The rating plate is stamped with the model number, type of gas 

and gas input rating. Make sure the unit is equipped to operate on 

the type of gas available.  The gas line installation must comply 

with local codes, or in the absence of local codes, with the latest 

edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1. 
Natural Gas Connection

1/2

3/4

1

1  1/4 1  1 /2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Pressure= .50 PSIG or less and Pressure Drop of 0.3" W.C.
(Based on 0.60 Specific Gravity Gas)

Natural Gas Capacity of Pipe

in Cubic Feet of Gas Per Hour (CFH)

Nominal Black Pipe Size (inches)

Length of

Pipe in Feet

Heating Value of Gas (BTU/Cubic Foot

CFH = 

BTUH Furnace Input

1.  Refer to the Proper Piping Practice drawing for the general 

layout at the unit. The following rules apply: 

2. 

Use black iron pipe and fittings for the supply piping.  The 

use of a flex connector and/or copper piping is permitted  as 

long as it is in agreement with local codes.

3.  Use pipe joint compound on male threads only. Pipe joint 

compound must be resistant to the action of the fuel used. 

4.  Use ground joint unions. 
5.  Install a drip leg to trap dirt and moisture before it can enter 

the gas valve. The drip leg must be a minimum of three 

inches long.

6.  Use two pipe wrenches when making connection to the gas 

valve to keep it from turning.

7. 

Install a manual shut-off valve in a convenient location 

(within six feet of unit) between the meter and the unit.

8.  Tighten all joints securely.
9.  The unit must be connected to the building piping by one of 

the following methods:

• 

Rigid metallic pipe and fittings

• 

Semirigid metallic tubing and metallic fittings (Aluminum 

alloy tubing must not be used in exterior locations)

• 

Listed gas appliance connectors used in accordance with 

the terms of their listing that are completely in the same 

room as the equipment

• 

In the prior two methods above the connector or tubing 

must be protected from physical and thermal damage. 

Aluminum alloy tubing and connectors must be coated to 

protect against external corrosion when in contact with 

masonry, plaster or insulation or are subject to repeated 

wettings by liquids (water - not rain water, detergents or 

sewage)

Proper Piping Practice 

NOTE: 

 The unit gas supply entrance is factory sealed with plugs.  

Keep plugs in place until gas supply is ready to be installed.  Once 

ready, replace the plugs with the supplied grommets and install 

gas supply line.

Gas Piping Checks

WARNING

To prevent property damage or personal injury 

due to fire, the following instructions must 

be performed regarding gas connections and 

pressure testing:

• 

The unit and its gas connections must be 

leak tested before fire, never use a match or 

open flame to test for leaks. Never exceed 

specified pressures for testing. Higher 

pressure may damage gas valve and cause 

overfiring which may result in premature 

heat exchanger failure. 

• 

This unit and its shut-off valve must be 

disconnected from the gas supply during any 

pressure testing of that system at pressures 

in excess of 1/2 PSIG (3.48 kPA).

• 

This unit must be isolated from the gas 

supply system by closing its manual shut-off 

valve during any pressure testing of the gas 

supply piping system at test pressures equal 

to or less than 1/2 PSIG (3.48 kPA).

WARNING

To avoid property damage or personal injury, be 

sure there is no open flame in the vicinity during 

air bleeding.

There will be air in the gas supply line after testing for leaks on a 

new installation. Therefore, the air must be bled from the line by 

loosening the ground joint union until pure gas is expelled. Tighten 

union and wait for five minutes until all gas has been dissipated in 

the air. Be certain there is no open flame in the vicinity during air 

bleeding procedure. The unit is placed in operation by closing the 

main electrical disconnect switch for the unit.

Summary of Contents for DP14U Series

Page 1: ...NTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is...

Page 2: ...ors 16 ECM Motors 16 Limit Check 16 Unit Shutdown 17 Cooling Startup 17 Compressor Protection Devices 17 Refrigerant Charge Check 17 Superheat 17 Subcooling 17 TROUBLESHOOTING 18 Ignition Control Erro...

Page 3: ...d Service organization right away Adhere to the following warnings and cautions when installing adjusting altering servicing or operating the furnace To ensure proper installation and operation thorou...

Page 4: ...ies la lettre cela peut entra ner la mort de graves blessures ou des dommages mat riels Ne jamais v rifier la pr sence de fuites de gaz au moyen d une flamme nue V rifier tous les raccords en utilisan...

Page 5: ...de ocurrir si un mon xido de carbono sigue operando en el lugar cerrado disposi vo que produce General Information WARNING To prevent property damage personal injury or death due to fire explosions sm...

Page 6: ...cord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes doivent tre suivies pour chacun des appareils...

Page 7: ...n proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not al...

Page 8: ...ith the National Roofing Contractors Association Manual Lower unit carefully onto roof mounting curb While rigging unit center of gravity will cause condenser end to be lower than supply air end Riggi...

Page 9: ...connectors used in accordance with the terms of their listing that are completely in the same room as the equipment In the prior two methods above the connector or tubing must be protected from physi...

Page 10: ...5 2 WIRE CONNECTS TO ECONOMIZER PLF PIN 2 24 Volt Dehumidistat Wiring For DP16UM Only The optional usage of a dehumidistat allows the unit s circulator blower to operate at a slightly lower speed app...

Page 11: ...0 10 8 8 6 6 WIRING TABLE Circulating Air and Filters Airflow Conversion Units can easily be converted from horizontal to down discharge airflow delivery In down discharge or high static installations...

Page 12: ...ity panel SCREEN HOOD LOWER FLUE HOOD LIP Installation Combustion Air Intake Hood 1 Locate the second hood 2 Using the three screws provided attach the hood with the opening facing down to the heat ex...

Page 13: ...rtup This unit is equipped with an electronic ignition device to automatically light the main burners It also has a power vent blower to exhaust combustion products On new installations or if a major...

Page 14: ...inlet pressure tap or the gas piping drip leg See White Rodgers 36J22Y 204 gas valve for location of inlet pressure tap 5 Turn ON the gas supply 6 Turn On power and operate the furnace and all other g...

Page 15: ...nly Check To measure the gas input use a gas meter and proceed as follows 1 Turn off gas supply to all other appliances except the unit 2 With the unit operating time the smallest dial on the meter fo...

Page 16: ...ING Two Stage Models NOTE Heating airflow must be adjusted to provide the temperature rise shown on rating plate ECM Motors The DP16UM models are equipped with ECM circulating blower motors ECM circul...

Page 17: ...on line After superheat is adjusted it is recommended to check unit sub cooling at the condenser coil liquid line out For charge adjustments see superheat and sub cooling charts show for each model Su...

Page 18: ...the adjustment screw and turn it clockwise in to increase superheat or counterclockwise out to decrease superheat Replace adjustment cap Wait a minimum of 10 minutes between adjustments to allow time...

Page 19: ...eration when flame is no longer sensed Low Flame Signal Under some conditions the fuel or air supply can create a nearly invisible coating on the flame sensor This coating acts as an insu lator causin...

Page 20: ...he microamp signal should be stable and in the range of 5 10 microamps DC Flue Passages Qualified Servicer Only At the start of each heating season inspect and if necessary clean the unit flue passage...

Page 21: ...ter Circulator Blower Motor Ignition Control Compressor Induced Draft Blower Condenser Coil Pressure Sensor Condenser Fan Blade Pressure Sensor Hose Condenser Fan Motor Spark Igniter Module Contactor...

Page 22: ...LASH RETRIES EXCEEDED RED 1 HOUR FIXED 10 FLASHES HIGH LIMIT SWITCH RECOVERY TIMER EXPIRED RED 1 HOUR OR HARD LOCKOUT RAPID FLASH CLEAR ERROR HISTORY GREEN N A 2 FLASHES PRESSURE SENSOR NULL ERROR RED...

Page 23: ...23 APPENDIX Unit Dimensions...

Page 24: ...CONNECTOR PLS PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER RELAY TR TRANSFORMER VM VENT MOTOR WIRE CODE BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW BK BL BR GR GY...

Page 25: ...EVAPORATOR MOTOR FC FAN CAPACITOR FPS FREEZE PROTECTION SWITCH FS FLAME SENSOR GND EQUIPMENT GROUND GPT GAS PRESSURE TRANSDUCER GV GAS VALVE HPS HIGH PRESSURE SWITCH IGN IGNITOR PLF FEMALE PLUG CONNE...

Page 26: ...TRANSDUCER GV GAS VALVE HPS HIGH PRESSURE SWITCH IGN IGNITOR LPS LOW PRESSURE SWITCH PLF FEMALE PLUG CONNECTOR PLM MALE PLUG CONNECTOR PLS PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER REL...

Page 27: ...TON t 180s R1 Y1 BL Y2 R2 PU 3 5 4 3 2 1 YL GR LINE VOLTAGE 208 230V 1PH 60Hz R C RD L1 L2 G R W Y C 5 4 3 2 1 GR COM TR BR RD BK RD YL OR BR WH BK OR YL BR 1 2 BK WH VM GR GR GR BL BL HPS LPS PU R C...

Page 28: ...C COMPRESSOR CONTACTOR CCH CRANKCASE HEATER CM CONDENSER MOTOR COMP COMPRESSOR CS COMP SOLENOID 2ND STG COOLING EM EVAPORATOR MOTOR FS FLAME SENSOR GND EQUIPMENT GROUND GPT GAS PRESSURE TRANSDUCER GV...

Page 29: ...instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant NOTE Roof overhang should be no more than 36 Reco...

Page 30: ...81 280 43 411 155 58 950 353 1177 468 0 8 343 161 717 285 44 343 161 X 879 360 1104 478 DP14UM3606041 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COO...

Page 31: ...49 0 6 759 200 945 249 53 945 249 1587 551 1738 660 0 7 697 206 867 264 56 867 264 1544 558 1689 664 0 8 632 216 806 271 61 806 271 1495 572 1634 676 DP14UM6108041 Rise Range 30 60 E s p T1 FAN ONLY S...

Page 32: ...660 0 7 697 206 867 264 56 867 264 1544 558 1689 664 0 8 632 216 806 271 61 806 271 1495 572 1634 676 DP14UM6108043 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T4 HIGH STAGE COOLING SPEE...

Page 33: ...heating application SWITCH 1 SWITCH 2 HEAT CFM SWITCH 5 DP16UM CFM OUTPUT AND DIP SWITCH SETTINGS CFM Output for DIP Switches 1 2 Heating CFM Output for DIP Switches 5 6 Cooling DP16UM3608041 MODEL S...

Page 34: ...mpressor The compressor motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified installer or...

Page 35: ...tural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1and L2Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressu...

Page 36: ...orm on the following link https daikincomfort com contact us You can also scan the QR code on the right to be directed to the feedback page Our continuing commitment to quality products may mean a cha...

Reviews: