background image

SERVICING

27

C L G N

1 2 3 4 5

High Voltage
Connections

3/16"

Low Voltage Connections

1/4”

EEM  MOTOR CONNECTIONS

S-17 CHECKING COMPRESSOR WINDINGS

WARNING

Hermetic compressor electrical terminal venting can
be dangerous. When insulating material which
supports a hermetic compressor or electrical terminal
suddenly disintegrates due to physical abuse or as a
result of an electrical short between the terminal and
the compressor housing, the terminal may be
expelled, venting the vapor and liquid contents of the
compressor housing and system. 

If the compressor terminal PROTECTIVE COVER and
gasket (if required) are not properly in place and se-
cured, there is a remote possibility if a terminal vents, that
the vaporous and liquid discharge can be ignited, spout-
ing flames several feet, causing potentially severe or fatal
injury to anyone in its path.

This discharge can be ignited external to the compressor
if the terminal cover is not properly in place and if the
discharge impinges on a sufficient heat source.

Ignition of the discharge can also occur at the venting
terminal or inside the compressor, if there is sufficient
contaminant air present in the system and an electrical
arc occurs as the terminal vents.

Ignition cannot occur at the venting terminal without the
presence of contaminant air, and cannot occur externally
from the venting terminal without the presence of an
external ignition source.

Therefore,  proper evacuation of a hermetic system is
essential at the time of manufacture and during servicing.

To reduce the possibility of external ignition, all open
flame, electrical power, and other heat sources should be
extinguished or turned off prior to servicing a system.

S-17A RESISTANCE TEST

Each compressor is equipped with an internal overload.

The line break internal overload senses both motor amperage
and winding temperature.  High motor temperature or amper-
age heats the disc causing it to open, breaking the common
circuit within the compressor on single phase units.

Heat generated within the compressor shell, usually due to
recycling of the motor, high amperage or insufficient gas to
cool the motor, is slow to dissipate.  Allow at least three to four
hours for it to cool and reset, then retest.

HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing this unit. Multiple power
sources may be present. Failure to do so
may cause property damage, personal injury
or death.

1. Remove the leads from the compressor terminals.

See warnings S-17  before removing compressor
terminal cover.

2. Using an ohmmeter, test continuity between terminals S-

R, C-R, and C-S, on single phase units or terminals T1,
T2 and T3, on 3 phase units.

S

R

C

COMP

OHMMETER

TESTING COMPRESSOR WINDINGS

If either winding does not test continuous, replace the
compressor.

NOTE: 

 If an open compressor is indicated, allow ample time

for the internal overload to reset before replacing compres-
sor.

S-17B GROUND TEST

If fuse, circuit breaker, ground fault protective device, etc.,
has tripped, this is a strong indication that an electrical
problem exists and must be found and corrected. The circuit
protective device rating must be checked, and its maximum
rating should coincide with that marked on the equipment
nameplate.

Summary of Contents for DCH048 SERIES

Page 1: ...or personal injury due to improper service procedures or services performed by an unqualified person RSDX6412006r1 November2016 DCC Cooling DCH Heat Pumps Commercial Package Units with R 410A Refriger...

Page 2: ...856 1821 Not a technical assistance line for dealers Outside the U S call 1 713 861 2500 Not a technical assistance line for dealers Your telephone company will bill you for the call IMPORTANTINFORMA...

Page 3: ...cover is not properly in place a venting terminal may discharge a combination of a hot lubricating oil and refrigerant b flammable mixture if system is contaminated with air inastreamofspraywhichmayb...

Page 4: ...ons 120 10 Tons 060 5 Tons 180 15 Tons 072 6 Tons 240 20 Tons B Belt Drive 090 7 Tons D Direct Drive Nominal Heating Capacity Gas Electric A C H P Factory Installed Electric Heat 180 180 000 BTU h XXX...

Page 5: ...ikin Commercial Package Heat Pump Multiposition heat pump units 400V 3 Phase 60 Hz Direct Drive Initial release of Daikin branded models DCH048XXX6DXXXAD DCH060XXX6DXXXAC Daikin Commercial Package Hea...

Page 6: ...irect Drive Initial release of 4 5 Ton Daikin branded models DCC 048 060 XXXBDXXXAA Daikin Commercial Package Cooler Multiposition cooling 400V 3 Phase 60 Hz Direct Drive Initial release of Daikin bra...

Page 7: ...f used do not allow the econo mizer manualfreshairdamper motorizedfreshairdamper to become blocked by snow or debris In some climates or locations it may be necessary to elevate the unit to avoidthese...

Page 8: ...esupplyand returnductopeningareasasdamagetotheunitmightoccur NOTE The unit and curb accessories are designed to allow vertical duct installation before unit placement Duct installation after unit plac...

Page 9: ...on unit for details Main power wiring should be sized for the minimum wire ampacity shown on the unit s database Size wires in accordance with the ampacity tables in Article 310 of the NationalElectri...

Page 10: ...pped LOW VOLTAGE CONTROL WIRING 1 A 24V thermostat must be installed for unit operation It may be purchased with the unit or field supplied Ther mostatsmaybeprogrammableorelectromechanicalas required...

Page 11: ...l Package Cooling or Package Gas RestrictorOrificeAssemblyinCoolingOperation In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the center...

Page 12: ...SYSTEM OPERATION 12 Typical Heat Pump System in Cooling Indoor Coil Accumulator Outdoor Coil Reversing Valve Energized Indoor Coil Accumulator Outdoor Coil Reversing Valve De Energized DCH XXX XXX...

Page 13: ...eaning is neces sary to prevent this build up from plugging the drain STARTUP ADJUSTMENTS AND CHECKS HIGH VOLTAGE OND THE FRAME OF THIS UNIT TO THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING T...

Page 14: ...aceajumperwireacrossterminals R and G at TB1 terminal block Close disconnect switch evaporator fan motor will operate so RPM can be checked For gas heat units the airflow must be adjusted so that the...

Page 15: ...perates properly NOTE Ifoutdoorthermostatsareinstalledtheoutdoor ambient must be below the set point of these thermo stats for the heaters to operate It may be necessary to jumper these thermostats to...

Page 16: ...o a feeder tube enteringtheoutdoorcoil Defrosttimingperiodsof30 60and 90 minutes may be selected by connecting the circuit board jumper to 30 60 and 90 respectively Accumulation of time for the timing...

Page 17: ...anual 14 Check condenser fans and tighten set screws FILTERS CAUTION TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERN...

Page 18: ...acts S 7 Open Control Circuit Test Control Circuit with Voltmeter S 4 Low Voltage Test Voltage S 1 Faulty Evap Fan Motor Repair or Replace S 16 Shorted or Grounded Fan Motor Test Motor Windings S 16 I...

Page 19: ...hecking Fan Blower Motor Windings PSC Motors 26 S 16D Checking EEM Motors 26 S 17 Checking Compressor Windings 27 S 17A ResistanceTest 27 S 17B GroundTest 27 S 17D OperationTest 28 S 18 Testing Crankc...

Page 20: ...oltage tabulation as shown If the voltage falls below the minimum voltage checkthelinewiresize Longrunsofundersizedwirecan causelowvoltage Ifwiresizeisadequate notifythelocal power company in regards...

Page 21: ...ir or replace as necessary S 3B COOLING ANTICIPATOR The cooling anticipator is a small heater resistor in the thermostat During the off cycle it heats the bimetal elementhelpingthethermostatcallforthe...

Page 22: ...TACTOR CONTACTS SINGLEPHASE HIGH VOLTAGE Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury...

Page 23: ...ard for single phase gas models For3phaseandbeltdrivemodels theprocedurefortesting the fan relay contacts will be the same as checking the compressor contactor contacts See section S 8 DCC DCH TheElec...

Page 24: ...roximately22PSIG Itwillautomaticallycut in close at approximately 50 PSIG Test for continuity using a VOM and if not as above replace the control S 12 CHECKING HIGH PRESSURE CONTROL HIGH VOLTAGE Disco...

Page 25: ...ype rather than metallized polypropylene as used in the run capacitor A switching device must be wired in series with the capacitor to remove it from the electrical circuit after the compressor starts...

Page 26: ...cable 2 Check the continuity between each of the motor leads 3 Touch one probe of the ohmmeter to the motor frame ground and the other probe in turn to each lead Ifthewindingsdonottestcontinuousorarea...

Page 27: ...reandduringservicing To reduce the possibility of external ignition all open flame electricalpower andotherheatsourcesshouldbe extinguished or turned off prior to servicing a system S 17A RESISTANCE T...

Page 28: ...re HIGH VOLTAGE Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death 1 Remove unit wi...

Page 29: ...cross the terminals DFT and R at defrost control board 2 Connectjumperacrosstestpinsondefrostcontrolboard 3 Set thermostat to call for heating System should go into defrost within 21 seconds 4 Immedia...

Page 30: ...elementisprotectedwithanautomatic rest limit control connected in series with each element to prevent overheating of components in case of low airflow This limit control will open its circuit at appro...

Page 31: ...e vacuum in the system NOTE Neverusethesystemcompressorasavacuumpump or run when under a high vacuum Motor damage could occur Do not front seat the service valve s with the compressor open with the su...

Page 32: ...rant in the charging cylinder hose and will definitely have liquid in the liquid hose Reseat the liquid line core Slowly open the high side manifold valve and transfertheliquidrefrigerantfromtheliquid...

Page 33: ...rant gas is considered superheated when its tem perature is higher than the saturation temperature corre spondingtoitspressure Thedegreeofsuperheatequalsthe degrees of temperature increase above the s...

Page 34: ...60 8 6 162 0 57 0 264 0 87 4 366 0 110 4 468 0 129 0 600 0 149 0 62 10 0 164 0 57 7 266 0 87 9 368 0 110 8 470 0 129 3 604 0 149 5 64 11 3 166 0 58 4 268 0 88 4 370 0 111 2 472 0 129 7 608 0 150 1 66...

Page 35: ...0 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94 384 106 104 1...

Page 36: ...evacuate and recharge S 113 OVERCHARGE OF REFRIGERANT An overcharge of refrigerant is normally indicated by an excessively high head pressure Anevaporatorcoil usinganexpansionvalvemeteringdevice willb...

Page 37: ...r a minimum of twelve 12 hours and recheck the pressure drop across the drier Pressure drop should not exceed 6 PSIG 7 Continue to run the system for several days repeatedly checking pressure drop acr...

Page 38: ...RE RISE S 205 CHECKING BELT TENSION NOTE Sectiononhighstatictablesmayrequireafieldmotor change BELT DRIVE MODELS ONLY TENSION AND ALIGNMENT ADJUSTMENT Check drive for adequate run in belt tension Corr...

Page 39: ...heckhasbeen made S 207 MOTOR SHEAVE ADJUSTMENT VL VM 2VP VARIABLE PITCH KEY TYPE MOTOR SHEAVES Thedrivinganddrivenmotorsheavesshouldbeinalignment with each other and the shafts parallel VL VM SHEAVES...

Page 40: ...40 DCC COMMERCIAL 3 6 Ton PackagedAir Conditioner Unit WIRING DIAGRAMS...

Page 41: ...INAL AT LEAST 105 C USE COPPER CONDUCTOR ONLY 2 TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW LEADS FROM 3 AND 4 TO 4 AND 5 IF BOTH LEADS ARE ENERGIZED THE HIGHER SPEED SETTING IS USED 3 USE...

Page 42: ...NOTES 1 REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL AT LEAST 105 C USE COPPER CONDUCTOR ONLY 2 TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW LEADS FROM 3 AND 4 TO 4 AN...

Page 43: ...ELAY EVAPORATOR MOTOR RELAY RELAY EVAPORATOR MOTOR FAN CAPACITOR EQUPIMENT GROUND HIGH PRESSURE SWITCH HIGH VOLTAGE DEFROST RELAY LOW PRESSURE SWITCH LOW VOLTAGE DEFROST RELAY LOW VOLTAGE JUNCTION BOX...

Page 44: ...44 DCH COMMERCIAL 3 6 Ton Packaged Heat Pump Unit WIRING DIAGRAMS...

Page 45: ...IRE 4 ECONOMIZER PLUG LOCATED IN TH E RETURNAIR COMPARTMENT REMOVEMALEPLUG AND ATTACH FEMALEPLUG TO ECONOMIZER ACCESSORY 5 6 3 1 2 SEE NOTE 4 LOW VOLTAG E LINE VOLTAG E FIEL D WIRING LOW VOLTAG E FACT...

Page 46: ...DR PLF PM RVC RCCF TB1 TR HVDR 6 T1 C L1 EM CHR CM COMPONENT LEGEND R F 6 1 DF2 P L F 1 G T2 NOTES 1 REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL AT LEAST 105 C USE COPPER CONDUC...

Page 47: ...personal injury due to improper service procedures or services performed by an unqualified person Copyright 2015 2016 RSDX6412007r2 November2016 DCC Cooling DCH Heat Pumps Commercial Package Units wit...

Page 48: ...assistance line for dealers Outside the U S call 1 713 861 2500 Not a technical assistance line for dealers Your telephone company will bill you for the call HIGH VOLTAGE Disconnect ALL power before s...

Page 49: ...cover is not properly in place a venting terminal may discharge a combination of a hot lubricating oil and refrigerant b flammable mixture if system is contaminated with air inastreamofspraywhichmayb...

Page 50: ...Tons B Belt Drive D Direct Drive Nominal Heating Capacity Gas Electric A C H P Factory Installed Electric Heat 180 180 000 BTU h XXX No Heat 030 30 kW 1 208 230 1 60 United States 4 460 3 60 United St...

Page 51: ...e 60Hz Belt Drive Initial release of 7 5 12 5 Ton Daikin branded models DCH 090 120 XXX6BXXXAB Daikin Commercial Package Heat Pump Multiposition heat pump units 400V 3 Phase 60Hz Belt Drive with phase...

Page 52: ...50 XXX6BVXXAA Daikin Commercial Package Cooler Multiposition cooling units 400V 3 Phase 60 Hz Belt Drive Factory installed options Low Leak Downflow Economizer DCC 090 120 XXX6BXXXAB Daikin Commercial...

Page 53: ...r be obstructed If used do not allow the econo mizer manualfreshairdamper motorizedfreshairdamper to become blocked by snow or debris In some climates or locations it may be necessary to elevate the u...

Page 54: ...heunitmightoccur NOTE The unit and curb accessories are designed to allow vertical duct installation before unit placement Duct installation after unit placement is not recommended ALL CURBS LOOK SIMI...

Page 55: ...y wired for the voltage shown on the unit s data plate Main power wiring should be sized for the minimum wire ampacity shown on the unit s database Size wires in accordance with the ampacity tables in...

Page 56: ...NCE LOCATIONS Unit is equipped with a Low Voltage Terminal Block and has SinglePointwiringtothecontactororpowerblockifequipped LOW VOLTAGE CONTROL WIRING 1 A 24V thermostat must be installed for unit...

Page 57: ...l Package Cooling or Package Gas RestrictorOrificeAssemblyinCoolingOperation In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the center...

Page 58: ...OPERATION 12 Indoor Coil Accumulator Outdoor Coil Reversing Valve Energized Indoor Coil Accumulator Outdoor Coil Reversing Valve De Energized DCH XXX XXX Typical Package Heat Pump COOLING CYCLE HEATIN...

Page 59: ...n STARTUP ADJUSTMENTS AND CHECKS HIGH VOLTAGE TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK BOND THE FRAME OF THIS UNIT TO THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING TERMINAL P...

Page 60: ...k Do not attempt to change load side wiring Internal wiring assures all motors and compressors will rotate in correct directiononceevaporatorfanmotorrotationcheckhasbeen made ELECTRICAL INPUT CHECK Ma...

Page 61: ...heck heater operation if outdoor ambient is mild 15 For thermostats with emergency heat switch return to step 11 The emergency heat switch is located at the bottomofthethermostat Movetheswitchtoemerge...

Page 62: ...as completed During operation the power to the circuit board is controlled by a temperature sensor which is clamped to a feeder tube enteringtheoutdoorcoil Defrosttimingperiodsof30 60and 90 minutes ma...

Page 63: ...ionManual 14 Check condenser fans and tighten set screws FILTERS CAUTION TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON IN...

Page 64: ...d Contacts S 7 Open Control Circuit Test Control Circuit with Voltmeter S 4 Low Voltage Test Voltage S 1 Faulty Evap Fan Motor Repair or Replace S 16 Shorted or Grounded Fan Motor Test Motor Windings...

Page 65: ...A Checking Fan Blower Motor Windings PSC Motors 26 S 17 CheckingCompressorWindings 26 S 17A Resistance Test 26 S 17B GroundTest 27 S 17D OperationTest 27 S 18 Testing Crankcase Heater optional item 27...

Page 66: ...oltage tabulation as shown If the voltage falls below the minimum voltage checkthelinewiresize Longrunsofundersizedwirecan causelowvoltage Ifwiresizeisadequate notifythelocal power company in regards...

Page 67: ...ir or replace as necessary S 3B COOLING ANTICIPATOR The cooling anticipator is a small heater resistor in the thermostat During the off cycle it heats the bimetal elementhelpingthethermostatcallforthe...

Page 68: ...TACTOR CONTACTS SINGLEPHASE HIGH VOLTAGE Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury...

Page 69: ...for checking control board for single phase gas models For3phaseandbeltdrivemodels theprocedurefortesting the fan relay contacts will be the same as checking the compressor contactor contacts See sect...

Page 70: ...of the control open breaking the controlcircuitbeforethecompressormotoroverloads This control is automatically reset 1 Using an ohmmeter check across terminals of high pressure control with wire remo...

Page 71: ...shock to the servicer See the Servicing Section for specific information concerning capacitors RELAY START A potential or voltage type relay is used to take the start capacitoroutofthecircuitoncethem...

Page 72: ...ity if a terminal vents that the vaporous andliquiddischargecanbeignited spoutingflamesseveral feet causingpotentiallysevereorfatalinjurytoanyoneinits path This discharge can be ignited external to th...

Page 73: ...ve the compressorterminalprotectivecoverandinspectfor loose leads or insulation breaks in the lead wires 4 Ifnovisualproblemsindicated carefullyremovetheleads at the compressor terminals WARNING Damag...

Page 74: ...tionofthethermostatandthecontinuityoftheconnect ing wiring from the O terminal of the thermostat to the unit If voltage is registered at the coil tap the valve body lightly while switching the system...

Page 75: ...it is on the heating cycle raise the discharge pressure by restricting airflow through the indoor coil If the valve does not shift tap it lightly on both ends with a screwdriver handle DO NOT TAP THE...

Page 76: ...the system to working pressure then apply the detector to suspect areas If leaks are found repairthem Afterrepair repeatthepressuretest Ifnoleaks exist proceed to system evacuation S 102 EVACUATION WA...

Page 77: ...roper amountofrefrigerantforthesystem Allowliquidrefriger ant only to enter the high side 2 After the system will take all it will take close the valve on the high side of the charging manifold 3 Star...

Page 78: ...consideredsuperheatedwhenitstempera tureishigherthanthesaturationtemperaturecorresponding toitspressure Thedegreeofsuperheatequalsthedegrees oftemperatureincreaseabovethesaturationtemperatureat existi...

Page 79: ...60 8 6 162 0 57 0 264 0 87 4 366 0 110 4 468 0 129 0 600 0 149 0 62 10 0 164 0 57 7 266 0 87 9 368 0 110 8 470 0 129 3 604 0 149 5 64 11 3 166 0 58 4 268 0 88 4 370 0 111 2 472 0 129 7 608 0 150 1 66...

Page 80: ...0 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94 384 106 104 1...

Page 81: ...oilandliquidreturntothecompressor but the head pressure would be lower Thereareothercausesforhighheadpressurewhichmaybe found in the Service Problem Analysis Guide Ifothercausescheckoutnormal anoverch...

Page 82: ...eat of an external static pressure will result in insufficient air that can cause icing of the coil whereas too much air can cause poor humidity control and condensate to be pulled off the evaporator...

Page 83: ...be measured using a belt tension gauge available through most belt manufacturers Thecorrectdeflectionforceis5Ibs foranewbeltand3 5Ibs for a belt that has been run in New belt tension includes initial...

Page 84: ...inganddrivenmotorsheavesshouldbeinalignment with each other and the shafts parallel VL VM SHEAVES ADJUSTMENT 1 Loosen set screw B using a 5 32 Allen key 2 Making half or full turns from closed positio...

Page 85: ...ls No Barometric Relief MCCDANIEL METALS 7 5 12 5 Ton 1036610B2 Downflow Economizer ROOFTOP SYSTEMS 7 5 10 Ton 1036612B2 Downflow Economizer ROOFTOP SYSTEMS 12 5 Ton DDNSQRD9020 Downflow Square to Rou...

Page 86: ...POWER BEFORE SERVICING OR INSTALLING THIS UNIT MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH Wiring is subject to change Always refer to the...

Page 87: ...e most up to date wiring EHK4 16 BK BK RD YL RD 9 WH 8 7 6 RS BL 5 4 3 2 PC 1 BK FL HTR 3 FL FL HTR 2 HTR 1 TL TL TL RD YL PU COMPONENT CODE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LIMIT RS R...

Page 88: ...00V EHK4 30 COMPONENT CODE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LIMIT RS RELAY SEQUENCER FL FUSE LINK OP OVERLOAD PROTECTION LOW VOLTAGE WIRING CODE HIGH VOLTAGE CT CONTACTOR BK RD YL RD 9...

Page 89: ...NT TL THERMAL LIMIT RS RELAY SEQUENCER FL FUSE LINK OP OVERLOAD PROTECTION LOW VOLTAGE WIRING CODE HIGH VOLTAGE CT CONTACTOR MODEL EHK3 45 EHK4 45 EHK7 45 BK RD YL RD 9 WH 8 7 6 BL 5 4 3 2 PC 1 BK FL...

Page 90: ...44 DCC COMMERCIAL 7 5 12 5 Ton Packaged Air Conditioner Unit WIRING DIAGRAMS...

Page 91: ...BK 6 2 8 5 7 3 9 4 1 PLF 1 WH GND COLOR CODE BK BLACK BL BLUE BR BROWN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW PK PINK GR GREEN WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH...

Page 92: ...BL O O OR W2 W2 BR COMPONENT LEGEND BC CC CM CMR COMP DC DFT ECON EBTD EMR R EM FC GND HPS HVDR LPS LVDR PB PLF PM RCCF TB1 TR BLOWER CONTACTOR COMPRESSOR CONTACTOR CONDENSER MOTOR CONDENSER MOTOR REL...

Page 93: ...47 DCH COMMERCIAL 7 5 12 5 Ton Packaged Heat Pump Unit WIRING DIAGRAMS...

Page 94: ...RED WH WHITE YL YELLOW PK PINK GR GREEN WIRING CODE FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE 5 3 2 1 4 NC NO S1 S2 R C G W1 W 2 Y1 Y2 O RD PK DFT1 DFT2...

Page 95: ...RS ONLY USE N E C CLASS 2 W IRE 3 ECONOMIZER PLUG LOCA TED IN THE RETURN AIR COMPARTMENT REMOVE MALE PLUG AND ATTAC H FEMA LE PLUG TO THE ECONOMIZER ACCESSORY 4 FOR TW O STAGE OPERATION REMOVE W 1 TO...

Page 96: ...improper service procedures or services performed by an unqualified person Copyright 2015 2016 RSDX6412008r2 September 2016 DCC Cooling Commercial Package Units with R 410A Refrigerant 15 25 Tons Acce...

Page 97: ...assistance line for dealers Outside the U S call 1 713 861 2500 Not a technical assistance line for dealers Your telephone company will bill you for the call HIGH VOLTAGE Disconnect ALL power before...

Page 98: ...cover is not properly in place a venting terminal may discharge a combination of a hot lubricating oil and refrigerant b flammable mixture if system is contaminated with air inastreamofspraywhichmayb...

Page 99: ...Tons 072 6 Tons 240 20 Tons B Belt Drive 090 7 Tons 300 25 Tons D Direct Drive Nominal Heating Capacity Gas Electric A C H P Factory Installed Electric Heat 180 180 000 BTU h XXX No Heat 030 30 kW 1...

Page 100: ...oler R410A 400V 3 Phase 60 Hz Belt Drive Initial release of 15 25 Ton Daikin branded models DCC 240 300 XXX6BXXXAB Daikin Commercial Package Cooler R410A 400V 3 Phase 60 Hz Belt Drive with phase monit...

Page 101: ...across finished roof without prior approvalofownerorarchitect Donotskidorslideonanysurfaceasthismaydamage unit base The unit must be stored on a flat level surface Protect the condenser coil because i...

Page 102: ...TH FACTORY WIRING THE INTERNAL POWER AND CONTROL WIRING OF THESE UNITS ARE FACTORY INSTALLED AND HAVE BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT CONTACT YOUR LOCAL REPRESENTATIVE IF ASSISTANCE IS REQUIR...

Page 103: ...t fused Protect the powerleadsatthepointofdistributioninaccordancewith the unit data plate The unit must be electrically grounded in accordance with local codes or in the absence of local codes with t...

Page 104: ...Block and has Single Point wiring to the contactor LOW VOLTAGE CONTROL WIRING 1 A 24V thermostat must be installed for unit operation It may be purchased with the unit or field supplied Ther mostatsm...

Page 105: ...ing or Package Gas Either a thermostatic expansion valve or restrictor orifice assembly may be used depending on model refer to the parts catalog for the model being serviced DCC XXX XXX Indoor Coil O...

Page 106: ...ic cleaning is neces sary to prevent this build up from plugging the drain STARTUP ADJUSTMENTS AND CHECKS HIGH VOLTAGE TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK BOND THE FRAME OF THIS...

Page 107: ...the ranges given stated on Data Plate ELECTRICAL INPUT CHECK Make preliminary check of evaporator fan ampere draw and verify that motor nameplate amps are not exceeded A final check of amp draw shoul...

Page 108: ...are shown on the unit s nameplate To confirm charge levels or if a leak occurs and charge needs to be added to the system it is recommendedtoevacuatethesystemandrechargerefriger atetounitnameplatespec...

Page 109: ...or mationManual 14 Check condenser fans and tighten set screws FILTERS TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTE...

Page 110: ...d Contacts S 7 Open Control Circuit Test Control Circuit with Voltmeter S 4 Low Voltage Test Voltage S 1 Faulty Evap Fan Motor Repair or Replace S 16 Shorted or Grounded Fan Motor Test Motor Windings...

Page 111: ...ngCapacitor 21 S 15A Resistance Check 22 S 15B CapacitanceCheck 22 S 16 CheckingMotors 23 S 16A Checking Fan Motor Windings PSC Motors 23 S 17 CheckingCompressorWindings 23 S 17A Resistance Test 23 S...

Page 112: ...oltage tabulation as shown If the voltage falls below the minimum voltage checkthelinewiresize Longrunsofundersizedwirecan causelowvoltage Ifwiresizeisadequate notifythelocal power company in regards...

Page 113: ...ir or replace as necessary S 3B COOLING ANTICIPATOR The cooling anticipator is a small heater resistor in the thermostat During the off cycle it heats the bimetal elementhelpingthethermostatcallforthe...

Page 114: ...mtheterminal T sideofthe contactor 2 With power ON energize the contactor 3 Using a voltmeter test across terminals A L1 L2 L1 L3 and L2 L3 If voltage is present proceedtoB Ifvoltageisnotpresent check...

Page 115: ...5 5 Using a VOM check for 24 volts from terminals 3 and 4 of relay Should read 24 volts If not as above replace relay CheckingEBTDRContactOperation With power on 1 Set the thermostat to the fan on po...

Page 116: ...self with a rise in pressure The low pressure control is designed to cut out open at approximately 22 PSIG 7 PSIG It will automatically cut in close at approximately 50 PSIG 7 PSIG Test for continuity...

Page 117: ...a capacitor are a resistance and a capacitance check S 15A RESISTANCE CHECK HIGH VOLTAGE Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to...

Page 118: ...e ignited external to the compressor if theterminalcoverisnotproperlyinplaceandifthedischarge impinges on a sufficient heat source Ignitionofthedischargecanalsooccurattheventingterminal orinsidethecom...

Page 119: ...harging Carefully retest for ground directly between com pressor terminals and ground 5 If ground is indicated replace the compressor S 17D OPERATION TEST Ifthevoltage capacitor overloadandmotorwindin...

Page 120: ...applying heat to the system When repairing the refrigeration system WARNING Disconnect ALL power before servicing 1 Never open a system that is under vacuum Air and moisture will be drawn in 2 Plug o...

Page 121: ...heshutoffvalvetothe high vacuum gauge manifold only After the compound gauge lowside hasdroppedtoapproximately29inches of vacuum open the valve to the vacuum thermocouple gauge See that the vacuum pum...

Page 122: ...toolow addcharge Ifpressuresandamp draw are too high remove charge Check subcooling and superheat as detailed in the following section 5 Withthesystemstillrunning removehoseandreinstall bothvalvecaps...

Page 123: ...be is plugged 5 Capturethecharge replacethevalveanddrier evacuate andrecharge S 112 CHECKING RESTRICTED LIQUID LINE When the system is operating the liquid line is warm to the touch If the liquid line...

Page 124: ...60 8 6 162 0 57 0 264 0 87 4 366 0 110 4 468 0 129 0 600 0 149 0 62 10 0 164 0 57 7 266 0 87 9 368 0 110 8 470 0 129 3 604 0 149 5 64 11 3 166 0 58 4 268 0 88 4 370 0 111 2 472 0 129 7 608 0 150 1 66...

Page 125: ...0 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94 384 106 104 1...

Page 126: ...drop across the drier Pressure drop should not exceed 6 PSIG 7 Continue to run the system for several days repeatedly checking pressure drop across the suction line drier If thepressuredropneverexcee...

Page 127: ...es not reverse any two incoming power cables at Single Point Power Block In this case repeat bearing check Do not attempt to change load side wiring Internal wiring assures all motors and compressors...

Page 128: ...is required to meet UL requirements Accessory Number Description Model Size EHK Heater Kit 15 25 Ton DAIKIN COMMERCIAL PACKAGE UNIT ACCESSORIES Complete listing of EHK kits listed on electrical data p...

Page 129: ...he most up to date wiring EHK4 31 LOW VOLTAGE WIRING CODE HIGH VOLTAGE MODEL EHK4 31 EHK7 31 COMPONENT CODE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LIMIT RS RELAY SEQUENCER FL FUSE LINK OR NO...

Page 130: ...DE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LIMIT RS RELAY SEQUENCER FL FUSE LINK OR NON RESETTING THERMOSTAT OP OVERLOAD PROTECTION LOW VOLTAGE WIRING CODE HIGH VOLTAGE MODEL EHK4 46 EHK7 46...

Page 131: ...EHK7 60 COMPONENT CODE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LIMIT RS RELAY SEQUENCER FL FUSE LINK OR NONRESETTING THERMOSTAT OP OVERLOAD PROTECTION WH M2 M1 BK BK BK BK BK BK BK BK PU PU...

Page 132: ...CTOR HTR HEATER ELEMENT TL THERMAL LIMIT RS RELAY SEQUENCER FL FUSE LINK OR NONRESETTING THERMOSTAT OP OVERLOAD PROTECTION WH M2 M1 BK BK BK BK BK BK BK BK BK BK PU PU WH BR BL 1 PC 2 3 4 5 6 7 8 9 FL...

Page 133: ...38 DCC COMMERCIAL 15 25 Ton Packaged Air Conditioner Unit WIRING DIAGRAMS...

Page 134: ...U BR BR BR BR BR BR BR BR RD RD BL BL BL BL BL BL BL BL YL YL GR GR YL BL BL YL PU WH WH YL YL GR PU PU BL YL BL PK 0140L06195 A 400 30 60 RD BK OR RD BK OR RD BK OR RD BK PB 6 2 8 5 7 3 9 4 1 M2 G XF...

Page 135: ...TYPE AND SIZE OF OVER CURRENT PROTECTION WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW YL PK YELLOW WITH PINK STRIP BL PK BLUE WITH PINK STRIP FAC...

Page 136: ...D R D R OR BK OR BK BK BK BK BK PU PU PU PU PU PU PU PU BR BR BR BR BR BR BR BR RD RD BL BL BL BL BL BL BL BL YL YL GR GR GR YL BL BL YL PU WH WH YL YL GR PU PU BL YL YL BL PK 400V RD BK OR RD BK OR...

Page 137: ...3 CC2 T3 T1 COMP2 T2 F CM3 CC2 T1 C CC2 T3 T2 THERMOSTAT THERMOSTAT BC BC BC EM RD W1 STAT Y1 Y2 WH C G YL Y2 R C G R W1 TB1 PK GR Y1 BL O O OR 9 7 8 W2 W2 BR CF1 F CM1 C T2 T3 T1 T1 TB2 CCH CCHR 2 1...

Page 138: ...MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL USE COPPER CONDUCTORS ONLY 2 IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF BL BL SUPPLY LINE VOLTAGE 24...

Page 139: ...NOT DESIGNED FOR OTHER CONDUCTORS THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT POWER DIAGRAM DCC300 6B GND RD BK OR L1 L2 L3 T1 T2 T3 L1 L2 L3 T1 T2 T3 EM GY BL YL RD BL YL BK OR GY...

Reviews: