To remove filters from an external filter rack in an upright 

upflow  installation,  follow  the  directions  provided  with 

external filter rack kit.

Horizontal Unit Filter Removal

Filters  in  horizontal  installations  are  located  in  the  central 

return register or the ductwork near the furnace.

To remove:

1.  Turn OFF electrical power to furnace.

2.  Remove filter(s) from the central return register or 

ductwork.

3.  Replace filter(s) by reversing the procedure for 

removal.

4.  Turn ON electrical power to furnace.

Media Air Filter or Electronic Air Cleaner 

Removal

Follow the manufacturer’s directions for service.

Burners

Visually  inspect  the  burner  flames  periodically  during  the 

heating season. Turn on the furnace at the thermostat and 

allow  several  minutes  for  flames  to  stabilize,  since  any 

dislodged  dust  will  alter  the  flames  normal  appearance. 

Flames  should  be  stable,  quiet,  soft,  and  blue  (dust  may 

cause orange tips but they must not be yellow).  They should 

extend  directly  outward  from  the  burners  without  curling, 

floating, or lifting off.  Flames must not impinge on the sides 

of the heat exchanger firing tubes.

Burner Flame

Figure 43

Induced Draft and Circulator Blowers

The bearings in the induced draft blower and circulator blower 

motors are permanently lubricated by the manufacturer. No 

further  lubrication  is  required.  Check  motor  windings  for 

accumulation of dust which may cause overheating. Clean 

as necessary.

Condensate Trap and Drain System (Qualified 

Servicer Only)

Annually  inspect  the  drain  tubes,  drain  trap,  and  field-

supplied drain line for proper condensate drainage. Check 

drain system for hose connection tightness, blockage, and 

leaks.  Clean or repair as necessary.

Flame Sensor (Qualified Servicer Only)

Under some conditions, the fuel or air supply can create a 

nearly  invisible  coating  on  the  flame  sensor.  This  coating 

acts as an insulator causing a drop in the flame sense signal.  

If the flame sense signal drops too low the furnace will not 

sense flame and will lock out. The flame sensor should be 

carefully cleaned by a qualified servicer using emery cloth 

or  steel  wool.  Following  cleaning,  the  flame  sense  signal 

should be as indicated in the Specifications Sheet.

Flue Passages (Qualified Servicer Only)

The heat exchanger flue passageways should be inspected 

at the beginning of each heating season.  

BEFORE LEAVING AN INSTALLATION

• 

  Cycle the furnace with the thermostat at least three 

times. Verify cooling and fan only operation.

• 

  Review the Owner’s Manual with the homeowner and 

discuss proper furnace operation and maintenance.

• 

  Leave literature packet near furnace.

REPAIR AND REPLACEMENT PARTS

• 

  When ordering any of the listed functional parts, be 

sure to provide the furnace model, manufacturing, and 

serial numbers with the order.

• 

  Although only functional parts are shown in the parts 

list, all sheet metal parts, doors, etc. may be ordered 

by description.

• 

  Parts are available from your distributor.

Functional Parts List-

Gas Valve 

 

Blower Motor 

Gas Manifold   

Blower Wheel

Natural Gas Orifice 

Blower Mounting Bracket 

Propane Gas Orifice 

Blower Cutoff

Igniter   

 

Blower Housing 

Flame Sensor   

Pressure Switch

Rollout Limit Switch 

Door Switch 

Primary Limit Switch 

Auxiliary Limit Switch

Coil Front Cover 

Integrated Control Module 

Transformer 

 

Door Switch

Induced Draft Blower   

Heat Exchanger with Recuperator Coil

Summary of Contents for DM92SS

Page 1: ...THIS SYMBOL AS A SAFETY PRECAUTION TABLE OF CONTENTS Safety Considerations 3 Shipping Inspection 4 Electrostatic Discharge ESD Precautions 5 To The Installer 5 Product Application 5 Location Requirem...

Page 2: ...26 High Altitude Derate 26 Propane Gas Conversion 26 Gas Piping Connections 26 Gas Piping Checks 29 Propane Gas Tanks and Piping 29 Circulating Air Filters 29 Duct work Air Flow 29 Checking Duct Stati...

Page 3: ...gas fired furnace for installation in a residential garage must be installed as specified in the LOCATION REQUIREMENTS AND CONSIDERATIONS section of this manual This furnace may be used as a construc...

Page 4: ...electrical shock the furnace must be located to protect the electrical components from water Drain trap must be primed at time of installation Trap is internally partitioned add water to both inlet po...

Page 5: ...ith static electricity i e do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discha...

Page 6: ...and the service area around the unit must have flooring To ensure proper furnace operation install operate and maintain the furnace in accordance with these installation and operation instructions al...

Page 7: ...above substances This protects the non direct vent furnace from airborne contaminants To ensure that the enclosed non direct vent furnace has an adequate supply of combustion air vent from a nearby u...

Page 8: ...nting system may be too large to properly vent the remaining attached appliances POSITION SIDES REAR FRONT BOTTOM FLUE TOP Upflow 0 0 3 C 0 1 Horizontal 6 0 3 C 0 6 C If placed on combustible floor fl...

Page 9: ...ant l un des essais d crits ci dessus des correctifs doivent tre apport s au syst me de ventilation conform ment au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou au Code d installation du gaz natur...

Page 10: ...tal counterflow furnaces return ductwork must be attached to the basepan top end of the blower compartment NOTE Ductwork must never be attached to the back of the furnace Contact your distributor for...

Page 11: ...gy content difference between natural and propane gas High Stage Low Stage Natural None 45 3 5 w c 1 9 w c None Propane LPM 07 1 1 25mm 10 0 w c 6 0 w c None Gas Altitude Kit Orifice Manifold Pressure...

Page 12: ...aterials and Joining Methods Two three inch nominal diameter PVC Schedule 40 pipe meeting ASTM D1785 PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used...

Page 13: ...es above ground level or the anticipated snow level Vent terminations non direct and direct vent must terminate at least 3 feet above any forced air inlet located within 10 feet NOTE This provision do...

Page 14: ...pipe Secure vent flue pipe directly into the furnace fitting with the appropriate glue Alternately a small section of 2 pipe may be glued in the furnace socket and a rubber coupling installed to allow...

Page 15: ...er outlet 5 Install cut end of the flanged section and connect to inducer with rubber coupling supplied with furnace Install screws removed in step 1 securing flange to cabinet MODEL PIPE SIZE 1 2 3 4...

Page 16: ...per material manufacturers specifications to prevent separation and flue gas leaks Figure 11 Insert flange Cut 2 long R 000142 F Figure 9 CUT HERE Figure 10 Vent Flue Pipe Cuts Upflow Horizontal model...

Page 17: ...secured to the combustion air intake to prevent inadvertent blockage The tee used in the vent flue termination must be included when determining the number of elbows in the piping system Vent Flue Pi...

Page 18: ...r specific details on termination construction For details concerning connection of pipes to the furnace refer to the Vent Flue Pipe and Combustion Pipe Standard Furnace Connections or Alternate Furna...

Page 19: ...ecifications Condensate Drain Lines Drain Trap Acondensing gas furnace achieves its high level of efficiency by extracting heat from the products of combustion to the point where condensation takes pl...

Page 20: ...ay be added in the area shown in Figure 21 Any unused cabinet opening must be sealed Do not allow drain hose to sag or trap water Figure 21 Drain Exiting Right Side 1 Locate and Install the 45 pipe ho...

Page 21: ...the top mounting tabs of the trap into the two predrilled holes in the side of the cabinet 9 Refer to Field Supplied Drain section for instructions on field supplied installed drain on outlet of furn...

Page 22: ...he non grommet end Discard the section without the grommet 5 Insert the cut end of tube 5 through the lower cabinet drain hole 6 Insert 100 degree elbow in the cut end of hose 5 7 Locate hose 6 Using...

Page 23: ...ses needed for installation and install per the following directions 1 Remove the drain trap and factory installed drain tube assemblies 2 Remove two 1 plugs from right side of cabinet 3 Draining the...

Page 24: ...n hole 12 Insert 100 elbow in hose 5 and secure with a red clamp 13 Locate hose 4 and cut a cut off a 4 straight section and discard the radius end 14 Connect the 4 straight section of hose 4 to the 1...

Page 25: ...low NOTE Wire routing must not to interfere with circulator blower operation filter removal or routine maintenance Junction Box Relocation WARNING HIGH VOLTAGE To avoid personal injury or death due to...

Page 26: ...t not be exceeded to prevent unit overfiring High Altitude Derate When this furnace is installed at high altitude the appropriate High Altitude orifice kit must be applied This is required due to the...

Page 27: ...1 8 NPT pipe plug fitting accessible for test gauge connection immediately upstream of the gas supply connection to the furnace Always use a back up wrench when making the connection to the gas valve...

Page 28: ...ation Gas Valve Burners Manual Shut Off Valve upstream from ground joint pipe union Drip Leg Grommet in Standard Gas Line Hole Ground Joint Pipe Union Ground Joint Pipe Union NOTE Union may be inside...

Page 29: ...de NSCNGPIC CAN CSA B149 1 15 For satisfactory operation propane gas pressure must be 10 WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on thre...

Page 30: ...an air conditioner coil or Electronic Air Cleaner is used in conjunction with the furnace the readings must also include theses components as shown in the following drawing 4 Consult proper tables for...

Page 31: ...e furnace The installation of a centrally installed air cleaner cabinet or a return duct filter installation may offer more practicality Clean Comfort brand MERV 11 air cleaners have 5 media filters a...

Page 32: ...t angle 2000 CFM 20 in X 25 in x 5 AM11 2025 5RA AM11 5RA Bottom return platform 2000 CFM 20 in X 25 in x 5 AM11 2832 5PP Bottom return platform 2000 CFM 20 in X 25 in x 5 AM11 2843 5PP AM11 5 2 X 160...

Page 33: ...ances on the same gas supply line 4 Measure furnace gas supply pressure with burners firing Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table If supply pressure...

Page 34: ...pplier if additional input rate adjustment is required 4 Turn ON gas to and relight all other appliances turned off in step 1 Be certain that all appliances are functioning properly and that all pilot...

Page 35: ...als 4 Connect all unused blower motor leads to the PARK terminals on the integrated control module Any leads not connected to the PARK terminals must be taped 5 Turn ON power to furnace 6 Verify prope...

Page 36: ...heat exchanger compartment temperatures It is a normally closed electrically automatic reset temperature activated sensor The limit guards against overheating as a result of insufficient conditioned...

Page 37: ...following a one hour lockout period 2 Manual power interruption Interrupt 115 volt power to the furnace 3 Manual thermostat cycle Lower the thermostat so that there is no longer a call for heat for 1...

Page 38: ...condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as necessary Flame Sensor Qualified Servicer Only Under some conditions the fuel or air supply c...

Page 39: ...Loose or improperly connected wiring Pressure switch circuit not closed Induced draft blower isoperating Induced draft blower runs continuously with no further furnace operation Integrated control mo...

Page 40: ...peration Rollout limit open Integrated control module fuse is blown Check burners for proper alignment Check flue and air inlet piping for blockage proper length elbows and termination Correct as nece...

Page 41: ...N A 1203 N A 1158 N A 1111 1058 932 HIGH 5 0 2235 38 2166 39 2110 40 2021 42 1956 44 1855 1740 1618 MED 4 0 1955 44 1921 44 1860 46 1808 47 1746 49 1645 1572 1461 MED LO 3 5 1658 51 1634 52 1590 54 15...

Page 42: ...OX 1 TO115 VAC 1 60HZ OR ID BLOWER PRESSURE SWITCH HEAT H GND WH RD WH GND BURNER COMPARTMENT BLOWER COMPARTMENT N O COOL H BK HI BR BR CAPACITOR YL WH CONTROL PRIMARY LIMIT AUTO RESET BL PU MANUAL RE...

Page 43: ...nimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less...

Page 44: ...se DB F Delta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG...

Page 45: ...45 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 46: ...46 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 47: ...47 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 48: ...e protec on of the standard warranty registering your product is a rela vely short process and en tles you to addi onal warranty protec on except that failure by California and Quebec residents to reg...

Reviews: