Daikin D2C20ND028A5AA Installation Manual Download Page 22

4 Installation

Installation manual

22

D2C20ND0 D2C24ND035A5AA

Wall-mounted condensing boiler

3P469346-10J – 2018.05

Flue part

Order code

90° elbow 60 mm

DR90ELBOW60AA

45° elbow 60 mm

DR45ELBOW60AA

Extension duct 60 mm

500 mm

DREXDUC0500AA

1000 mm

DREXDUC1000AA

B33 flue kit

DRB33FLUKITAA

4.8.11

Guidelines when connecting LAN adapter

To connect the router

Connect the LAN adapter to the router using the Ethernet cable.

NOTICE

To  prevent  communication  problems  due  to  cable
breakdown do not exceed the minimum bend radius of the
ethernet cable.

Configurations

NOTICE

In  order  to  use  the  app  “Daikin  Online  Control  Heating”,
Daikin Room Thermostat must be connected to the boiler.

Overview

Get the app “Daikin Online Control Heating”.

The adapter and the “device” running the app (smartphone or tablet)
should  be  connected  to  the  same  router  in  order  to  be  able  to
discover the unit.

The boiler needs to be powered during the configuration.

Follow the steps below;

Power on the unit

The green LED is blinking slowly when the adapter is powered and
no error occurs.

The  yellow  LED  shows  communication  activity  to  the  router  and  to
the unit.

Launch the app

Run the app “Daikin Online Control Heating”.

Agree with the terms of use

When launching the app for the first time, the terms of use needs to
be  accepted.  After  this,  the  app  can  be  used.  Accept  is  enabled
when reaching the bottom of the page.

The app discovers the unit

In case the adapter firmware is not up to date, the unit is shown with
next to it the download button.

If  the  adapter  firmware  is  up  to  date,  then  no  adapter  upgrade  is
required and the “space heating” and “domestic hot water” units are
shown.

Update adapter firmware

Tap the “Update” to start the update process. When the app finalizes
the  update  the  next  screen  with  the  current  firmware  version
appears.  It  will  take  some  time  before  the  adapter  finalized  the
firmware reboot process.

Expected unit overview

The “Home screen” is displayed, listing up the available units.

Remarks;

The  overview  below  depends  on  the  boiler  type.  E.g.  for  a  boiler
without  domestic  hot  water  unit,  only  the  space  heating  unit  will  be
visible.

If  not  only  a  boiler  but  also  e.g.  an  Altherma  heat  device  is
connected in the same local network (same router), then the app will
also display the Altherma related units.

In  case  of  more  than  1  boiler  connected  to  the  same  network,  all
boiler units will be visible.

Update adapter date / time

1

Start the app and go to the Home screen.

2

Tap on settings (top-right of screen), the LAN adapter time and
date are displayed.

3

Tap on “Time”, this will bring up a dialog.

4

Confirm the update by tapping “Yes”.

Updating firmware

You  can  update  the  LAN  adapter  firmware  using  the  Daikin  Online
Controller Heating App.

When  the  app  is  opened,  In  case  the  adapter  firmware  is  not  up  to
date, the unit is shown with next to it the download button.

Tap the “Update” to start the update process. When the app finalized
the  update  the  next  screen  with  the  current  firmware  version
appears.  It  will  take  some  time  before  the  adapter  finalized  the
firmware reboot process.

Factory reset

1

Open  unit  control  app  run  the  app  Daikin  Online  Control
Heating.

2

Tap on settings.

3

Tap on “Factory reset”.

4

Confirm the update request by tapping OK.

After successful reset, the adapter reboots.

Troubleshooting

LED indication

2  status  LED’s  are  available  and  positioned  next  to  the  LAN
connector.

Status

Green LED

Yellow LED

Normal operation

Pulse every 2

seconds

-

LAN communication

-

Lights up when

communication is

active

Adapter error

Fast blinking

Fast blinking

Upgrade busy

Slow blinking

Slow blinking

Summary of Contents for D2C20ND028A5AA

Page 1: ...Installation manual Wall mounted condensing boiler English Manuel d installation Chaudi re murale condensation Fran ais Installation manual Wall mounted condensing boiler D2C20ND028A5AA D2C24ND035A5AA...

Page 2: ...tiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lie...

Page 3: ...commission the domestic hot water 25 6 Hand over to the user 25 Disposal Old units must be appropriately disposed of in accordance with local and national regulations The components are easy to separa...

Page 4: ...ualified person shall explain the operating principles and the use of the unit to the user The user is not allowed to perform any modifications maintenance or repairs on the unit unless otherwise stat...

Page 5: ...llation Automatic air vents There are two air vents one on the pump other on the heat exchanger They help discharging the air inside the installation and heating circuit to avoid air traps and consequ...

Page 6: ...vessel 10 litres d Gas valve e Heat exchanger f 3 way valve stepper motor g Domestic hot water temperature sensor h Plate heat exchanger i Safety valve 3 bar j Condensate trap k Ignition transformer...

Page 7: ...min max m h 0 51 2 04 0 51 2 45 Natural Gas G25 Consumption min max m h 0 59 2 35 0 59 2 85 LPG G31 Consumption min max m h 0 2 0 98 0 2 1 19 Combustion products mass flow rate min max G20 g s 2 2 12...

Page 8: ...60 C return temperature at heater inlet and 80 C flow temperature at heater outlet b Low temperature means for condensing boilers 30 C for low temperature boilers 37 C and for other heaters 50 C retur...

Page 9: ...room or compartment it does not require a dedicated ventilation for combustion air If however installed in a room containing a bath or a shower then particular reference is drawn to the current I E E...

Page 10: ...3 m 1 5 bar h h System water height m p System charge pressure bar According to the graph below there is no need to install an additional expansion vessel for the systems with a water volume in the ar...

Page 11: ...central heating circuit 0 0 100 200 300 400 500 600 700 800 200 400 600 800 1000 1200 1400 1600 1800 A mbar B l h A Residual pump lift mbar B Flow l h 4 8 Connections NOTICE During installation do no...

Page 12: ...onger than 1 5 metres The safety valve piping should be connected to a water outlet with an additional hose or piping This outlet should not be installed in places where there is risk of freezing nor...

Page 13: ...b a L N a b WARNING Do not interchange the supply conductors L and the neutral conductor N DANGER Do not use gas and water pipes for earthing purposes and ensure that they have not been used for this...

Page 14: ...C20ND028A5AA D2C24ND035A5AA Wall mounted condensing boiler 3P469346 10J 2018 05 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing...

Page 15: ...temperature sensor Ext1 X8 BCC Boiler Chip Card Ext2 X10 Personal computer production interface Ext3 X1M Daikin room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1...

Page 16: ...The boiler must be installed so that the terminal is exposed to external air Position of the terminal must allow the free passage of air across it at all times Pluming may occur at the flue terminal P...

Page 17: ...flue length value Flue length determination Flue duct length L is measured from lip of the elbow to end of the flue terminal L a L Flue duct length a Distance of outer lip of terminal to outer wall a...

Page 18: ...e flex boiler connection set 100 or 130 b Extension 60 mm c Chimney connection 60 100 d Elbow 60 100 90 Optional e 90 elbow 60 100 f 45 elbow 60 100 g Inspection elbow 60 100 h 30 elbow 60 100 i Exten...

Page 19: ...45 elbow 80 mm 1 0 m 90 elbow 80 mm 2 0 m Subtract equivalent length value of bends from the allowable flue length value Note The air intake length is 3 metres In case of longer air intake use flue o...

Page 20: ...ular and rough 140 18 2 53 5 Allowable flue length for C93x DN 80 Flex circular and rough 130 11 6 34 1 DN 80 Flex circular and rough 120 4 4 13 0 DN 80 Flex square and rough 140 23 8 69 9 DN 80 Flex...

Page 21: ...FGP4661 45 elbow 80 125 EKFGP4811 30 elbow 60 100 EKFGP4664 30 elbow 80 125 EKFGP4814 Extension duct 60 100 500 mm EKFGP4651 1000 mm EKFGP4652 Extension duct 80 125 500 mm EKFGP4801 1000 mm EKFGP4802...

Page 22: ...t the update process When the app finalizes the update the next screen with the current firmware version appears It will take some time before the adapter finalized the firmware update reboot process...

Page 23: ...e opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting 9 If after the venting the pressure decreases below 0 8 bar re...

Page 24: ...outlet 5 2 Gas air ratio No need to adjust The installer does not have to adjust the gas air ratio because the boiler has an electronic gas adaptive feature 5 3 To check for gas leakage DANGER Before...

Page 25: ...weeper mode again press Cancel and Menu buttons together five seconds Sweeper mode will be deactivated and boiler will return to normal operation mode Sweeper mode also finishes automatically after 15...

Page 26: ...e en service de l eau chaude sanitaire 49 6 Remise l utilisateur 49 Mise au rebut Les anciennes unit s doivent tre mises au rebut correctement conform ment aux r glements locaux et nationaux Les compo...

Page 27: ...r L utilisateur n est pas autoris effectuer une quelconque modification maintenance ou r paration de l unit sauf mention contraire ou demander des tiers non agr s d effectuer de telles actions Sinon l...

Page 28: ...Purgeurs d air automatiques Il y a deux purgeurs d air un sur la pompe et un autre sur l changeur de chaleur Ils aident d charger l air l int rieur de l installation et du circuit de chauffage afin d...

Page 29: ...r pas pas de vanne 3 voies g Capteur de temp rature d eau chaude sanitaire h changeur de chaleur plaques i Vanne de s curit 3 bar j Purgeur de condensat k Transformateur d allumage l Capteur de temp r...

Page 30: ...in max m h 0 51 2 04 0 51 2 45 Consommation de gaz naturel G25 min max m h 0 59 2 35 0 59 2 85 Consommation de GPL G31 min max m h 0 2 0 98 0 2 1 19 D bit de masse de produits de combustion min max G2...

Page 31: ...de retour de 60 C l entr e du chauffage et une temp rature du d part de 80 C la sortie du chauffage b Une temp rature faible signifie 30 C pour les chaudi res condensation 37 C pour les chaudi res bas...

Page 32: ...la mesure applicable Reportez vous la section Espacements d installation minimaux la page 32 Si la chaudi re est install e dans une pi ce ou un compartiment une a ration s par e pour l air comburant n...

Page 33: ...rature de l eau qui circule dans le circuit La d termination de la hauteur d eau du syst me et de la pression de charge du syst me concern e est indiqu e ci dessous h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0...

Page 34: ...Graphique de rel vement de pompe r siduel Le graphique de rel vement de pompe r siduel montre la quantit de rel vement de pompe mbar qui reste pour le circuit de chauffage central 0 0 100 200 300 400...

Page 35: ...ges Le circuit de chauffage central doit tre capable de r sister une pression d au moins 6 bar Le branchement crois doit tre privil gi dans les radiateurs d une longueur sup rieure 1 5 m tre La tuyaut...

Page 36: ...idement Le c ble d alimentation lectrique doit tre au minimum quivalent H05RN F 2451EC57 Conformez vous au point ci dessous lors du c blage au bloc de bornes d alimentation b a L N a b AVERTISSEMENT N...

Page 37: ...2C24ND035A5AA Chaudi re murale condensation 3P469346 10J 2018 05 4 8 6 Sch ma de c blage DANGER RISQUE D LECTROCUTION D branchez l alimentation lectrique pendant plus de 10 minutes avant d effectuer l...

Page 38: ...ce pour chaudi re Ext2 X10 Interface de production pour ordinateur personnel Ext3 X1M Thermostat d ambiance Daikin Ext4 X2M Sortie d alimentation ext rieure 230 V c a Ext5 X2M R serv pas en usage X1M...

Page 39: ...r rapport aux ouvertures pour l a ration doivent tre conformes aux r glementations nationales La chaudi re doit tre install e de mani re exposer le terminal l air externe La position du terminal doit...

Page 40: ...gment e jusqu 19 9 m tres en r glant le param tre C3 sur 5 Reportez vous aux consignes d entretien pour cette op ration La longueur de ventouse 80 125 peut tre augment e jusqu 99 m tres en r glant le...

Page 41: ...une valeur de longueur de coudes quivalente de la valeur de longueur de ventouse admissible Syst me de ventouse 80 125 mm Pour augmenter la longueur de conduit de combustion maximale admissible vous p...

Page 42: ...ion maximale autoris e entre l entr e d air comburant et la sortie de gaz de combustion y compris les pressions du vent 185 Pa pour les mod les D2C T ND028 et D2C T ND035 D bit de masse minimale des p...

Page 43: ...oivent tre obtenus par l interm diaire de Daikin Dans les unit s de type C83x le flux de condensat n est pas admis dans l unit a b d c d f g L h e a Plaque murale b Rallonge 80 mm c Adaptateur 60 100...

Page 44: ...yez une valeur de longueur de coudes quivalente de la valeur de longueur de ventouse admissible Type B53 syst me de ventouse ouverte La chaudi re aspire de l air comburant de la pi ce d installation e...

Page 45: ...54 60 130 EKFGS0257 Raccord de chemin e 60 100 EKFGP4678 80 125 EKFGS4828 Kit de terminal pour toit 80 mm EKFGP6864 Coude 80 mm de 90 EKFGW4085 Coude 80 mm de 45 EKFGW4086 Conduit de rallonge de 80 mm...

Page 46: ...vous dans l cran d accueil 2 Appuyez sur les r glages partie sup rieure droite de l cran pour afficher l heure et la date de l adaptateur LAN 3 Appuyez sur Heure pour afficher une fen tre de dialogue...

Page 47: ...8 bar 10 R glez la vanne 8 sur la position arr t D montez la boucle de remplissage si les r glementations locales l exigent 11 V rifiez que le circuit de chauffage central les raccords du circuit en...

Page 48: ...combustion de la chaudi re 5 2 Rapport gaz air R glage non n cessaire L installateur ne doit pas r gler le rapport gaz air car la chaudi re dispose d une fonctionnalit de gaz adaptatif lectronique 5 3...

Page 49: ...ouveau les boutons Annuler et Menu appuy s ensemble pendant cinq secondes Le mode ramoneur se d sactive et la chaudi re repasse au mode de fonctionnement normal Le mode ramoneur s arr te aussi automat...

Page 50: ......

Page 51: ......

Page 52: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 10J 2018 05...

Reviews: