IM 1339-1 • DKN509 Wireless Thermostat
www.DaikinApplied.com
Outputs
6 x Relays rated for 24V DC/1A
3 x 0-10V or 4-20mA Analog outputs
2.8" 240x320 pixel TFT display
Onboard Sensors
CO2 sensor with a range of 0 - 40,000 ppm, accuracy of +/-30ppm
(0 - 5000ppm, 25C). Drift +/- 50ppm over 400 -5000ppm range
over a lifetime of 15 years
VOC sensor with derived e-CO2; Typical accuracy: 15% of
measured value; TVOC: 0 - 60,000 ppb
Occupancy sensor based on passive infrared (PIR) with detection
range of 4m with 15-degree angle
Light sensor - Ambient light sensor • <100 LUX resolution • High-
accuracy UV index sensor • Matches erythermal curve
Temperature sensor: Typical accuracy of +/- 0.2°C
Humidity sensor: Typical accuracy of +/- 2% RH
Sound sensor with 40-120dB response for 100Hz to 10KHz
PM2.5, PM10 sensor (optional). Detection range of 0-1000µg/m3
and accuracy of +/-10µg/m3 (PM2.5, 0-100µg/m3) or +/-25µg/m3
(PM10, 0-100µg/m3). Maximum long-term mass concentration
precision limit drift:
•
0 to 100 µg/m3 ±1.25 µg/m3/year
100 to 1000 µg/m3 ±1.25 % mV/year
WARNINGS AND DISCLAIMERS
The following compiles a list of warnings and notes associated with the installation and
operation of this kit. Make sure to follow these warnings, as well as always having
properly trained technicians and electricians, or Daikin-authorized technicians perform
work.
⚠
CAUTION
Failure to wire devices for power with the correct polarity when using a shared
transformer may result in damage to any device powered by the shared transformer.
Turn off the power before wiring. Never connect or disconnect the wiring with the
power turned on. Do NOT allow live wires to touch the circuit boards.
Do not connect the front to the back plate assembly when the power is ON.
Install in accordance with all state and local codes.