SiUS121632EA
Service Diagnosis
Service Diagnosis
129
3.2.2 Wireless Remote Controller Kit (BRC082A41W, BRC082A42W(S))
Relations
Between Modes
The following modes can be selected by using
INSPECTION/TEST OPERATION
button on the
remote controller.
Service
Diagnosis
To find the error code, proceed as follows:
(R24049)
Press
INSPECTION/TEST
OPERATION
button for
more than 4 seconds.
Press
INSPECTION/TEST
OPERATION
button once.
Field
setting
mode
Service
mode
Normal
mode
Test
operation
mode
Inspection
mode
Press
INSPECTION/TEST
OPERATION
button once.
Press
INSPECTION/TEST
OPERATION
button for more
than 4 seconds.
Indoor unit settings can be made.
z
Filter cleaning sign time
z
Others
Following codes can be checked.
z
Error codes
z
Indoor model code
Service data can be obtained.
z
Error code history
z
Temperature data of various sections
Service settings can be made.
z
Forced fan ON
z
Airflow rate setting
Press
INSPECTION/
TEST OPERATION
button once.
Press
ON/OFF
button within 10 seconds
to start test operation.
Test operation will stop automatically
after 15~30 minutes.
Thermostat is forcibly turned on.
After 60
seconds
Press
INSPECTION/TEST
OPERATION
button once.
After 10 seconds without starting test operation
or press
INSPECTION/TEST OPERATION
button once
or 30 min. after the test operation start
Step
Action
1
Press
INSPECTION/TEST OPERATION
button to enter the inspection mode. Then the
figure
0
blinks on the UNIT No. display.
(R24050)
INSPECTION/TEST
OPERATION
button