BLOWER PERFORMANCE DATA
NOTES:
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4%.
DCG090-102XXX*HXXXA*
HIGH STATIC BELT DRIVE - 7.5 & 8.5 TON
DCG090 DOWN SHOT HIGH STATIC BELT DRIVE
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
0.7
3575
904
1.66
0.9
3258
925
1.56
3113
909
1.41
1.1
3580 1013
1.97
3001
948
1.42
2722
915
1.25
1.3
3616 1063
2.17
3247 1019
1.79
2646
959
1.3
1.5
3275 1069
2.05
2803 1025
1.68
1.7
3346 1118
2.24
2885 1074
1.97
1.9
3009 1125
2.05
2.1
DCG090 HORIZONTAL HIGH STATIC BELT DRIVE
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
0.7
3567
903
1.58
0.9
3596
953
1.79
3145
906
1.39
1.1
3630 1007
1.97
3168
963
1.56
2675
909
1.18
1.3
3649 1063
2.19
3255 1021
1.8
2724
965
1.35
1.5
3316 1068
2
2823 1058
1.61
1.7
3287 1112
2.16
2869 1074
1.78
1.9
2970 1122
2
2.1
2644 1133
1.92
DCG102 HORIZONTAL HIGH STATIC BELT DRIVE
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
0.7
3417
900
1.55
0.9
3446
950
1.76
2995
903
1.36
1.1
3480 1004
1.94
3018
960
1.53
2525
906
1.15
1.3
3499 1060
2.16
3105 1018
1.77
2574
962
1.32
1.5
3166 1065
1.97
2673 1055
1.58
1.7
3137 1109
2.13
2719 1071
1.75
1.9
3107 1154
2.28
2820 1119
1.97
2.1
2790 1164
2.12
DCG102 DOWN SHOT HIGH STATIC BELT DRIVE
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
CFM
RPM
BHP
CFM RPM
BHP
0.7
3425
901
1.63
0.9
3108
922
1.53
2963
906
1.38
1.1
3430 1010
1.94
2851
945
1.39
2572
912
1.22
1.3
3466 1060
2.14
3097 1016
1.76
2496
956
1.27
1.5
3125 1066
2.02
2653 1022
1.65
1.7
3196 1115
2.21
2735 1071
1.94
1.9
3251 1160
2.36
2859 1122
2.02
2.1
2914 1167
2.17
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
5
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4
5
DO NOT
OPERATE
DO NOT
OPERATE
ESP, In
H
2
O
TURNS OPEN
0
1
2
3
4