background image

7 Installation

Installation manual

9

DCC601A51
intelligent Tablet Controller
4P414342-1D – 2020.12

f

A maximum of 32 indoor units can be connected (a
unique DIII address is required for each unit).

To connect digital input and output devices

The  intelligent  Tablet  Controller  can  be  connected  with  an  external
signal input device for stopping air conditioners, with electric energy
meters  for  calculating  the  electricity  usage  of  individual  air
conditioners or other devices.

1

Connect  the  contact  input  lines  or  pulse  input  lines  to  the  Di1,
Di2,  Di3,  Di4  and  COM  terminals  of  the  connector  on  the
bottom  of  the  I/O  module.  The  function  of  each  terminal  is  as
shown in the following figure.

Schematic wiring diagram with Di and Do terminals

Di1

Di2 COM Di3 Di4 COM

COM

Do

a

b

c

a

[Di1]

 Forced stop contact input (normally open).

b

[Di2] [Di3] [Di4]

 Digital inputs. Can be configured as

normally open (A-type) or normally closed (B-type)
contact inputs, or as pulse inputs.

c

[Do]

 Provided for future use.

You can change the function assignment at a later time.

For  more  details  on  the  required  pulse  width  and  interval,  refer  to

"7.2.1 Wiring requirements"

 [

4

 7].

INFORMATION

At  the  time  of  writing,  the  digital  output  connection  Do  is
NOT active, but provided for future use.

NOTICE

▪ When  the  forced  stop  contact  input  is  closed,  a  stop

signal is sent to all connected devices. There is no hard
guarantee that all devices have effectively stopped and
remain stopped during the time the forced stop contact
input is active.

▪ When  the  forced  stop  contact  input  is  closed,  the

connected  devices  cannot  be  restarted  unless  the
contact input is reopened.

NOTICE

▪ The  COM  terminals  are  all  connected  internally.  So,

you  can  use  any  one  of  them.  However,  you  can  only
connect  up  to  2  wires  simultaneously  to  each  COM
terminal.

▪ If applicable, connect the I/O module’s COM terminal to

the negative side of the device terminals.

7.2.3

Connecting the power supply to all
modules

For all wiring requirements see 

"7.2.1 Wiring requirements"

 [

4

 7].

To connect the power supply to all modules

1

Connect the power supply to the 3 terminals, L (live), N (neutral)
and ground in the input section of the WAGO power supply unit
(PSU).

INFORMATION

Use a flat-head screwdriver to manipulate the WAGO PSU
cage clamp as described below, so that the wires are fixed
to the power supply.

a

b

c

a

 Place the screwdriver in the upper clamp entry and place

it above the clamp.

b

  Push  the  clamp  downwards  by  pivoting  the  screwdriver

in direction 'b', so that the lower clamp entry opens.

c

 Put the wire in the respective lower clamp entry.

2

Connect  the  DC  output  of  the  WAGO  PSU  to  the  DC  input  of
the CPU module. Take the polarity of the wires into account.

3

Plug  the  A-type  plug  of  the  USB  cable  in  the  rightmost  USB
socket on the CPU module. This socket is marked "I/O IF".

4

Plug the B-type plug of the USB cable in the B-type USB socket
on the I/O module.

5

Provide  an  earth  connection  to  the 

  terminal  of  the  CPU

module, using one of the following 2 options:

▪ connect  the  terminal  to  the  earth  rail  bar  of  the  electrical

cabinet (if provided), or

▪ connect the terminal to the M3 earthing screw on the bottom

face of the WAGO PSU.

USB

230 V AC

POWER

I/O IF

CPU IF

24 V DC

+ + - -

L N

CPU

I/O

NOTICE

If  you  want  to  connect  the  earth  wire  to  the  WAGO  PSU,
you  can  only  use  a  stranded  wire  with  a  crimp-style
terminal on the tip of the wire.

Place the round crimp-style terminal on the wire up to the
insulated  part  and  fasten  the  terminal  with  a  Phillips
screwdriver.

b

a

a

 Stranded conductor wire

b

 Round crimp-style terminal

Summary of Contents for DCC601A51

Page 1: ...Installation manual intelligent Tablet Controller English Installation manual intelligent Tablet Controller DCC601A51 ...

Page 2: ...t audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Preparation of the installation reference data Format Digital files on http www daikineurope com support and manuals product information Latest revisions of the supplied ...

Page 3: ... performed in accordance with the wiring diagram supplied with the product Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required fuses or circuit breakers Make sure to inst...

Page 4: ...ller kit see 10 5 Schematic setup of the intelligent Tablet Controller 4 11 Before installing the intelligent Tablet Controller kit modules draw up an efficient plan of work using this schematic and based on the real environment it needs to be installed in 5 3 Compatible Daikin equipment The intelligent Tablet Controller solution can connect to certain Daikin units that provide a DIII NET communic...

Page 5: ...ments Location Indoor inside an electrical cabinet The electrical cabinet must be lockable or designed to be opened only with a special tool The key or tool should be available only to service personnel must be installed in a space with no access for the general public must comply with the applicable legislation must have ingress protection class of IP4X or higher however make sure enough ventilat...

Page 6: ...itches a RESET Button for restarting the CPU module and I O module k DIP SW Reserved for servicing Factory default all switches are set to OFF OFF n BACKUP Switch for turning on off the backup power supply for retaining the current settings provided by the internal battery Factory default OFF OFF This will be set to the ON ON position during commissioning q Lever To assist mounting dismounting the...

Page 7: ...perating condition CPU ALIVE ALARM Normal Blink OFF Hardware failure OFF ON Power interruption OFF OFF Communication failure between CPU module and I O module for 10 seconds or more ON Blink 7 Installation 7 1 Installation of the intelligent Tablet Controller hardware The intelligent Tablet Controller components are to be mounted onto a 35 mm DIN rail inside an electrical cabinet For more informat...

Page 8: ...on terminal sized for maximum 4 mm According to applicable legislation Solid or stranded wire allowed The internal protection of the WAGO PSU is fused at 2 5 A 250 V 24 V DC power supply to the CPU module According to applicable legislation Solid or stranded wire allowed USB cable 5 m Commercial USB 2 0 cable type A to type B connector provided in the intelligent Tablet Controller kit a Total leng...

Page 9: ...ternally So you can use any one of them However you can only connect up to 2 wires simultaneously to each COM terminal If applicable connect the I O module s COM terminal to the negative side of the device terminals 7 2 3 Connecting the power supply to all modules For all wiring requirements see 7 2 1 Wiring requirements 47 To connect the power supply to all modules 1 Connect the power supply to t...

Page 10: ...e data backup battery Both intelligent Tablet Controller modules are marked with the following symbol This means that electrical and electronic products may not be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable...

Page 11: ...chematic setup of the intelligent Tablet Controller USB 230 V AC RJ 45 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 OUT IN F1 F2 http cloud daikineurope com DIII NET POWER I O IF CPU IF LAN F1 F2 Di1 Di4 d e f i i i h j k 24 V DC c b g a l l L N a WAGO power supply unit b CPU module c I O module d Optional Daikin supplied tablet e Daikin Cloud Service f Daikin Cloud Service g LAN gateway optional Dai...

Page 12: ...4P414342 1D 2020 12 Copyright 2015 Daikin 4P414342 1 D 0000000Y Verantwortung für Energie und Umwelt ...

Reviews: