.1
10
34.1
20
68.2
20
68.2
20
68.2
20
68.2
40
136.5
40
136.5
40
136.5
40
136.5
60
176.7
60
195.5
60
204.7
60
204.7
NOTE:
Electric Preheat does not come with Single Point Power if the unit is configured for primary heat electric heat.
Electric Preheat cannot be run simultaneously with mechanical cooling