IM 1339-1 • DKN509 Wireless Thermostat 

www.DaikinApplied.com 

 

Outputs 

 

6 x Relays rated for 24V DC/1A 
3 x 0-10V or 4-20mA Analog outputs 
2.8" 240x320 pixel TFT display 

Onboard Sensors 

 

CO2 sensor with a range of 0 - 40,000 ppm, accuracy of +/-30ppm 

(0 - 5000ppm, 25C). Drift +/- 50ppm over 400 -5000ppm range 

over a lifetime of 15 years 
VOC sensor with derived e-CO2; Typical accuracy: 15% of 

measured value; TVOC: 0 - 60,000 ppb 
Occupancy sensor based on passive infrared (PIR) with detection 

range of 4m with 15-degree angle 
Light sensor - Ambient light sensor • <100 LUX resolution • High-

accuracy UV index sensor • Matches erythermal curve 
Temperature sensor: Typical accuracy of +/- 0.2°C 
Humidity sensor: Typical accuracy of +/- 2% RH 
Sound sensor with 40-120dB response for 100Hz to 10KHz 
PM2.5, PM10 sensor (optional). Detection range of 0-1000µg/m3 

and accuracy of +/-10µg/m3 (PM2.5, 0-100µg/m3) or +/-25µg/m3 

(PM10, 0-100µg/m3). Maximum long-term mass concentration 

precision limit drift: 

 

0 to 100 µg/m3 ±1.25 µg/m3/year 

100 to 1000 µg/m3 ±1.25 % mV/year 

 

WARNINGS AND DISCLAIMERS 

The following compiles a list of warnings and notes associated with the installation and 

operation of this kit. Make sure to follow these warnings, as well as always having 

properly trained technicians and electricians, or Daikin-authorized technicians perform 

work. 
 

 CAUTION 

Failure to wire devices for power with the correct polarity when using a shared 

transformer may result in damage to any device powered by the shared transformer.  
Turn off the power before wiring. Never connect or disconnect the wiring with the 

power turned on. Do NOT allow live wires to touch the circuit boards. 
Do not connect the front to the back plate assembly when the power is ON. 
Install in accordance with all state and local codes.  

 

 